Emerson NX manual Safety Precautions

Page 36

Maintenance

4.0MAINTENANCE

4.1Safety Precautions

Observe the safety precautions in Battery Cabinet Precautions on page 2.

Observe all of the warnings below before performing any maintenance on the UPS and associated equipment. Also observe the manufacturer’s safety precautions pertaining to the DC source, along with the DC source safety precautions in this section.

NOTE

Service and maintenance work must be performed only by properly trained and qualified personnel and in accordance with applicable regulations as well as with manufacturers’ specifications.

! WARNING

Risk of electric shock and high short circuit current. Can cause equipment damage, personal injury and death.

• Extreme caution is required when performing maintenance.

• Be constantly aware that the UPS system contains high DC as well as AC voltages. With input power Off and the DC source disconnected, high voltage at filter capacitors and power circuits should be discharged within 5 minutes. However, if a power circuit failure has occurred, you should assume that high voltage may still exist after shutdown. Check with a voltmeter before making contact.

• AC voltage will remain on the bypass and output circuit breakers and the static bypass switch, unless associated external circuit breakers are opened.

• Check for voltage with both AC and DC voltmeters prior to making contact.

• When the UPS system is under power, both the operator and any test equipment must be isolated from direct contact with earth ground and the UPS chassis frame by using rubber mats.

• Some components within the cabinets are not connected to chassis ground.

• Any contact between floating circuits and the chassis is a lethal shock hazard. Use differential oscilloscopes when measuring a floating circuit.

• Exercise caution that the test instrument exterior does not make contact, either physically or electrically, with earth ground.

• In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or others approved for use in fighting electrical fires.

! WARNING

Risk of electric shock and high short circuit current. Can cause equipment damage, personal injury and death.

Always identify connecting wiring prior to disconnecting any wiring.

Do not substitute parts except as authorized by Emerson® Corporation.

Maintain the UPS cabinets free of foreign materials such as solder, wire cuttings, etc.

Contact Liebert Services if you are not sure of the procedures to follow or if you are unfamiliar with the circuitry.

Liebert®NX

30

Image 36
Contents Liebert NX Product Warranty Registration Table of Contents Maintenance SpecificationsOptions Figures Page Important Safety Instructions Battery Cabinet Precautions Typical single module UPS system one-line diagram General DescriptionNormal Mode Bypass ModeBattery Mode Maintenance BypassOptions Features Main component locations-225 to 300kVA Liebert NXFront Doors Removed Main display screen, typical Touchscreen Navigation Main Display ScreenSystem Status Rectifier Bypass Inverter Chg/Boost Battery Load StatusEvents Log Menu Measures MenuBattery Menu Battery StatusBattery Test Battery Measures Battery parametersLife Menu Life menuSettings Menu Animated One Line MimicRectifier Functional Block About MenuLoad on Bypass Load on bypass, UPS availableInput Power Failure-Load on DC Source Off DC SourceRemote Emergency Power Off Manual Operations-All SystemsStartup-Single Module System Startup-1+N System Transfer Procedure Retransfer ProcedureLoad Transfer and Retransfer-Single Module System 6 1+N System Transfer load from UPS to Bypass 7 1+N System Transfer load from Bypass to UPS Shut Down-Single Module UPS System9 1+N System Shutdown Load Transfer-1+N System Remove a UPS from System Collective Load Transfer-1+N System Add a UPS to the System CollectiveAutomatic Operations Overloads Without TransferCurrent-versus-time curves of overload capacity Automatic Transfers to Bypass, UPS System Faults Automatic Transfers to Bypass Overload ConditionAutomatic Retransfers to UPS Remote Alarm Unit MopUPS Shutdown and Monitoring SoftwareManage UPS Adapter ConnectivityConnectivity combinations Available Selectable Input Contacts Available Selectable Output ContactsSafety Precautions Liebert Services Maintenance Agreements The Signature ProgramProfessional Startup TrainingRoutine Maintenance Record LogAir Filters Battery Maintenance UPS component service lifeLimited Life Components Component Expected Life ReplaceBattery Safety Precautions Matching Battery Cabinets-Optional Battery voltage, nominal and floatBattery Voltage, VDC Number of Cells Nominal Float 240 480 527Battery retorque values Battery Mfr Battery Model # In-lb N-mOther DC Sources Retorque ValueReporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsDetecting Trouble Items to check includeBattery Operation Environmental specificationsDC Sources Other DC SourcesElectrical specifications Physical specificationsSpecifications LiebertNX Page Ne t Is tTwor k Care