Emerson NX manual Electrical specifications, Physical specifications

Page 45

Specifications

Table 8

Electrical specifications

 

 

 

Input Parameters

 

 

Input Voltage to Rectifier, VAC, 3-phase, 3-wire

480V

 

Input Voltage to Bypass, VAC, 3-phase, 3-wire

480V

 

Input Voltage Range, VAC

+10% to -30%

 

Input Frequency, Hz

60

 

Permissible Input Frequency Range, Hz

55-65

 

Rectifier Power Walk-In, sec

1-90 (selectable) in 1 Sec. Increments

DC Parameters

 

 

Battery Type

VRLA (Valve Regulated Lead Acid)

 

or FLA (Flooded Lead Acid)

 

 

 

DC Bus Range, VDC

396-600

 

DC Float Voltage, VPC

2.27

 

End-Cell Voltage, VPC

1.65 (for VRLA / FLA)

DC Ripple Voltage in Float and Const V Ch. mode, %

<1 (RMS Value) < 3.4% Vpp

Output Parameters

 

 

Output Voltage, 3-phase, 3-wire

480V

 

Output Voltage Regulation, %

< 1% (3-Phase RMS Average)

 

Output Frequency, Hz

60

 

Output Frequency Regulation, %

± 0.1

 

Capacity to Handle Step Load, %

0-100 or 100-0

 

Voltage Displacement, ° el

120° ±1° el (With Unbalanced Load)

 

Compliance to FCC Class-A

Standard

Table 9

Physical specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liebert NX Model Size

225

 

250

 

300

 

400

 

500

600

Physical Parameters and Standards, in (mm)

 

 

 

 

 

 

 

 

 

 

 

Width

 

53.4

 

 

 

 

 

90.7

 

 

Depth

 

 

 

 

 

33.7

 

 

 

 

Height

 

 

 

 

 

78.6

 

 

 

Weight, Unpackaged, approximate, lb. (kg)

 

2,450 (1,110)

 

 

4450 lb. (2019kg)

Maximum Heat Dissipation, Full Load, BTU/hr

41,000

 

45,000

 

54,000

 

72,000

 

90,000

108000

Color

 

 

 

 

 

Black (ZP-7021)

 

 

Front Door Opening (for serviceability)

 

 

 

 

More than 90°

 

 

Degree of Protection for UPS Enclosure

 

 

IP 20 (with and without front door open)

 

Minimum Clearance, Top, In. (mm)

 

 

 

 

24in (610mm)

 

 

Minimum Clearance, Back, In. (mm)

 

 

 

 

 

0

 

 

 

Minimum Clearance, Sides, In. (mm)

 

 

 

 

 

0

 

 

 

Location of Cable Entrance

 

 

 

 

Top or Bottom

 

 

 

 

 

 

 

 

UL, 1778, 4th Ed.

 

 

 

 

 

 

 

 

CSA 22.2 107.3

 

 

 

 

 

 

 

FCC Part 15, Class A

 

 

 

 

 

 

IEC62040-2, Level 4, Criteria A

 

 

 

 

 

EN61000-4-3, Level 3, Criteria A

 

Standards & Conformities

 

 

EN61000-4-6, Level 4, Criteria A

 

 

 

 

 

EN61000-2-2, Criteria A

 

 

 

 

 

EN61000-4-4, Level 4, Criteria A

 

 

 

 

 

ANSI C62.41, Category A3 &B3

 

 

 

 

 

 

 

ISTA Procedure 1H

 

 

 

 

 

 

 

 

WEEE

 

 

39

Liebert®NX

Image 45
Contents Liebert NX Product Warranty Registration Table of Contents Maintenance SpecificationsOptions Figures Page Important Safety Instructions Battery Cabinet Precautions General Description Typical single module UPS system one-line diagramBypass Mode Normal ModeBattery Mode Maintenance BypassOptions Main component locations-225 to 300kVA Liebert NX FeaturesFront Doors Removed Main display screen, typical Touchscreen Navigation Main Display ScreenSystem Status Status Rectifier Bypass Inverter Chg/Boost Battery LoadEvents Log Menu Measures MenuBattery Menu Battery StatusBattery Test Battery parameters Battery MeasuresLife menu Life MenuAnimated One Line Mimic Settings MenuRectifier Functional Block About MenuLoad on bypass, UPS available Load on BypassOff DC Source Input Power Failure-Load on DC SourceManual Operations-All Systems Remote Emergency Power OffStartup-Single Module System Startup-1+N System Transfer Procedure Retransfer ProcedureLoad Transfer and Retransfer-Single Module System 6 1+N System Transfer load from UPS to Bypass 7 1+N System Transfer load from Bypass to UPS Shut Down-Single Module UPS System9 1+N System Shutdown Load Transfer-1+N System Add a UPS to the System Collective Load Transfer-1+N System Remove a UPS from System CollectiveAutomatic Operations Overloads Without TransferCurrent-versus-time curves of overload capacity Automatic Transfers to Bypass Overload Condition Automatic Transfers to Bypass, UPS System FaultsAutomatic Retransfers to UPS MopUPS Shutdown and Monitoring Software Remote Alarm UnitManage UPS Adapter ConnectivityConnectivity combinations Available Selectable Output Contacts Available Selectable Input ContactsSafety Precautions Maintenance Agreements The Signature Program Liebert ServicesProfessional Startup TrainingRoutine Maintenance Record LogAir Filters UPS component service life Battery MaintenanceLimited Life Components Component Expected Life ReplaceBattery Safety Precautions Battery voltage, nominal and float Matching Battery Cabinets-OptionalBattery Voltage, VDC Number of Cells Nominal Float 240 480 527Battery Mfr Battery Model # In-lb N-m Battery retorque valuesOther DC Sources Retorque ValueUpstream Feeder Circuit Breaker Setting Inspections Reporting a ProblemDetecting Trouble Items to check includeEnvironmental specifications Battery OperationDC Sources Other DC SourcesPhysical specifications Electrical specificationsSpecifications LiebertNX Page Is t Ne tTwor k Care