Emerson GXT3 230V user manual Troubleshooting table, Problem Cause Solution

Page 38

Troubleshooting

11.2Troubleshooting

In the event of an issue with the UPS, refer to Table 6 to determine the cause and solution. If the fault persists, contact Emerson Channel Support.

Table 6 Troubleshooting table

Problem

Cause

Solution

UPS fails to start when the

UPS is short-circuited or

Ensure UPS is Off. Disconnect all loads and ensure

On/Alarm Silence/Manual

nothing is lodged in output receptacles. Ensure loads

overloaded

Battery Test button is pressed

are not defective or shorted internally.

 

 

 

 

 

UPS is not plugged in

UPS is operating from battery mode. Ensure UPS is

 

securely plugged into the wall receptacle.

 

 

 

UPS input protection fuse has

UPS is operating from battery mode. Save data and

 

close applications. Replace UPS input fuse, then restart

Battery indicator is illuminated

blown/opened

UPS.

 

 

 

 

UPS is operating from battery mode. Save data and

 

Mains power is out of tolerance

close applications. Ensure mains supply voltage is

 

 

within acceptable limits for UPS.

 

Batteries are not fully charged

Keep UPS plugged in continuously at least 24 hours to

 

recharge batteries.

 

 

UPS has reduced battery

UPS is overloaded

Check load level indicator and reduce the load on the

UPS.

backup time

 

Batteries may not be able to

Replace batteries. Contact your local dealer, Emerson

 

 

representative or Emerson Channel Support for

 

hold a full charge due to age

 

replacement battery kit.

 

 

 

 

 

Fault and Bypass indicators

 

Check load level indicator and remove non-essential

and all LED segments of

UPS is overloaded or load is

loads. Recalculate the load and reduce number of loads

battery level indicator are

faulty

connected to UPS. Check load for faults.

illuminated

 

 

 

 

 

 

 

 

Ensure UPS is not overloaded, ventilation holes are not

Fault and Bypass indicators

UPS has been shut down due

blocked and room ambient temperature is not

excessive. Wait 30 minutes to allow UPS to cool, then

and diagnostic A indicator are

to temperature condition; load

restart UPS. If UPS cannot restart, contact your local

illuminated

is on bypass power

dealer, Emerson representative or Emerson Channel

 

 

 

 

Support.

 

 

 

Fault and Bypass indicators

UPS internal DC bus

UPS requires service. Contact your local dealer,

and diagnostic B indicator are

overvoltage

Emerson representative or Emerson Channel Support.

illuminated

 

 

 

 

 

Fault and Bypass indicators

 

UPS requires service. Contact your local dealer,

and diagnostic C indicator are

UPS DC/DC fault

Emerson representative or Emerson Channel Support.

illuminated

 

 

 

 

 

 

Fault indicator and diagnostic

UPS PFC (Power Factor

UPS requires service. Contact your local dealer,

D indicator are illuminated

Correction Circuit) fault

Emerson representative or Emerson Channel Support.

 

 

 

Fault and Bypass indicators

 

UPS requires service. Contact your local dealer,

and diagnostic E indicator are

UPS inverter fault

Emerson representative or Emerson Channel Support.

illuminated

 

 

 

 

 

 

Fault indicator and diagnostic

 

Replace batteries. Contact your local dealer, Emerson

A and C indicators are

UPS failed the battery test

representative or Emerson Channel Support.

illuminated

 

 

 

 

 

 

 

 

Your UPS has received a signal or command from the

Fault and Bypass indicators

UPS has been shut down by a

attached computer. If this was inadvertent, ensure the

and diagnostic C and E

command from the

communication cable used is correct for your system.

indicators are illuminated

communications port(s)

For assistance, contact your local dealer, Emerson

 

 

representative or Emerson Channel Support.

32

Image 38
Contents Liebert GXT3 230V,5000VA-UL Listed Page Table of Contents Specifications MaintenanceTroubleshooting CommunicationFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionDynamic Bypass BatteryDC-to-DC Converter Liebert GXT3 5000VA Terminal Block Communication Main Frame and ElectronicsMajor Components Outer Surface View Power Distribution Box Quick-Connect Internal Battery PacksRemovable Power Distribution Box WHAT’S Included Tower UPS Installation Install the Main CabinetInstallation and Configuration Connectors Spacers Support BasesOperation and Display Panel Rotated Clockwise 90 Degrees Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityDepth UPS or battery813mm Retaining latchExternal Battery Cabinet Installation UPS or battery cabinet Apply greaseConnect Input/Output Power To removeTo install Distribution Box Electrical Connections HardwireTerminal Block ConnectionsElectrical specifications Branch circuit breaker ratingsWhat You Will Need Configuration Program FeaturesConfiguration Program Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Operation Startup Checklist for the Liebert GXT3Initial Startup and Electrical Checks Maintenance Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Put the Liebert GXT3 in Manual BypassIT Power System Configuration Remove Screws IT Power System ConnectorsCommunication Interface Port Any Mode ShutdownBattery Mode Shutdown Dry ContactLiebert IntelliSlot Communication Cards On BatteryLow Battery Liebert MultiLink Remote Emergency Power OffRepo switch connection diagram Battery Replacement Procedures Replacing the Internal Battery PackMaintenance Battery Charging PrecautionsChecking UPS Status Checking UPS FunctionsIndicators UPS SymptomsTroubleshooting Indicator Diagnosis/Audible alarmCondition Alarm Audible AlarmAudible alarm description Troubleshooting table Problem Cause SolutionIlluminated Specifications UPS specificationsExternal battery cabinet specifications Operating temperature parametersPower distribution specifications Auto-Learning Battery Run Times Page Twor k Ne tIs t Care