Emerson GXT3 230V user manual Replacing the Internal Battery Pack, Maintenance

Page 33

Maintenance

10.0MAINTENANCE

This section describes replacing the internal battery pack, precautions, checking the Liebert® GXT3’s status and checking UPS functions.

10.1Replacing the Internal Battery Pack

The Liebert GXT3 is designed to allow the user to replace the internal battery pack safely. Read the safety cautions before proceeding. Contact your local dealer or Emerson representative to obtain the part number and pricing of the appropriate replacement battery pack.

10.1.1Battery Replacement Procedures

1.Gently remove the front plastic bezel cover from the UPS.

2.Loosen and remove the six screws on the battery door, as shown in Figure 15.

3.Lay the battery door and screws aside for reassembly.

Figure 15 Removing the front plastic bezel cover and battery door

Battery Door

Screws, 6

Front Bezel

10,000VA model shown; 5000VA model arrangement is similar

4. Gently pull the battery wires out and disconnect the battery connector, as shown in Figure 16.

Figure 16 Disconnecting the battery plug and battery receptacle (front view)

Battery

Receptacle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery Connector

Battery Connector Battery Receptacle

5.Grasp the battery handle and pull one of the internal battery packs out of the UPS, as shown in Figure 17.

Repeat this step if both battery packs will be replaced. Each model has two battery packs

27

Image 33
Contents Liebert GXT3 230V,5000VA-UL Listed Page Table of Contents Troubleshooting MaintenanceSpecifications CommunicationFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionBattery DC-to-DC ConverterDynamic Bypass Main Frame and Electronics Major ComponentsLiebert GXT3 5000VA Terminal Block Communication Internal Battery Packs Removable Power Distribution BoxOuter Surface View Power Distribution Box Quick-Connect WHAT’S Included Installation and Configuration Install the Main CabinetTower UPS Installation Connectors Spacers Support BasesInstalling the Adjustable Rack-Mount Kit-Sold Separately Rack-Mount UPS InstallationOperation and Display Panel Rotated Clockwise 90 Degrees Quantity813mm UPS or batteryDepth Retaining latchUPS or battery cabinet Apply grease External Battery Cabinet InstallationTo remove Connect Input/Output PowerTo install Electrical specifications HardwireTerminal Block ConnectionsDistribution Box Electrical Connections Branch circuit breaker ratingsConfiguration Program Features Configuration ProgramWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsStandby/Manual Bypass Button Battery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberUPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Startup Checklist for the Liebert GXT3 Initial Startup and Electrical ChecksOperation Disconnecting Input Power from the Liebert GXT3 Manual Battery TestMaintenance Bypass Put the Liebert GXT3 in Manual BypassRemove Screws IT Power System Connectors IT Power System ConfigurationBattery Mode Shutdown Any Mode ShutdownCommunication Interface Port Dry ContactOn Battery Low BatteryLiebert IntelliSlot Communication Cards Remote Emergency Power Off Repo switch connection diagramLiebert MultiLink Replacing the Internal Battery Pack MaintenanceBattery Replacement Procedures Precautions Battery ChargingChecking UPS Functions Checking UPS StatusTroubleshooting UPS SymptomsIndicators Indicator Diagnosis/Audible alarmAudible Alarm Audible alarm descriptionCondition Alarm Problem Cause Solution Troubleshooting tableIlluminated UPS specifications SpecificationsOperating temperature parameters Power distribution specificationsExternal battery cabinet specifications Auto-Learning Battery Run Times Page Is t Ne tTwor k Care