Emerson GXT3 230V user manual Connect Input/Output Power, To remove

Page 20

Installation and Configuration

1.Visually inspect the external battery cabinet for freight damage. Report damage to the carrier and your local dealer or Liebert® representative.

2.For slide rail installations, first remove the top/side fin. Top/side fin slides forward and then lift up to remove. Optional rack-mount handles are shipped with the external battery cabinet and may be installed at this time if desired.

3.Securing hardware and slide rails are sold separately. Please contact your local dealer or Liebert representative for these additional options and any assistance needed. Fasten the slides into position with the screws per the instructions included with the slide rails.

4.Use the enclosed support bases for the tower option to prevent tip-over. One additional set of support base extensions ships with each external battery cabinet.

5.Put the UPS in Bypass Mode by pressing the bypass button on the front of the unit one time.

6.Verify the External Battery Cabinet breaker is in the Off position.

7.Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, then to the rear of the UPS.

8.Turn the External Battery Cabinet breaker to the On position.

9.Press the On button on the front of the UPS for 4 seconds to return the unit to inverter Mode.

10.Verify the circuit breaker on the External Battery Cabinet is in the On position.

11.Use the included configuration program to program the UPS for the number of external battery cabinets connected. Instructions for the configuration program are in 6.0 - Configuration Program.

12.The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to Table 11.

NOTE

When removing the External Battery Cabinet, the circuit breaker on the rear of the cabinet must be turned off before disconnecting the cable.

NOTE

If the UPS is to be shipped or stored for an extended time, the connector should be disconnected. This will minimize any standby current drain on the batteries and help attain their design life.

5.3Connect Input/Output Power

Figure 9 Power Distribution box removal—captive screws and maintenance bypass breaker

 

 

 

 

Maintenance

 

 

 

 

Extract these

 

 

Bypass Breaker

 

 

 

 

captive screws

 

 

The UPS should arrive with the power distribution box attached. If the box needs to be removed for maintenance or replacement, follow these instructions to remove and install the power distribution pack.

To remove:

1.Ensure maintenance bypass lamp is on. To place the unit in maintenance bypass, see 8.4 - Put the Liebert® GXT3in Manual Bypass.

2.Loosen one captive screw over the maintenance bypass breaker.

3.Turn the maintenance bypass breaker on.

NOTICE

The load is unprotected from disturbances in the power supply while the UPS is on bypass.

14

Image 20
Contents Liebert GXT3 230V,5000VA-UL Listed Page Table of Contents Maintenance TroubleshootingSpecifications CommunicationFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionDynamic Bypass BatteryDC-to-DC Converter Liebert GXT3 5000VA Terminal Block Communication Main Frame and ElectronicsMajor Components Outer Surface View Power Distribution Box Quick-Connect Internal Battery PacksRemovable Power Distribution Box WHAT’S Included Install the Main Cabinet Installation and ConfigurationTower UPS Installation Connectors Spacers Support BasesRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyOperation and Display Panel Rotated Clockwise 90 Degrees QuantityUPS or battery 813mmDepth Retaining latchExternal Battery Cabinet Installation UPS or battery cabinet Apply greaseConnect Input/Output Power To removeTo install HardwireTerminal Block Connections Electrical specificationsDistribution Box Electrical Connections Branch circuit breaker ratingsWhat You Will Need Configuration Program FeaturesConfiguration Program Standby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS Status Indicator Icon Color Description UPS Status IndicatorsUPS status indicators Operation Startup Checklist for the Liebert GXT3Initial Startup and Electrical Checks Manual Battery Test Disconnecting Input Power from the Liebert GXT3Maintenance Bypass Put the Liebert GXT3 in Manual BypassIT Power System Configuration Remove Screws IT Power System ConnectorsAny Mode Shutdown Battery Mode ShutdownCommunication Interface Port Dry ContactLiebert IntelliSlot Communication Cards On BatteryLow Battery Liebert MultiLink Remote Emergency Power OffRepo switch connection diagram Battery Replacement Procedures Replacing the Internal Battery PackMaintenance Battery Charging PrecautionsChecking UPS Status Checking UPS FunctionsUPS Symptoms TroubleshootingIndicators Indicator Diagnosis/Audible alarmCondition Alarm Audible AlarmAudible alarm description Troubleshooting table Problem Cause SolutionIlluminated Specifications UPS specificationsExternal battery cabinet specifications Operating temperature parametersPower distribution specifications Auto-Learning Battery Run Times Page Ne t Is tTwor k Care