Operation
2.4.4Remote Emergency Power Off
The Remote Emergency Power Off control is a
When the Remote Emergency Power Off switch is operated, the UPS will shut down and open bypass circuit breakers. All power through the UPS is removed from the load. Typically, the REPO circuit also opens the circuit breakers that provide power to the bypass lines and the UPS controls. Refer to 2.5.8 - Shut
Figure 18 Remote Emergency Power Off
Module Bypass
AC Input
BFB
Module Rectifier
AC Input
| UPS Module |
DC | UPS Output |
Bus |
|
Critical
Load
To DC Supply
2.5Manual Operations—All Systems
The Liebert NX UPS is designed to function while unattended by an operator. The system control logic automatically handles many important functions, as explained in 2.16 - Automatic Operations. Other procedures must be performed manually.
Manual procedures available to the operator include startup, load transfers and shutdowns. These procedures are performed by using the touchscreen and some manually operated circuit breakers and switches.
This section lists typical
•
•Load
•Maintenance Bypass Load
•
NOTE
The following procedure assumes that the UPS installation inspection and initial startup have been performed by Emerson Network Power® Liebert Services. An