Introduction
1.0INTRODUCTION
1.1General Description
The Liebert NX UPS provides continuous,
The Liebert NX utilizes the latest in
As shown in Figure 1, the AC utility source is input to the rectifier converts the AC utility into DC power. The inverter converts that DC power from the
If maintenance or repair of the UPS is necessary, the load can be switched without interruption in service to the optional maintenance bypass.
Figure 1 Typical single module UPS system one-line diagram
Module Bypass | UPS Module |
AC Input |
|
3 Wire + GND | BFB |
Module Rectifier |
| DC |
AC Input |
| |
3 Wire + GND | CB1 | Bus |
| (Note 5) |
|
UPS Output
3 Wire + GND
Critical
Load
2 Wire +GND
(See Note 2)
To DC Supply
1.UPS rectifier bypass input and output cables must be run in separate conduits.
2.All power cables from DC supply should be sized for a total maximum of 2V drop at maximum discharge current.
3.Control wiring and power wiring must be run in separate conduits.
4.Emerson recommends installing grounding conductors .
5.Standard configuration has CB1 removed. If CB1 is required, option must be ordered.
3 | Liebert®NX™ |