Emerson NX manual Automatic Retransfers to UPS

Page 32

Operation

2.6.4Automatic Retransfers to UPS

The following critical bus conditions must be present to initiate an automatic retransfer of the critical load from the bypass source to the UPS inverter:

1.Critical load was initially transferred to the bypass source due to a system overload only. A manual retransfer from bypass is required if the transfer to bypass was caused by any condition other than output overload.

2.Overload has since dropped below 95% of the rated load.

3.Both the Input and the DC source (MBD) circuit breakers have remained closed since the overload transfer.

4.OK to Transfer signal received from the control logic for at least 10 seconds, within 5 minutes of the system overload transfer. A manual retransfer from bypass is required for overloads lasting 5 minutes or more.

5.Cyclic-type overloads, which occur up to five (select range is 0 to 5) times in 60 minutes, are automatically returned to the inverter for each event including the Nth overload.

NOTE

If you do not want the UPS system to initiate any automatic retransfers, this can be set during the initial commissioning or by calling your local Liebert Services representative.

Liebert®NX

26

Image 32
Contents Liebert NX Product Warranty Registration Table of Contents Options MaintenanceSpecifications Figures Page Important Safety Instructions Battery Cabinet Precautions Typical single module UPS system one-line diagram General DescriptionNormal Mode Bypass ModeBattery Mode Maintenance BypassOptions Features Main component locations-225 to 300kVA Liebert NXFront Doors Removed Main display screen, typical System Status Touchscreen NavigationMain Display Screen Rectifier Bypass Inverter Chg/Boost Battery Load StatusEvents Log Menu Measures MenuBattery Test Battery MenuBattery Status Battery Measures Battery parametersLife Menu Life menuSettings Menu Animated One Line MimicRectifier Functional Block About MenuLoad on Bypass Load on bypass, UPS availableInput Power Failure-Load on DC Source Off DC SourceRemote Emergency Power Off Manual Operations-All SystemsStartup-Single Module System Startup-1+N System Load Transfer and Retransfer-Single Module System Transfer ProcedureRetransfer Procedure 6 1+N System Transfer load from UPS to Bypass 9 1+N System Shutdown 7 1+N System Transfer load from Bypass to UPSShut Down-Single Module UPS System Load Transfer-1+N System Remove a UPS from System Collective Load Transfer-1+N System Add a UPS to the System CollectiveCurrent-versus-time curves of overload capacity Automatic OperationsOverloads Without Transfer Automatic Transfers to Bypass, UPS System Faults Automatic Transfers to Bypass Overload ConditionAutomatic Retransfers to UPS Remote Alarm Unit MopUPS Shutdown and Monitoring SoftwareConnectivity combinations Manage UPS AdapterConnectivity Available Selectable Input Contacts Available Selectable Output ContactsSafety Precautions Liebert Services Maintenance Agreements The Signature ProgramProfessional Startup TrainingAir Filters Routine MaintenanceRecord Log Battery Maintenance UPS component service lifeLimited Life Components Component Expected Life ReplaceBattery Safety Precautions Matching Battery Cabinets-Optional Battery voltage, nominal and floatBattery Voltage, VDC Number of Cells Nominal Float 240 480 527Battery retorque values Battery Mfr Battery Model # In-lb N-mOther DC Sources Retorque ValueReporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsDetecting Trouble Items to check includeBattery Operation Environmental specificationsDC Sources Other DC SourcesElectrical specifications Physical specificationsSpecifications LiebertNX Page Ne t Is tTwor k Care