Test of Remote Transmission (RT)

Test of Remote Transmission (RT)

Purpose and principle

In test mode the function of the remote transmission can be tested without activating an alarm device or a manual call point.

The function of the remote transmission facility has to be checked periodically. The remote alarm transmission and the remote fault transmission can be tested separately.

Frequency

The acoustic alarm devices have to be tested at least once a year.

i

Before the remote alarm transmission is tested, inform the fire brigade!

 

Test procedure for remote alarm transmission

1.Inform the fire brigade before a remote alarm transmission test will be performed.

2. Press St .

 

SELECT:

1.

ENabling

Ü Display shows

*

(main menu)

2.

DISabling

 

3.

INFO polling

 

 

 

4.

other functions

 

 

 

 

 

3.Select option 4. ä 2. ä 1. ä 3.

ÜTo initiate the remote ALARM test.

Ü Display shows

*

4.If the fire brigade is informed, press ok .

Ü Display shows

*

ÜThe test runs for 30 sec. The remaining time is indicated.

ATTENTION: testing remote transm. ALARM!

>> fire brigade notified? > then: ok

hm: back to menu

Stop: end operating

TESTING remote transm. ALARM (RT−alarm): > remaining active time

hm: stop test

Stop: end operating

ÜAfter the test has finished, the submenu is displayed again.

If the remote alarm did not arrive at the fire departement, call the SIEMENS service organization for repair.

" The test can be stopped before expiration of the 30 seconds by pressing hm .

Test procedure for remote fault transmission

1.

Press St .

 

 

Ü Display shows

*

2.

Select option 4. ä 2. ä 1. ä 4.

 

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

ÜTo initiate the remote FAULT test.

Ü Display shows

*

ÜThe test runs for 30 sec. The remaining time is indicated.

TESTING remote transm. FAULT (RT−fault): > remaining active time

hm: stop test

Stop: end operating

ÜAfter the test has finished, the submenu is displayed again.

If the fault message did not arrive at the remote location, call the SIEMENS service organization for repair.

" The test can be stopped before expiration of the 30 seconds by pressing hm .