Purpose of the lamp test

Alarms, faults and operating state of the fire detection system are indicated by LEDs in the dis- play fields, the text display and the alarm buzzer of the control console.

To check the correct function of these parts the lamp test can be initiated: All visual and audible devices of the control console are activated for a few seconds.

Frequency

The lamps have to be tested at least once a year.

Lamp test procedure

1. Press St .

 

Ü Display shows

*

2.Select option 4. ä 2. ä 2. ä 1.

ÜTo initiate the lamp test.

Ü Display shows

*

3.Check:

all LEDs on?

buzzer audible?

missing segments in text display?

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

TESTING lamps and display:

(→← ↓↑)

> remaining time

.........................................

.........................................

i

38

If one or more devices are malfunctional, call the SIEMENS service organization.

Lamp test on local indication and control panels + page 5.