Emerson GXT3 230V user manual Specifications, UPS specifications

Page 40

Specifications

12.0SPECIFICATIONS

Table 7

UPS specifications

 

 

 

 

 

Model #

Liebert® GXT35000RT230U

Rating

 

5000VA/4000W

Dimensions, mm (in)

 

 

Unit, W x D x H

570 x 430 x 220 (22.4 x 16.9 x 8.7)

 

 

 

 

Shipping, W x D x H

745 x 530 x 516 (29.3 x 20.9 x 20.3)

 

 

Weight, kg (lb)

 

 

Unit

60 (132.2)

 

 

 

 

Shipping

71 (156.5)

 

 

Input AC Parameters

 

 

Operating Frequency, Nom

50 or 60Hz (Factory Default = 50)

 

 

 

 

Factory Default VAC

230VAC

 

 

 

 

User-Configurable VAC

220/230/240VAC

 

(May be modified using included configuration program)

 

 

Operating Voltage Range Without Battery Operation

176 - 280VAC

 

 

 

 

Maximum Allowable VAC

280VAC

 

 

 

 

Input Frequency Without Battery Operation

40 - 70Hz

 

 

 

 

Input Power Connection

Hardwire Terminal Block Standard

 

(See 3.3 - Removable Power Distribution Box)

 

 

 

 

Output AC Parameters

 

 

Factory Default VAC

230VAC

 

 

 

 

Output Connections

Hardwire Terminal Block Standard

 

(See 3.3 - Removable Power Distribution Box)

 

 

 

 

 

 

Frequency

50Hz or 60Hz, Nominal

 

 

 

 

Waveform

Sinewave

 

 

 

 

Main Mode Overload

>200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10

 

 

seconds; 105 - 130% 1 minute

Battery Parameters

 

 

Type

Valve-regulated, non-spillable, lead acid

 

Quantity x V

20 x 12V

 

 

 

 

Battery Mfr. / Part #

5AH battery, CSB HR1221W or YUASA NPH5-12

 

 

 

 

Backup Time

See Table 11 - Typical battery run times, minutes at 25°C

 

 

(77°F ), 100% resistive load and

 

Recharge Time (Internal Batteries)

3 hr. to 90% capacity after full discharge into 100% load

 

 

Bypass Protection Limits

 

 

Disable Bypass Operation

If input voltage exceeds ±15% of the nominal voltage

 

 

 

 

Re-Enable Bypass Operation

If input voltage returns to within ±10% of nominal output

 

voltage

 

 

 

Disable Bypass operation

When the input frequency prevents synchronous operation

 

 

Environmental

 

 

Operating Temperature, °C (°F)

0 to 40 (32 to 104) see Table 8 - Operating temperature

 

parameters

 

 

 

Storage Temperature, °C (°F)

-15 to 50 (5 to 122)

 

 

 

 

Relative Humidity

0-95% non-condensing

 

Operating Elevation

Up to 1000m (3281 ft) at 25°C (77°F) without derating

 

 

 

 

Audible Noise

<55 dBA at 1 meter from the rear;

 

<50 dBA, at 1 meter from the front or sides

 

 

34

Image 40
Contents Liebert GXT3 230V,5000VA-UL Listed Page Table of Contents Maintenance TroubleshootingSpecifications CommunicationFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionDC-to-DC Converter BatteryDynamic Bypass Major Components Main Frame and ElectronicsLiebert GXT3 5000VA Terminal Block Communication Removable Power Distribution Box Internal Battery PacksOuter Surface View Power Distribution Box Quick-Connect WHAT’S Included Install the Main Cabinet Installation and ConfigurationTower UPS Installation Connectors Spacers Support BasesRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyOperation and Display Panel Rotated Clockwise 90 Degrees QuantityUPS or battery 813mmDepth Retaining latchExternal Battery Cabinet Installation UPS or battery cabinet Apply greaseConnect Input/Output Power To removeTo install HardwireTerminal Block Connections Electrical specificationsDistribution Box Electrical Connections Branch circuit breaker ratingsConfiguration Program Configuration Program FeaturesWhat You Will Need Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonStandby/Manual Bypass Button Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Initial Startup and Electrical Checks Startup Checklist for the Liebert GXT3Operation Manual Battery Test Disconnecting Input Power from the Liebert GXT3Maintenance Bypass Put the Liebert GXT3 in Manual BypassIT Power System Configuration Remove Screws IT Power System ConnectorsAny Mode Shutdown Battery Mode ShutdownCommunication Interface Port Dry ContactLow Battery On BatteryLiebert IntelliSlot Communication Cards Repo switch connection diagram Remote Emergency Power OffLiebert MultiLink Maintenance Replacing the Internal Battery PackBattery Replacement Procedures Battery Charging PrecautionsChecking UPS Status Checking UPS FunctionsUPS Symptoms TroubleshootingIndicators Indicator Diagnosis/Audible alarmAudible alarm description Audible AlarmCondition Alarm Troubleshooting table Problem Cause SolutionIlluminated Specifications UPS specificationsPower distribution specifications Operating temperature parametersExternal battery cabinet specifications Auto-Learning Battery Run Times Page Ne t Is tTwor k Care