Emerson GXT3 230V Manual Battery Test, Put the Liebert GXT3 in Manual Bypass, Maintenance Bypass

Page 28

Operation

8.3Manual Battery Test

To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least half a second while operating from mains power with no alarm conditions present.

If only the first two of the five LED segments illuminate, allow the UPS to recharge the batteries for 24 hours.

Retest the batteries after 24 hours of charging.

After the batteries have been retested, if only two of the five Battery LEDs illuminate, contact your local Emerson representative or Emerson Network Power Channel Support.

If none of the five Battery LEDs illuminate during a manual battery test, check the battery con- nection and allow the UPS to recharge the batteries for 1 hour, then initiate a manual battery test again.

If none of the five Battery LEDs illuminate during the second manual battery test, replace batter- ies and contact your local Emerson representative or Emerson Channel Support.

8.4Put the Liebert® GXT3in Manual Bypass

Press the Standby/Manual Bypass button once while the UPS is in Mains (AC) Mode. The UPS will transfer the connected loads to the internal bypass. If the internal bypass is not available because of mains power problems, pressing this button once will be ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If other indicators are illuminated, refer to

11.0 - Troubleshooting.)

8.5Shut Down the Liebert GXT3

1.Transfer the UPS to manual bypass by pressing the Standby/Manual Bypass button once. If manual bypass is not available, disregard the first step.

2.Press the Standby/Manual Bypass button twice within four seconds to shut down the UPS.

Power to the connected loads is now Off.

8.6Disconnecting Input Power from the Liebert GXT3

1.After the UPS has been shut down as detailed in 8.5 - Shut Down the Liebert GXT3, turn off the Output Circuit Breaker.

2.Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates that the power-off is complete.

3.Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet.

After powering off the UPS, the UPS ceases output and the load is powered Off.

8.7Maintenance Bypass

Maintenance Bypass Mode is used when maintenance or replacement is required. To place the unit in Maintenance Bypass:

1.Place the UPS on internal bypass. This may be done by either of the following methods:

a.Press the Off button on the front panel one time.

b.Slide the bracket away from the manual bypass breaker on the rear of the UPS. This requires loosening the captive screw and sliding the bracket up and away from the Manual Bypass Breaker.

2.Move the Manual Bypass Breaker on the rear of the UPS to the bypass position. This requires loosening the captive screw and sliding the bracket up and away from the manual bypass breaker.

22

Image 28
Contents Liebert GXT3 230V,5000VA-UL Listed Page Table of Contents Maintenance TroubleshootingSpecifications CommunicationFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionDC-to-DC Converter BatteryDynamic Bypass Major Components Main Frame and ElectronicsLiebert GXT3 5000VA Terminal Block Communication Removable Power Distribution Box Internal Battery PacksOuter Surface View Power Distribution Box Quick-Connect WHAT’S Included Install the Main Cabinet Installation and ConfigurationTower UPS Installation Connectors Spacers Support BasesRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyOperation and Display Panel Rotated Clockwise 90 Degrees QuantityUPS or battery 813mmDepth Retaining latchExternal Battery Cabinet Installation UPS or battery cabinet Apply greaseConnect Input/Output Power To removeTo install HardwireTerminal Block Connections Electrical specificationsDistribution Box Electrical Connections Branch circuit breaker ratingsConfiguration Program Configuration Program FeaturesWhat You Will Need Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonStandby/Manual Bypass Button Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Initial Startup and Electrical Checks Startup Checklist for the Liebert GXT3Operation Manual Battery Test Disconnecting Input Power from the Liebert GXT3Maintenance Bypass Put the Liebert GXT3 in Manual BypassIT Power System Configuration Remove Screws IT Power System ConnectorsAny Mode Shutdown Battery Mode ShutdownCommunication Interface Port Dry ContactLow Battery On BatteryLiebert IntelliSlot Communication Cards Repo switch connection diagram Remote Emergency Power OffLiebert MultiLink Maintenance Replacing the Internal Battery PackBattery Replacement Procedures Battery Charging PrecautionsChecking UPS Status Checking UPS FunctionsUPS Symptoms TroubleshootingIndicators Indicator Diagnosis/Audible alarmAudible alarm description Audible AlarmCondition Alarm Troubleshooting table Problem Cause SolutionIlluminated Specifications UPS specificationsPower distribution specifications Operating temperature parametersExternal battery cabinet specifications Auto-Learning Battery Run Times Page Ne t Is tTwor k Care