Emerson NX 7 1+N System Transfer load from Bypass to UPS, Shut Down-Single Module UPS System

Page 28

Operation

2.5.71+N System: Transfer load from Bypass to UPS

1.Verify that the module’s rectifier is On and in bypass mode. See 2.5.1 - Startup—Single Module System for the startup sequence.

2.For every module in the system, close the Bypass Input Breaker (BIB) or verify that it is closed. This breaker is external to the UPS; it may be in the Maintenance Bypass Cabinet.

3.For every module in the system, close the Module Output Breaker (MOB) or verify that it is closed. This breaker is external to the UPS; it may be in the Maintenance Bypass Cabinet.

4.Place all modules in Bypass mode (see Steps 1 and 2 in 2.5.2 - Startup-1+N System.

5.If transferring to a wraparound Maintenance Bypass

a.If using a key interlock system,

1.Depress the key-release unit push button.

2.Turn the key and remove it from the key-release unit.

3.Insert the key into the lock for the Maintenance Isolation Breaker (MIB).

4.Retract the bolt.

b.Close the Maintenance Isolation Breaker (MIB).

c.Open the Maintenance Bypass Breaker (MBB). Load is now on UPS Internal Bypass.

d.If using a key interlock system,

1.Remove the key from the lock for the Maintenance Bypass Breaker (MBB) to lock it open.

2.Reinsert the key into the solenoid.

6.Select the “Start Inverter” icon on the USER LCD of Module 1. It is recommended that you start with Module 1 and then continue in order when instructed to do so.

7.Verify that “Inverter pending on command” message is displayed in the INVERTER section of the Status screen.

8.Repeat Steps 6 and 7 for the remaining modules.

NOTE

After the “Start Inverter” icon on the last module has been selected, all inverters will turn On simultaneously.

2.5.8Shut Down-Single Module UPS System

Perform a Module Shutdown to remove power from a UPS module.

Read all warnings in 4.0 - Maintenance before performing any maintenance on your Liebert NX UPS. These warnings and cautions must be observed during any work on the UPS.

Use the module Monitor/Mimic Display to determine the operating condition of the UPS module.

1.Press the “Stop Inverter” button on the touchscreen. This will put the load on bypass.

2.Open all DC breakers.

Open the bypass and rectifier breakers to complete the shutdown.

2.5.91+N System Shutdown

This section lists typical step-by-step instructions.

Perform a System Shutdown Procedure when you want to remove power from the entire UPS system.

Read all warnings in 4.0 - Maintenance before performing any maintenance on your Liebert NX UPS. These warnings and cautions must be observed during any work on the UPS.

Use the module Monitor/Mimic Display to determine the operating condition of the UPS module. 1. On each module, press the “Stop Inverter” button on the touchscreen.

NOTE

The inverters will stay online until the Stop inverter button is pressed on the last module.

2. This will transfer the UPS system to bypass.

Liebert®NX

22

Image 28
Contents Liebert NX Product Warranty Registration Table of Contents Specifications MaintenanceOptions Figures Page Important Safety Instructions Battery Cabinet Precautions Typical single module UPS system one-line diagram General DescriptionNormal Mode Bypass ModeBattery Mode Maintenance BypassOptions Features Main component locations-225 to 300kVA Liebert NXFront Doors Removed Main display screen, typical Main Display Screen Touchscreen NavigationSystem Status Rectifier Bypass Inverter Chg/Boost Battery Load StatusEvents Log Menu Measures MenuBattery Status Battery MenuBattery Test Battery Measures Battery parametersLife Menu Life menuSettings Menu Animated One Line MimicRectifier Functional Block About MenuLoad on Bypass Load on bypass, UPS availableInput Power Failure-Load on DC Source Off DC SourceRemote Emergency Power Off Manual Operations-All SystemsStartup-Single Module System Startup-1+N System Retransfer Procedure Transfer ProcedureLoad Transfer and Retransfer-Single Module System 6 1+N System Transfer load from UPS to Bypass Shut Down-Single Module UPS System 7 1+N System Transfer load from Bypass to UPS9 1+N System Shutdown Load Transfer-1+N System Remove a UPS from System Collective Load Transfer-1+N System Add a UPS to the System CollectiveOverloads Without Transfer Automatic OperationsCurrent-versus-time curves of overload capacity Automatic Transfers to Bypass, UPS System Faults Automatic Transfers to Bypass Overload ConditionAutomatic Retransfers to UPS Remote Alarm Unit MopUPS Shutdown and Monitoring SoftwareConnectivity Manage UPS AdapterConnectivity combinations Available Selectable Input Contacts Available Selectable Output ContactsSafety Precautions Liebert Services Maintenance Agreements The Signature ProgramProfessional Startup TrainingRecord Log Routine MaintenanceAir Filters Battery Maintenance UPS component service lifeLimited Life Components Component Expected Life ReplaceBattery Safety Precautions Matching Battery Cabinets-Optional Battery voltage, nominal and floatBattery Voltage, VDC Number of Cells Nominal Float 240 480 527Battery retorque values Battery Mfr Battery Model # In-lb N-mOther DC Sources Retorque ValueReporting a Problem Upstream Feeder Circuit Breaker Setting InspectionsDetecting Trouble Items to check includeBattery Operation Environmental specificationsDC Sources Other DC SourcesElectrical specifications Physical specificationsSpecifications LiebertNX Page Ne t Is tTwor k Care