Communication

9.0COMMUNICATION

9.1Communication Interface Port

The Liebert® GXT3UPS has a terminal block on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows.

9.2Dry Contact

The Dry Contact includes eight pins, as shown in Figure 14.

Figure 14 Dry contact pin layout

1

2

3

4

(Low Battery

 

Warning)

 

(Any Mode

 

Shutdown)

 

 

 

 

 

 

(On- Battery

 

Warning)

 

(Battery Mode

 

Shutdown)

 

 

 

 

 

9.2.1Any Mode Shutdown

The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter and static switch so that there is no power to the loads.

Any Mode Shutdown can be operated locally or remotely:

Local Any Mode Shutdown can be performed by shorting the pins in Set 3.

Remote Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and mounted at a remote location.

Activation of the Any Mode Shutdown will be logged as an event in the event history log.

NOTE

Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown. The current limited source (+12VDC, 50mA) will be available from UPS.

The connection to UPS for remote connection will be via terminal block connector.

Any Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.

! WARNING

When the Auto-enable output option is selected and the UPS output is disabled using the pins in Set 3, the Liebert GXT3-G’s output can turn On automatically and without warning if the connection of the pins in Set 3 is changed.

9.2.2Battery Mode Shutdown

Battery Mode Shutdown permits shutting down the UPS by turning off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active.

Battery Mode Shutdown can be performed locally or remotely:

Local Battery Mode shutdown can be performed by shorting the pins in Set 4.

Remote Battery Mode Shutdown can be performed using a switch connected the pins in Set 4 and mounted at remote location.

Activation of the Battery Mode Shutdown will be logged as an event in the event history log.

24

Image 30
Contents Liebert GXT3 230V,5000VA-UL Listed Page Table of Contents Specifications MaintenanceTroubleshooting CommunicationFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionBattery DC-to-DC ConverterDynamic Bypass Main Frame and Electronics Major ComponentsLiebert GXT3 5000VA Terminal Block Communication Internal Battery Packs Removable Power Distribution BoxOuter Surface View Power Distribution Box Quick-Connect WHAT’S Included Tower UPS Installation Install the Main CabinetInstallation and Configuration Connectors Spacers Support BasesOperation and Display Panel Rotated Clockwise 90 Degrees Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityDepth UPS or battery813mm Retaining latchExternal Battery Cabinet Installation UPS or battery cabinet Apply greaseConnect Input/Output Power To removeTo install Distribution Box Electrical Connections HardwireTerminal Block ConnectionsElectrical specifications Branch circuit breaker ratingsConfiguration Program Features Configuration ProgramWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsStandby/Manual Bypass Button Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Startup Checklist for the Liebert GXT3 Initial Startup and Electrical ChecksOperation Maintenance Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Put the Liebert GXT3 in Manual BypassIT Power System Configuration Remove Screws IT Power System ConnectorsCommunication Interface Port Any Mode ShutdownBattery Mode Shutdown Dry ContactOn Battery Low BatteryLiebert IntelliSlot Communication Cards Remote Emergency Power Off Repo switch connection diagramLiebert MultiLink Replacing the Internal Battery Pack MaintenanceBattery Replacement Procedures Battery Charging PrecautionsChecking UPS Status Checking UPS FunctionsIndicators UPS SymptomsTroubleshooting Indicator Diagnosis/Audible alarmAudible Alarm Audible alarm descriptionCondition Alarm Troubleshooting table Problem Cause SolutionIlluminated Specifications UPS specificationsOperating temperature parameters Power distribution specificationsExternal battery cabinet specifications Auto-Learning Battery Run Times Page Twor k Ne tIs t Care