Emerson NX manual Manual Operations-All Systems, Remote Emergency Power Off

Page 23

Operation

2.4.4Remote Emergency Power Off

The Remote Emergency Power Off control is a user-provided switch located remotely from the UPS system. It usually is installed in the same room as the critical load equipment. This mode can also be initiated by an automatic contact closure in the same external circuit as the manually operated switch.

When the Remote Emergency Power Off switch is operated, the UPS will shut down and open bypass circuit breakers. All power through the UPS is removed from the load. Typically, the REPO circuit also opens the circuit breakers that provide power to the bypass lines and the UPS controls. Refer to 2.5.8 - Shut Down-Single Module UPS System.

Figure 18 Remote Emergency Power Off

Module Bypass

AC Input

BFB

Module Rectifier

AC Input

 

UPS Module

DC

UPS Output

Bus

 

Critical

Load

To DC Supply

2.5Manual Operations—All Systems

The Liebert NX UPS is designed to function while unattended by an operator. The system control logic automatically handles many important functions, as explained in 2.16 - Automatic Operations. Other procedures must be performed manually.

Manual procedures available to the operator include startup, load transfers and shutdowns. These procedures are performed by using the touchscreen and some manually operated circuit breakers and switches.

This section lists typical step-by-step instructions.

Startup—Including initial startup, recovering from input power failure, recovering from DC source shutdown and recovering from shutdowns for emergencies or maintenance.

Load Transfers-Including transfers from UPS to bypass and retransfers from bypass to the UPS system.

Maintenance Bypass Load Transfers—Including transfers from internal bypass to maintenance bypass and transfers from maintenance bypass to internal bypass.

Shutdowns—Including module shutdowns for maintenance and emergency shutdowns.

NOTE

The following procedure assumes that the UPS installation inspection and initial startup have been performed by Emerson Network Power® Liebert Services. An Emerson-authorized representative must perform the initial system startup to ensure proper system operation.

17

Liebert®NX

Image 23
Contents Liebert NX Product Warranty Registration Table of Contents Options MaintenanceSpecifications Figures Page Important Safety Instructions Battery Cabinet Precautions General Description Typical single module UPS system one-line diagramMaintenance Bypass Normal ModeBypass Mode Battery ModeOptions Main component locations-225 to 300kVA Liebert NX FeaturesFront Doors Removed Main display screen, typical System Status Touchscreen NavigationMain Display Screen Measures Menu Rectifier Bypass Inverter Chg/Boost Battery LoadStatus Events Log MenuBattery Test Battery MenuBattery Status Battery parameters Battery MeasuresLife menu Life MenuAbout Menu Settings MenuAnimated One Line Mimic Rectifier Functional BlockLoad on bypass, UPS available Load on BypassOff DC Source Input Power Failure-Load on DC SourceManual Operations-All Systems Remote Emergency Power OffStartup-Single Module System Startup-1+N System Load Transfer and Retransfer-Single Module System Transfer ProcedureRetransfer Procedure 6 1+N System Transfer load from UPS to Bypass 9 1+N System Shutdown 7 1+N System Transfer load from Bypass to UPSShut Down-Single Module UPS System Load Transfer-1+N System Add a UPS to the System Collective Load Transfer-1+N System Remove a UPS from System CollectiveCurrent-versus-time curves of overload capacity Automatic OperationsOverloads Without Transfer Automatic Transfers to Bypass Overload Condition Automatic Transfers to Bypass, UPS System FaultsAutomatic Retransfers to UPS MopUPS Shutdown and Monitoring Software Remote Alarm UnitConnectivity combinations Manage UPS AdapterConnectivity Available Selectable Output Contacts Available Selectable Input ContactsSafety Precautions Training Liebert ServicesMaintenance Agreements The Signature Program Professional StartupAir Filters Routine MaintenanceRecord Log Component Expected Life Replace Battery MaintenanceUPS component service life Limited Life ComponentsBattery Safety Precautions Number of Cells Nominal Float 240 480 527 Matching Battery Cabinets-OptionalBattery voltage, nominal and float Battery Voltage, VDCRetorque Value Battery retorque valuesBattery Mfr Battery Model # In-lb N-m Other DC SourcesItems to check include Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Detecting TroubleOther DC Sources Battery OperationEnvironmental specifications DC SourcesPhysical specifications Electrical specificationsSpecifications LiebertNX Page Care Ne tIs t Twor k