Emerson NX manual Battery Maintenance, Limited Life Components, UPS component service life

Page 39

Maintenance

4.3.3Limited Life Components

The Liebert NX UPS has a design life well in excess of 10 years. Well-maintained units can continue to provide economic benefits for 20 years or more. Long-life components are used in the UPS wherever practical and cost-effective. However, due to the currently available component material, manufacturing technology limitations and the general function and use of the component, a few components in your Liebert NX will have a shorter life cycle and require replacement in less than 10 years.

The following components utilized in your UPS system have a limited life cycle and are specifically exempt from warranty. To prevent a wear-out failure of one of these components affecting your critical load operations, Emerson recommends these components be periodically inspected and replaced before the expected expiration of their life cycle. The expected life of each component listed below is simply an estimate and is not a guarantee. Individual users may have site-specific requirements, maintenance and other environmental conditions that affect the length of the component's useful life cycle.

In most cases, replacement components must exactly match the original component specifications. These replacement components are not readily available from third-party component distributors.

For assistance with your specific component specifications, replacement component selection and sourcing, call 1-800-LIEBERT. For customers using Liebert Services’ preventive maintenance, periodic inspection of these components is part of this service, as well as recommending component replacement intervals to customers to avoid unanticipated interruptions in critical load operations.

4.4Battery Maintenance

Table 4

UPS component service life

 

 

 

 

Component

Expected Life

Replace in:

Power AC Filter Capacitors

> 7 years (~62,000 hours)

5 to 6 years

 

 

 

Power DC Filter Capacitors

> 7 years (~62,000 hours)

5 to 6 years

 

 

 

Low-Profile Fans

> 7 years (~62,000 hours)

5 to 6 years

 

 

 

 

Air Filters

 

1 to 3 years

Check four times per year

 

 

 

Battery, Lithium Logic Memory Backup

10 years (~87,600 hours)

8 to 9 years

 

 

 

Battery, Storage

 

 

 

 

 

Lead-Acid Wet-Cell (User Selection)

20-Year Design Life

12 to 15 years

 

 

 

 

 

 

5-Year Design Life

2 to 3 years

 

 

 

 

Valve-Regulated, Lead-Acid (VRLA)

10-Year Design Life

3 to 5 years

 

 

 

8 to 12 years

 

 

 

 

 

20-Year Design Life

Confirm need for replacement via load test or

 

 

 

continuous battery performance monitoring.

! WARNING

Risk of electric shock and high short circuit current. Can cause equipment damage, personal injury and death.

These maintenance procedures will expose hazardous live parts. Refer servicing to properly trained and qualified personnel working in accordance with applicable regulations as well as with the manufacturers’ specifications.

DC fuses operate at the rated battery voltage at all times. A blown DC bus fuse indicates a serious problem. Serious injury or damage to the equipment can result if the fuse is replaced without knowing why it failed. Contact Liebert Services for assistance.

33

Liebert®NX

Image 39
Contents Liebert NX Product Warranty Registration Table of Contents Maintenance SpecificationsOptions Figures Page Important Safety Instructions Battery Cabinet Precautions General Description Typical single module UPS system one-line diagramMaintenance Bypass Normal ModeBypass Mode Battery ModeOptions Main component locations-225 to 300kVA Liebert NX FeaturesFront Doors Removed Main display screen, typical Touchscreen Navigation Main Display ScreenSystem Status Measures Menu Rectifier Bypass Inverter Chg/Boost Battery LoadStatus Events Log MenuBattery Menu Battery StatusBattery Test Battery parameters Battery MeasuresLife menu Life MenuAbout Menu Settings MenuAnimated One Line Mimic Rectifier Functional BlockLoad on bypass, UPS available Load on BypassOff DC Source Input Power Failure-Load on DC SourceManual Operations-All Systems Remote Emergency Power OffStartup-Single Module System Startup-1+N System Transfer Procedure Retransfer ProcedureLoad Transfer and Retransfer-Single Module System 6 1+N System Transfer load from UPS to Bypass 7 1+N System Transfer load from Bypass to UPS Shut Down-Single Module UPS System9 1+N System Shutdown Load Transfer-1+N System Add a UPS to the System Collective Load Transfer-1+N System Remove a UPS from System CollectiveAutomatic Operations Overloads Without TransferCurrent-versus-time curves of overload capacity Automatic Transfers to Bypass Overload Condition Automatic Transfers to Bypass, UPS System FaultsAutomatic Retransfers to UPS MopUPS Shutdown and Monitoring Software Remote Alarm UnitManage UPS Adapter ConnectivityConnectivity combinations Available Selectable Output Contacts Available Selectable Input ContactsSafety Precautions Training Liebert ServicesMaintenance Agreements The Signature Program Professional StartupRoutine Maintenance Record LogAir Filters Component Expected Life Replace Battery MaintenanceUPS component service life Limited Life ComponentsBattery Safety Precautions Number of Cells Nominal Float 240 480 527 Matching Battery Cabinets-OptionalBattery voltage, nominal and float Battery Voltage, VDCRetorque Value Battery retorque valuesBattery Mfr Battery Model # In-lb N-m Other DC SourcesItems to check include Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Detecting TroubleOther DC Sources Battery OperationEnvironmental specifications DC SourcesPhysical specifications Electrical specificationsSpecifications LiebertNX Page Care Ne tIs t Twor k