Page 18

Installation and Configuration

The adjustable rack-mounting brackets (Part#: RMKIT18-32) feature retaining latches to prevent users from inadvertently sliding the UPS or battery cabinet out of the rack.

To install the rack mount brackets:

1.Unpack two (2) rack-mounting bracket assemblies and mounting hardware from this kit. Bracket assemblies are interchangeable between left-hand or right-hand.

Remove inner member of each bracket assembly as shown at right by extending it to its outermost position, depress- ing the retaining latch and then pulling the inner member out of the bracket assembly.

2.Determine the height position inside the rack enclosure where you want to mount the UPS or battery cabinet.

! CAUTION

Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the lowest possible rack position.

3. Install the rear member of each bracket assembly into the

rack enclosure with two (2) M5 screws provided in this kit

(see figure at right). The return flanges on the bracket

assembly fit to the inside of rack mounting rails. Insert

screws loosely (finger-tight) into the top and bottom holes

of the return flange on the rear member. Extend the

bracket assembly by sliding the front member forward

until it touches the front rack mounting rail. Insert two (2)

M5 screws loosely (finger-tight) into the top and bottom

holes of the return flange on each front member. Make sure

that the bracket assemblies are at the same mounting

height on all four (4) rack mounting rails.

4. Get eight (8) M4 screws and eight (8) M4 nuts from the

hardware pack in this kit. Each nut has a locking, nylon

insert that begins gripping the screw when it is halfway

tight. Make sure to tighten the nut and screw completely to

ensure locking action. Fasten the rear member and the

front member together using (4) screws and (4) nuts per

bracket assembly as shown in at right. For maximum

support, insert fasteners for each bracket assembly as far

apart as possible, depending on rack depth, while still

joining both members (see figures at right). Check

alignment of bracket assemblies and TIGHTEN ALL

SCREWS FROM Steps 2 3.

Retaining

Latches

Inner members

Front rack mounting rails

M5 screws

M4 nuts

457mm

(18") rack depth

M4 nuts

Return flanges

Front members

M5 screws

M4 screws

M4 nuts

M4 screws

5. Prepare the UPS or battery cabinet (the “equipment”) for

rack mounting by following instructions in the equipment’s

user manual. The equipment may require additional parts

to be added or parts to be removed for rack mounting. After

it is prepared, lay the equipment in rack-mounting

position. Fasten the inner members from Step 1 to the

equipment on both sides as shown at right with eight (8)

M4 screws provided in the kit. Make sure retaining latch is

near the rear of the equipment as shown (see figure at

right).

813mm

 

(32") rack

M4 nuts

depth

M4 screws

Retaining latch

 

UPS or battery

 

cabinet

Front

M4 screws

12

Image 18
Contents Liebert GXT3 230V,5000VA-UL Listed Page Table of Contents Specifications MaintenanceTroubleshooting CommunicationFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionBattery DC-to-DC ConverterDynamic Bypass Main Frame and Electronics Major ComponentsLiebert GXT3 5000VA Terminal Block Communication Internal Battery Packs Removable Power Distribution BoxOuter Surface View Power Distribution Box Quick-Connect WHAT’S Included Tower UPS Installation Install the Main CabinetInstallation and Configuration Connectors Spacers Support BasesOperation and Display Panel Rotated Clockwise 90 Degrees Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityDepth UPS or battery813mm Retaining latchExternal Battery Cabinet Installation UPS or battery cabinet Apply greaseConnect Input/Output Power To removeTo install Distribution Box Electrical Connections HardwireTerminal Block ConnectionsElectrical specifications Branch circuit breaker ratingsConfiguration Program Features Configuration ProgramWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsStandby/Manual Bypass Button Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Startup Checklist for the Liebert GXT3 Initial Startup and Electrical ChecksOperation Maintenance Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Put the Liebert GXT3 in Manual BypassIT Power System Configuration Remove Screws IT Power System ConnectorsCommunication Interface Port Any Mode ShutdownBattery Mode Shutdown Dry ContactOn Battery Low BatteryLiebert IntelliSlot Communication Cards Remote Emergency Power Off Repo switch connection diagramLiebert MultiLink Replacing the Internal Battery Pack MaintenanceBattery Replacement Procedures Battery Charging PrecautionsChecking UPS Status Checking UPS FunctionsIndicators UPS SymptomsTroubleshooting Indicator Diagnosis/Audible alarmAudible Alarm Audible alarm descriptionCondition Alarm Troubleshooting table Problem Cause SolutionIlluminated Specifications UPS specificationsOperating temperature parameters Power distribution specificationsExternal battery cabinet specifications Auto-Learning Battery Run Times Page Twor k Ne tIs t Care