Poll system status
Purpose
After acknowledging messages from various system states differing from “normal operation” as “isolation” or “fault”, detailed information may be no longer visible on the text display. Only the LEDs of the display fields and a more general message like “parts of the system isolated” on the text display indicate a special system state. More detailed informations e. g. which zones are isolated, or which elements are faulty can be retrieved by polling the system status at any time.
Polling the system status
1. Press St . |
|
Ü Display shows | * |
2.Select option 3. ä 1.
Ü Display shows | * |
3.Select option 1.
ÜA scroll page for the selected item is dis- played, here for example for “fault“.
Ü Display shows | * |
SELECT: 1. ENabling (main menu) 2. DISabling
3.INFO polling
4.other functions
STATUS: 1. fault (3.1) 2. isolation
3.pre−alarm
4.techn.alarm /element status
display FAULT messages: | total:## | |
(key: ↓ = forward / ↑ = backward) | ||
hm: back to menu | Stop: end operating |
4.Use and to scroll through the messages.
Ü Display shows
5.Use hm to go back to the submenu or
| display FAULT messages: | total:## |
* | fault messages | |
|
| |
| ↓: forward | ↑: backwards |
|
|
|
St to terminate the system status polling.
49