Emerson NX manual Load Transfer and Retransfer-Single Module System, Transfer Procedure

Page 26

Operation

2.5.3Load Transfer and Retransfer-Single Module System

Changing the load from the UPS system to the UPS bypass is called a transfer. Changing the load from UPS bypass to the UPS system is called a retransfer. Note that the UPS system control logic can initiate automatic load transfers and retransfers. Refer to 2.6 - Automatic Operations.

Transfer Procedure

1.Press the “Stop Inverter” menu button on the touchscreen.

2.The load will transfer to Bypass mode and Inverter will turn Off.

Retransfer Procedure

1.Press the “Start Inverter” menu button on the touchscreen.

2.The Inverter will synchronize with the bypass and transfer the load to Normal mode.

2.5.4Maintenance Bypass Load Transfers-Single Module System: If Load is on UPS Bypass

Follow these instructions to manually transfer the load between the Maintenance Bypass and the UPS bypass line. Do not transfer the load between the Maintenance Bypass and the UPS module (inverter) output. Use the Monitor/Mimic Display screen to verify that the UPS bypass line is available.

NOTICE

Risk of improper operation. Can cause equipment damage.

Failing to follow the proper sequence when operating any circuit breaker may cause damage to the connected equipment. Operating a Maintenance Bypass circuit breaker out of sequence could cut Off power to the critical load.

NOTICE

Risk of improper operation. Can cause equipment damage.

The UPS system must be on internal bypass before the following procedures are performed or the MIB or the MBB is operated. Doing so may damage to the UPS and the critical load may be lost.

1.Transfer the UPS system to bypass (see 2.5.3 - Load Transfer and Retransfer-Single Module System). The “OK to transfer” lamp on the key-release unit will light.

NOTE

If the maintenance bypass cabinet or switchboard has any other type of custom interlock, follow the specific instructions for that interlock system to remove the key.

2.If using a key interlock system:

a. Depress the key-release unit push button, turn the key and remove from key-release unit.

NOTE

The UPS system is now locked in bypass and cannot be retransferred to the inverter until the key is reinserted.

b. Insert the key into the lock for the Maintenance Bypass Breaker (MBB); retract the bolt.

3.Close the Maintenance Bypass Breaker (MBB).

NOTICE

Risk of improper operation sequence. May cause equipment damage.

Failure to close the Maintenance Bypass Breaker (MBB) will interrupt power to the load.

4.Open the Maintenance Isolation Breaker (MIB). The UPS system is now isolated from the critical load and the load is now on Maintenance Bypass.

5.If using a key interlock system,

a.Remove the key from the lock for the Maintenance Isolation Breaker (MIB).

b.Put the key back in the solenoid.

6.If UPS bypass shutdown is required, open the Bypass Input Breaker (BIB). This breaker is external to the UPS; it may be in the Maintenance Bypass Cabinet.

Liebert®NX

20

Image 26
Contents Liebert NX Product Warranty Registration Table of Contents Options MaintenanceSpecifications Figures Page Important Safety Instructions Battery Cabinet Precautions Typical single module UPS system one-line diagram General DescriptionBattery Mode Normal ModeBypass Mode Maintenance BypassOptions Features Main component locations-225 to 300kVA Liebert NXFront Doors Removed Main display screen, typical System Status Touchscreen NavigationMain Display Screen Events Log Menu Rectifier Bypass Inverter Chg/Boost Battery LoadStatus Measures MenuBattery Test Battery MenuBattery Status Battery Measures Battery parametersLife Menu Life menuRectifier Functional Block Settings MenuAnimated One Line Mimic About MenuLoad on Bypass Load on bypass, UPS availableInput Power Failure-Load on DC Source Off DC SourceRemote Emergency Power Off Manual Operations-All SystemsStartup-Single Module System Startup-1+N System Load Transfer and Retransfer-Single Module System Transfer ProcedureRetransfer Procedure 6 1+N System Transfer load from UPS to Bypass 9 1+N System Shutdown 7 1+N System Transfer load from Bypass to UPSShut Down-Single Module UPS System Load Transfer-1+N System Remove a UPS from System Collective Load Transfer-1+N System Add a UPS to the System CollectiveCurrent-versus-time curves of overload capacity Automatic OperationsOverloads Without Transfer Automatic Transfers to Bypass, UPS System Faults Automatic Transfers to Bypass Overload ConditionAutomatic Retransfers to UPS Remote Alarm Unit MopUPS Shutdown and Monitoring SoftwareConnectivity combinations Manage UPS AdapterConnectivity Available Selectable Input Contacts Available Selectable Output ContactsSafety Precautions Professional Startup Liebert ServicesMaintenance Agreements The Signature Program TrainingAir Filters Routine MaintenanceRecord Log Limited Life Components Battery MaintenanceUPS component service life Component Expected Life ReplaceBattery Safety Precautions Battery Voltage, VDC Matching Battery Cabinets-OptionalBattery voltage, nominal and float Number of Cells Nominal Float 240 480 527Other DC Sources Battery retorque valuesBattery Mfr Battery Model # In-lb N-m Retorque ValueDetecting Trouble Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Items to check includeDC Sources Battery OperationEnvironmental specifications Other DC SourcesElectrical specifications Physical specificationsSpecifications LiebertNX Page Twor k Ne tIs t Care