Siemens FC330A Functional test of manual call points, Test procedure for type KAC

Models: FC330A

1 58
Download 58 pages 30.31 Kb
Page 41
Image 41
Functional test of manual call points

Functional test of manual call points

Response indicator

Test−Test procedure for type KAC key

Response Test procedure for type DIN (indirect activation)indicator

Control console Button

Test procedure for type KAC

1.Set the desired zone into detector test mode (+ page 34).

2.Insert the test key into the opening at the lower left side of the housing.

ÜA test alarm is simulated.

3.Observe, whether the response indicator near the upper right corner of the housing flashes.

4.Remove the test key.

ÜThe functional testing is completed.

"If the tested manual call point did not respond, call the SIEMENS service organization.

Test procedure for type DIN (indirect activation)

1.Set the desired zone into detector test mode (+ page 34).

2.Open the housing of the manual call point with the key.

3.Press down the button completely.

ÜA test alarm is simulated.

4.Observe, whether the response indicator, a red LED to the right of the button, flashes.

5.Close the housing.

ÜThe functional testing is completed.

"If the tested manual call point did not respond, call the SIEMENS service organization.

Control console

 

Ü Display shows

*

mode ’detector TEST’ ACTIVE

>test−ALARM zone ###/##

WED 21.7.99 15:00

"Each test alarm is indicated in the display for a few seconds and also registered in the event memory.