4.After entering the last number press ok twice.
Ü Display shows | * |
for a few seconds |
|
ÜThe selected detector zones are set into detector test mode.
Ü Display shows | * |
ÜThe yellow LED of the display field de- tector test mode are on.
Mode ’DET. TEST’ zones: ###,###,###,###
Outputs NOT activated
timeout /hm: menu | Stop: end operating |
Mode ’DET. TEST’ zones: ###,###,###,###
Mode ’DET. TEST’ range: ### − ###
TUE 27.7.99 10:35
Setting a zone range or all detectors into detector test mode
1. Press St . |
|
Ü Display shows | * |
2.Select option 4. ä 2. ä 3. ä 2.
Ü Display shows | * |
3.Enter the first number of the desired zone range (e. g. 2) or 555 for testing all zones.
Ü Display shows | * |
for a few seconds |
|
4.Enter the last number of the desired zone range (e. g. 5).
Ü Display shows | * |
ÜThe selected zone range is set into de- tector test mode.
Ü Display shows | * |
Terminating the detector test mode for single zones
1. Press St . |
|
Ü Display shows | * |
2.Select option 4. ä 2. ä 3. ä 1.
Ü Display shows | * |
3.Press del to delete all displayed zone numbers and enter “0” (zero) instead.
4.Press ok twice.
Ü Display shows | * |
for a few seconds |
|
ÜThe detector test mode is terminated for all detector zones.
SELECT: 1. ENabling (main menu) 2. DISabling
3.INFO polling
4.other functions
No ’DET.TEST’ mode, set range ### − ###:
> zone no.? (555=all, 0=end)
zone range ### − ### in ’DET. TEST’ mode Outputs NOT activated
timeout /hm: menu | Stop: end operating |
zone ### SELECTED. ok = SINGLE zone > 2nd zone no.? (range ### − ###)
Mode ’DET. TEST’ zones: ###,###,###,###
Mode ’DET. TEST’ range: ### − ###
TUE 27.7.99 10:35
SELECT: 1. ENabling (main menu) 2. DISabling
3.INFO polling
4.other functions
No ’DET. TEST’ mode, set single zone(s): > zone no.? (max. 4)
hm: back to menu | Stop: end operating |
| |
’DET. TEST’ mode TERMINATED | |
timeout /hm: menu | Stop: end operating |
|
|
Terminating the detector test mode for a zone range
1. Press St . |
|
Ü Display shows | * |
2.Select option 4. ä 2. ä 3. ä 2.
Ü Display shows | * |
3.Enter “0” (zero) and press ok .
Ü Display shows | * |
for a few seconds |
|
ÜThe detector test mode is terminated for all detector zones.
SELECT: 1. ENabling (main menu) 2. DISabling
3.INFO polling
4.other functions
No ’DET.TEST’ mode, set range ### − ###:
> zone no.? (555=all, 0=end)
hm: back to menu | Stop: end operating |
| |
’DET. TEST’ mode TERMINATED | |
timeout /hm: menu | Stop: end operating |
|
|
35