Emerson NX manual Load on Bypass, Load on bypass, UPS available

Page 21

Operation

2.4.1Load on Bypass

In this operating mode, the connected loads are supplied from line power via the Static Bypass Switch. The Static Bypass Switch is used to provide power to the loads. If an overload or short-circuit on UPS output occurs, the Static Bypass Switch is automatically activated to provide uninterrupted power to the loads. The Bypass operating condition is displayed. From this operating mode, the UPS automatically reverts to on-line operation after the fault is corrected. Bypass operation can also be specifically selected from the control panel using the push button.

Load on Bypass is shown in Figure 13. The UPS system could be in this mode of operation during either initial startup or UPS system shutdown or isolation for maintenance.

NOTICE

Risk of unexpected power loss. Can cause equipment damage.

When the critical load is being supplied power from the bypass line, the load is vulnerable to utility failure and fluctuations.

Figure 13 Load on bypass

Module Bypass

AC Input

BFB

Module Rectifier

AC Input

DC

Bus

To DC Supply

UPS Module

UPS Output

Critical

 

Load

Figure 14 Load on bypass, UPS available

Module Bypass

 

AC Input

 

 

BFB

Module Rectifier

DC

AC Input

 

Bus

UPS Module

UPS Output Critical

Load

To DC Supply

Figure 15 Load on UPS, bypass available

Module Bypass

 

AC Input

 

 

BFB

Module Rectifier

DC

AC Input

 

Bus

UPS Module

UPS Output Critical

Load

To DC Supply

15

Liebert®NX

Image 21
Contents Liebert NX Product Warranty Registration Table of Contents Maintenance SpecificationsOptions Figures Page Important Safety Instructions Battery Cabinet Precautions General Description Typical single module UPS system one-line diagramBypass Mode Normal ModeBattery Mode Maintenance BypassOptions Main component locations-225 to 300kVA Liebert NX FeaturesFront Doors Removed Main display screen, typical Touchscreen Navigation Main Display ScreenSystem Status Status Rectifier Bypass Inverter Chg/Boost Battery LoadEvents Log Menu Measures MenuBattery Menu Battery StatusBattery Test Battery parameters Battery MeasuresLife menu Life MenuAnimated One Line Mimic Settings MenuRectifier Functional Block About MenuLoad on bypass, UPS available Load on BypassOff DC Source Input Power Failure-Load on DC SourceManual Operations-All Systems Remote Emergency Power OffStartup-Single Module System Startup-1+N System Transfer Procedure Retransfer ProcedureLoad Transfer and Retransfer-Single Module System 6 1+N System Transfer load from UPS to Bypass 7 1+N System Transfer load from Bypass to UPS Shut Down-Single Module UPS System9 1+N System Shutdown Load Transfer-1+N System Add a UPS to the System Collective Load Transfer-1+N System Remove a UPS from System CollectiveAutomatic Operations Overloads Without TransferCurrent-versus-time curves of overload capacity Automatic Transfers to Bypass Overload Condition Automatic Transfers to Bypass, UPS System FaultsAutomatic Retransfers to UPS MopUPS Shutdown and Monitoring Software Remote Alarm UnitManage UPS Adapter ConnectivityConnectivity combinations Available Selectable Output Contacts Available Selectable Input ContactsSafety Precautions Maintenance Agreements The Signature Program Liebert ServicesProfessional Startup TrainingRoutine Maintenance Record LogAir Filters UPS component service life Battery MaintenanceLimited Life Components Component Expected Life ReplaceBattery Safety Precautions Battery voltage, nominal and float Matching Battery Cabinets-OptionalBattery Voltage, VDC Number of Cells Nominal Float 240 480 527Battery Mfr Battery Model # In-lb N-m Battery retorque valuesOther DC Sources Retorque ValueUpstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemDetecting Trouble Items to check includeEnvironmental specifications Battery OperationDC Sources Other DC SourcesPhysical specifications Electrical specificationsSpecifications LiebertNX Page Is t Ne tTwor k Care