Overview operating menu

Overview operating menu

After getting operating access, the start menu appears. From the main menu, all menus can be selected (+ page 9, fundamental operation).

With access level 2 all menu points exept other functions − configuration can be selected.

The passwort for access level 2 is:

SELECT: 1. ENabling

(main menu) 2. DISabling

3.INFO polling

4.other functions

ENABLE:

1. Detector/ConTrol ZONES

(1)2. horn/RT/alarm contacts

3. printer

SELECT: 1. ENabling

(main menu) 2. DISabling

3.INFO polling

4.other functions

 

 

ENabling:

1.

detector ’zone’

Enable detector zones 1...256

 

(1.1)

2.

detector ’element’

 

Enable detector elements within zone

 

 

 

 

3.

ConTrol ’zone’

 

 

 

 

Enable control zones 1...64

 

 

 

 

4.

All Fire Ctrl ’zones’

Enable all control zones

 

 

 

 

 

 

 

 

 

 

ENabling:

1.

horn

 

Enable control lines 1...4 for alarm horns

 

(1.2)

2.

alarm contacts

Enable alarm contacts 1...4

 

 

 

 

3.

RT−alarm

 

Enable remote transmission ALARM

 

 

 

 

4.

RT−fault

 

Enable remote transmission FAULT

 

 

 

ENable printout messages:

1. log ALL

Enable only event logging or all messages

 

 

 

 

 

(old: #)

2. only ALARMS

3. log NONE

Enable only alarms or none

DISabling: 1. detector/ConTrol ZONES

(2)2. horn/RT/alarm contacts

3. printer

DISabling: 1. detector ’zone’

(2.1) 2. detector ’element’

3.ConTrol ’zone’

4.All Fire Ctrl ’zones’

DISabling: 1. horn

(2.2) 2. alarm contacts

3.RT−alarm

4.RT−fault

Disable detector zones 1...256

disabling permanent or for a set time 1...98h

Disable detector ELEMENTS within zone disabling permanent or for a set time 1...98h

Disable conTrol zones 1....64

Disable all control zones

Disable control line 1..4 for alarm horns Disable alarm contacts 1...4

Disable remote transmission ALARM Disable remote transmission FAULT

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

INFO: 1. system status

(3)2. event memory/alarm counter

3.configuration/user text

4.configuration zone/line/LON

 

 

 

 

 

Disable only event logging or all messages

ENable printout messages:

1.

log ALL

 

(old: #)

2. only ALARMS

3.

log NONE Disable only alarms or none

 

 

 

 

STATUS: 1.

fault

View fault messages

 

 

 

(3.1)

2.

isolation

View turned off system components

 

 

 

 

 

 

3.

pre−alarm

View pre-alarm messages

 

 

 

 

 

 

4.

techn.alarm /element status

View ELEMENT states

 

 

 

 

 

 

 

 

 

 

MEMORY: 1. event memory

View reviewing event list

 

 

 

 

 

 

 

 

View number of alarms and remote alarms

 

 

(3.2)

2. alarm counter

 

 

 

 

 

 

 

 

INFO:

1.

configuration system

View general parameter settings

 

 

(3.3)

2.

configuration coll line

View parameter settings coll. lines

 

 

 

 

 

 

3.

user text detector zn/elem

View user texts detector zones/elements

 

 

 

 

 

 

4.

user text ConTrol zone

View user texts control zones

 

 

 

 

 

INFO:

1.

configuration det. zones

View parameter settings detector zones

 

 

 

 

 

 

 

(3.4)

2.

configuration addr. lines

View parameter settings addr. lines

 

 

 

 

 

 

3.

configuration LON devices

View parameter settings LON-bus

6

Fire & Security Products

e1973c-2

Siemens Building Technologies Group

02.2004

Page 10
Image 10