Emerson NX manual Routine Maintenance, Record Log, Air Filters

Page 38

Maintenance

4.3Routine Maintenance

You should become thoroughly familiar with the equipment, but at no time should you go beyond the specific procedures in this manual while performing maintenance or correcting a malfunction.

If you have any doubt as to what must be done, call Liebert Services at 1-800-LIEBERT for further instructions.

The UPS is designed for unattended operation, but does require some common-sense maintenance.

Keep good records—Troubleshooting is easier if you have historical background.

Keep it clean—Maintain the UPS free of dust and moisture.

Keep it cool—Battery systems must be kept in the range of 72-77°F (22-26°C) in order to meet design specifications for capacity and longevity.

The UPS will reliably meet all performance specifications and design life at temperatures up to 104°F (40°C). However, performance and longevity will be optimized when the UPS is operated at the same temperature as the batteries. Contact your local Emerson® sales representative or call 1-800-LIEBERT for further details.

Keep connections tight—Tighten all connections at installation and at least annually thereafter (see Table 6 - Battery retorque values.)

Keep it inspected—Periodically inspect external upstream and downstream circuit breakers to assure that the trip current settings are correct.

Become familiar with typical ambient conditions surrounding equipment so that abnormal conditions may be more quickly recognized. Know what typical meter readings are and where adjustable settings should be.

4.3.1Record Log

Set up a maintenance log to record scheduled checks and any abnormal conditions.

The log should have space for all metered parameter indications including phase readings, alarm messages, UPS mode of operation, air filter replacement date and observation notes. A second log should be maintained for the DC source as directed by the DC source manufacturer.

A periodic walk-through inspection of the UPS and DC source rooms is advised to check for visible and audible indications of problems. Log the inspection, metered parameter indications and any discrepancies.

4.3.2Air Filters

The air filters must be inspected and serviced on a regular schedule. The period between inspections will depend upon environmental conditions. Under normal conditions, the air filters will require cleaning or replacement approximately every two months. Abnormal or dusty conditions will require more-frequent cleaning and replacement of air filters. Inspect installations in new buildings more often, then extend the inspection period as experience dictates.

All Liebert NX models have a replaceable air filter inside the front doors. These filters can be changed while the UPS is in operation.

NOTE

Service and maintenance work must be performed only by properly trained and qualified personnel and in accordance with applicable regulations as well as with manufacturers’ specifications.

Liebert®NX

32

Image 38
Contents Liebert NX Product Warranty Registration Table of Contents Options MaintenanceSpecifications Figures Page Important Safety Instructions Battery Cabinet Precautions Typical single module UPS system one-line diagram General DescriptionBattery Mode Normal ModeBypass Mode Maintenance BypassOptions Features Main component locations-225 to 300kVA Liebert NXFront Doors Removed Main display screen, typical System Status Touchscreen NavigationMain Display Screen Events Log Menu Rectifier Bypass Inverter Chg/Boost Battery LoadStatus Measures MenuBattery Test Battery MenuBattery Status Battery Measures Battery parametersLife Menu Life menuRectifier Functional Block Settings MenuAnimated One Line Mimic About MenuLoad on Bypass Load on bypass, UPS availableInput Power Failure-Load on DC Source Off DC SourceRemote Emergency Power Off Manual Operations-All SystemsStartup-Single Module System Startup-1+N System Load Transfer and Retransfer-Single Module System Transfer ProcedureRetransfer Procedure 6 1+N System Transfer load from UPS to Bypass 9 1+N System Shutdown 7 1+N System Transfer load from Bypass to UPSShut Down-Single Module UPS System Load Transfer-1+N System Remove a UPS from System Collective Load Transfer-1+N System Add a UPS to the System CollectiveCurrent-versus-time curves of overload capacity Automatic OperationsOverloads Without Transfer Automatic Transfers to Bypass, UPS System Faults Automatic Transfers to Bypass Overload ConditionAutomatic Retransfers to UPS Remote Alarm Unit MopUPS Shutdown and Monitoring SoftwareConnectivity combinations Manage UPS AdapterConnectivity Available Selectable Input Contacts Available Selectable Output ContactsSafety Precautions Professional Startup Liebert ServicesMaintenance Agreements The Signature Program TrainingAir Filters Routine MaintenanceRecord Log Limited Life Components Battery MaintenanceUPS component service life Component Expected Life ReplaceBattery Safety Precautions Battery Voltage, VDC Matching Battery Cabinets-OptionalBattery voltage, nominal and float Number of Cells Nominal Float 240 480 527Other DC Sources Battery retorque valuesBattery Mfr Battery Model # In-lb N-m Retorque ValueDetecting Trouble Reporting a ProblemUpstream Feeder Circuit Breaker Setting Inspections Items to check includeDC Sources Battery OperationEnvironmental specifications Other DC SourcesElectrical specifications Physical specificationsSpecifications LiebertNX Page Twor k Ne tIs t Care