Operating access

Operating access

Possible access levels

i

Acknowledge messages possible: with access level 1 p

with access level 2 p

Three main access levels are defined allowing different privileges for the operation of the fire detection system. Access is provided by a four digit password for the higher access levels, re- spectively.

After 3 consecutive incorrect password entries the operation access is disabled for 15 minu- tes.

Overview of the access levels

Access level

Group of persons

 

Enabled operating functions

 

 

 

 

Access level 1

everybody

Scrolling alarm messages

(no password)

 

Acknowledge messages

 

 

 

 

Access level 2

system operator 1 (e. g. jani-

Acknowledge messages

(password required or

tor)

Alarm reset

 

key−lock switch, if instal-

 

Fault/Info scrolling

led)

 

− Isolation of system parts

 

 

 

 

Poll system information

 

 

Perform system tests

 

 

 

 

Access level 3

service engineer

Edit user text

(various passwords to di-

or

 

 

stinguish)

system operator 2 (e. g. se-

 

 

 

curity officer)

 

 

 

 

 

 

 

service engineer

Service functions

 

 

Erase data

 

 

 

 

 

service engineer

Application setting

 

 

Setting passwords

 

 

 

 

Automatic timeout

The access by password is automatically cancelled if no key is operated for:

n5 min during state of “normal operation“

n30 sec during condition “alarm“

How do I get operating access?

"Enter the password on the keypad Ê as described below. or

"Turn the keylock switch Ë in horizontal position.

ÜAccess with level user operating 2 is provided as long as the key is left in horizontal position.

System on

Remote alarm

Alarm delay

Remote alarm

7

8

9

F1

Start/

fault / off

off

active

Stop

 

 

 

 

 

Fault

Alarm horn

Premises

 

4

5

6

F2

 

fault / off

manned

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

Isolation

System fault

 

 

1

2

3

ok

 

 

 

 

 

 

 

Detector

 

 

 

del

0

 

 

2

test mode

 

 

 

hm

 

FC330A

 

 

 

 

 

 

 

 

11

Fire & Security Products

e1973c-2

Siemens Building Technologies Group

02.2004

Page 15
Image 15
Siemens FC330A manual Operating access, Possible access levels, How do I get operating access?