Faults
How do I respond to fault messages?
Fault messages are issued on the text display if a malfunction in the system, the cabling or the attached devices is detected. Additionally the LED in the fault display field is blinking.
1.Confirm the message by pressing the Acknowledge key.
Ü The yellow LED in the fault display field changes from blinking to constant on.
2.Read the fault message on the display and decide, whether the fault can be remedied by the user (see next paragraph: What remedies are available to the user).
3.To cancel the fault message after the fault is remedied, press the Reset key.
WARNING
If the fault cannot remedied by the user, immediately call the SIEMENS service organiza- tion!
What remedies are available to the user?
Only a few faults can be remedied by the user. These are listed below. For all other faults call the
SIEMENS service organization.
Defective or missing detector |
|
Ü Display shows | * |
or |
|
Ü Display shows | * |
Broken glass on manual call point |
|
Ü Display shows | * |
ÜManual call point with broken glass is flashing
"If a detector is missing, insert a detector of the same type into the detector base.
FAULT message(s): | total:### | |
zone ### elem. ##: dev. DEFECTIVE | ||
TUE 27.7.99 | 10:35 |
|
|
| |
|
| |
FAULT message(s): | total:### | |
zone ### elem. ##: NO RESPONSE | ||
TUE 27.7.99 | 10:35 |
|
|
| |
|
| |
FAULT message(s): | total:### | |
zone ### elem ##: Broken glass | ||
TUE 27.7.99 | 10:35 |
|
|
|
|
"If a detector is damaged, replace it with a detector of the same type and order a new reserve detector from the SIEMENS service organization.
"If a manual call point has been operated and the glass is broken, replace it, then press the key
Reset.
Mains POWER OFF |
|
Ü Display shows | * |
FAULT message(s): | total:### |
EARTH FAULT to 24V |
|
TUE 27.7.99 10:35 |
|
|
|
Emergency power | n | If the public power supply is down, no action is required. The emergency battery supplies the | ||
supply: | h |
| system for several hours (according to local requirements at least 12 h, max. 72 h), depen- | |
|
|
|
| ding on the size of the emergency battery. |
|
|
| n | If the outage is not in the public power supply: |
1.Check the power fuse at the main distribution panel of the building.
2.If the fuse is blown, replace the fuse.
Printer out of paper
"Insert a new paper roll (+ page 45, Printer: Paper replenishing).