Troubleshooting
11.2Troubleshooting
In the event of an issue with the UPS, refer to Table 6 to determine the cause and solution. If the fault persists, contact Emerson Channel Support.
Table 6 Troubleshooting table
Problem | Cause | Solution | |
UPS fails to start when the | UPS is | Ensure UPS is Off. Disconnect all loads and ensure | |
On/Alarm Silence/Manual | nothing is lodged in output receptacles. Ensure loads | ||
overloaded | |||
Battery Test button is pressed | are not defective or shorted internally. | ||
| |||
|
|
| |
| UPS is not plugged in | UPS is operating from battery mode. Ensure UPS is | |
| securely plugged into the wall receptacle. | ||
|
| ||
| UPS input protection fuse has | UPS is operating from battery mode. Save data and | |
| close applications. Replace UPS input fuse, then restart | ||
Battery indicator is illuminated | blown/opened | ||
UPS. | |||
|
| ||
|
| UPS is operating from battery mode. Save data and | |
| Mains power is out of tolerance | close applications. Ensure mains supply voltage is | |
|
| within acceptable limits for UPS. | |
| Batteries are not fully charged | Keep UPS plugged in continuously at least 24 hours to | |
| recharge batteries. | ||
|
| ||
UPS has reduced battery | UPS is overloaded | Check load level indicator and reduce the load on the | |
UPS. | |||
backup time |
| ||
Batteries may not be able to | Replace batteries. Contact your local dealer, Emerson | ||
| |||
| representative or Emerson Channel Support for | ||
| hold a full charge due to age | ||
| replacement battery kit. | ||
|
| ||
|
|
| |
Fault and Bypass indicators |
| Check load level indicator and remove | |
and all LED segments of | UPS is overloaded or load is | ||
loads. Recalculate the load and reduce number of loads | |||
battery level indicator are | faulty | ||
connected to UPS. Check load for faults. | |||
illuminated |
| ||
|
| ||
|
|
| |
|
| Ensure UPS is not overloaded, ventilation holes are not | |
Fault and Bypass indicators | UPS has been shut down due | blocked and room ambient temperature is not | |
excessive. Wait 30 minutes to allow UPS to cool, then | |||
and diagnostic A indicator are | to temperature condition; load | ||
restart UPS. If UPS cannot restart, contact your local | |||
illuminated | is on bypass power | ||
dealer, Emerson representative or Emerson Channel | |||
|
| ||
|
| Support. | |
|
|
| |
Fault and Bypass indicators | UPS internal DC bus | UPS requires service. Contact your local dealer, | |
and diagnostic B indicator are | |||
overvoltage | Emerson representative or Emerson Channel Support. | ||
illuminated | |||
|
| ||
|
|
| |
Fault and Bypass indicators |
| UPS requires service. Contact your local dealer, | |
and diagnostic C indicator are | UPS DC/DC fault | ||
Emerson representative or Emerson Channel Support. | |||
illuminated |
| ||
|
| ||
|
|
| |
Fault indicator and diagnostic | UPS PFC (Power Factor | UPS requires service. Contact your local dealer, | |
D indicator are illuminated | Correction Circuit) fault | Emerson representative or Emerson Channel Support. | |
|
|
| |
Fault and Bypass indicators |
| UPS requires service. Contact your local dealer, | |
and diagnostic E indicator are | UPS inverter fault | ||
Emerson representative or Emerson Channel Support. | |||
illuminated |
| ||
|
| ||
|
|
| |
Fault indicator and diagnostic |
| Replace batteries. Contact your local dealer, Emerson | |
A and C indicators are | UPS failed the battery test | ||
representative or Emerson Channel Support. | |||
illuminated |
| ||
|
| ||
|
|
| |
|
| Your UPS has received a signal or command from the | |
Fault and Bypass indicators | UPS has been shut down by a | attached computer. If this was inadvertent, ensure the | |
and diagnostic C and E | command from the | communication cable used is correct for your system. | |
indicators are illuminated | communications port(s) | For assistance, contact your local dealer, Emerson | |
|
| representative or Emerson Channel Support. |