Zone isolation procedure
1. Press St . |
|
Ü Display shows | * |
2.Select option 2. ä 1. ä 1.
Ü Display shows | * |
Now you can disable single zones, a range of detector zones or all zones as described be- low:
SELECT: 1. ENabling (main menu) 2. DISabling
3.INFO polling
4.other functions
DISable zones: (range ### to ###)
> zone no.? (555 = all)
hm: back to menu | Stop: end operating |
Disable single zones
| 1. | Enter the desired zone number (e. g. |
|
|
| 2). |
|
|
| Ü Display shows | * |
| 2. | Press ok to disable the single zone. |
|
|
| Ü Display shows | * |
Permanent disabling | 3. Enter 99 for permanent disabling. |
| |
|
| Ü Display shows | * |
|
| or |
|
Disabling for a few |
| " Enter the desired disabling time in full | |
hours |
| hours (e. g. 2). |
|
|
| Ü Display shows | * |
| 4. | Press St to finish the zone disabling |
|
|
| procedure. |
|
or
zone ### SELECTED. ok = SINGLE zone > 2nd zone no.? (range ### − ###)
hm: back to menu | Stop: end operating |
zone ### SELECTED
> hours DISABLED? (99=permanent)
zone ### permanent DISABLED
(hm = end) | new zone no.? | |
hm: back to menu | Stop: end operating | |
|
| |
|
| |
zone ### DISABLED for | ## hours | |
(hm = end) | new zone | no.? |
hm: back to menu | Stop: end operating | |
|
|
|
"Enter another single zone number to disable.
Ü Display shows | * |
ÜThe yellow LED isolation is on.
parts of system DISABLED | total:### |
WED 21.7.00 15:00
Disable a range of zones
1.Enter the first zone number of the range of zones to be disabled (e. g. 2).
Ü Display shows | * |
zone ### SELECTED. ok = SINGLE zone |
| |
> 2nd zone no.? (range ### − ###) | _ | |
hm: back to menu | Stop: end operating |
| 2. | Enter the last zone number of the range | |
|
| of zones to be disabled (e. g. 5). |
|
|
| Ü Display shows | * |
Permanent disabling | 3. | Enter 99 for permanent disabling. |
|
|
| Ü Display shows | * |
|
| or |
|
Disabling for a few |
| " Enter the desired disabling time in full | |
hours |
| hours (e. g. 2). |
|
|
| Ü Display shows | * |
4.Press St to finish the zone disabling procedure.
or
"Enter another zone number to disable.
Ü Display shows | * |
ÜThe yellow LED isolation is on.
zone ### − ### SELECTED
> hours DISABLED? (99=permanent)
| hm: back to menu | Stop: end operating | ||
|
| |||
|
| |||
| zones ### − ### permanent DISABLED | |||
| (hm = end) | new zone no.? |
| |
| hm: back to menu | Stop: end operating | ||
|
| |||
|
| |||
| zones ### − ### DISABLED for ## hours | |||
| (hm = end) | new zone no.? |
| |
| hm: back to menu | Stop: end operating | ||
|
|
| ||
|
|
| ||
| parts of system DISABLED | total:### | ||
| WED 21.7.00 | 15:00 |
|
|