4.other functions

SELECT: 1. ENabling (main menu) 2. DISabling

3.INFO polling

4.other functions

FUNCTIONS: 1. function

(4)2. system TEST

3.printout

4.configuration

page 8 page 8

FUNCTIONS:

1.

switching alarm org.

Switching manned $ unmanned via menu

(4.1)

2.

set time / date

Set or adjust time and date

SYSTEM TEST: 1. horn/al.contact/RT

(4.2) 2. lamps/battery

3. fire and contr.zones

SYSTEM TEST: 1. horn

(4.2.1) 2. alarm contacts

3.RT−alarm

4.RT−fault

SYSTEM Test:

1.

lamps/display

(4.2.2)

2.

battery

SYSTEM TEST: 1. single zone test

(4.2.3) 2. zone range test 3. set control zones

Activate all ’horns’ for 30 sec

Activate all ’alarm contacts’ for 30 sec. Activate ’remote alarm’ for 30 sec. Activate ’remote fault’ for 30 sec.

Activate all LEDs and LCD for 10 sec. Load battery for 10 sec.

Set detectors to ’Detector test’ per zone Set detectors to ’Detector test’ zone X...Y Set control zone to ’control zone Test’ X..Y

PRINT: 1. system status

(4.3) 2. event memory/alarm counter

3.configuration/user text

4.configuration zone/line/LON

PRINT: 1. fault (4.3.1) 2. isolation

3.pre−alarm

4.techn.alarm /element status

PRINT: 1. event memory (4.3.2) 2. alarm counter

PRINT: 1. configuration system (4.3.3) 2. configuration coll. line

3.user text detector zn/elem

4.user text ConTrol zone

PRINT: 1. configuration det. zones (4.3.4) 2. configuration addr. lines 3. configuration LON devices

Print current fault messages

Print current turned off system components Print current information messages

Print current ELEMENT states

Print event memory list

Print alarm counter readings

Print general parameter settings Print parameter settings coll. lines

Print user texts detector zones / elements Print user texts control zones

Print parameter settings detector zones Print parameter settings addr. lines Print parameter settings LON-bus

7

Fire & Security Products

e1973c-2

Siemens Building Technologies Group

02.2004

Page 11
Image 11
Siemens FC330A manual page, other functions