Emerson GXT3 230V UPS Symptoms, Troubleshooting, Indicators, Indicator Diagnosis/Audible alarm

Page 36

Troubleshooting

11.0TROUBLESHOOTING

This section indicates various UPS symptoms a user may encounter and provides a troubleshooting guide in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation.

11.1UPS Symptoms

The following symptoms indicate the Liebert® GXT3is malfunctioning:

The relative indicators illuminate, indicating the UPS has detected a problem.

An alarm buzzer sounds, alerting the user that the UPS requires attention.

11.1.1Indicators

In addition to the fault indicator being illuminated, one or more of LED segments of battery level indicator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 18. The descriptions are listed in Table 4.

Figure 18 Battery level indicator

 

 

 

 

 

 

 

 

 

 

 

 

A

B

C

D

E

 

Table 4

Indicator descriptions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicator

Diagnosis/Audible alarm

 

 

 

 

 

 

 

 

 

 

 

A-E

On bypass from output overload (half-second beep every half second)

 

 

 

 

 

 

 

A

On bypass due to overtemperature condition (1-second beep every 4 seconds)

 

 

 

 

 

 

 

B

On bypass due to DC bus overvoltage (1-second beep every 4 seconds)

 

 

 

 

 

 

 

C

On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)

 

 

 

 

 

 

 

D

PFC failure (1-second beep every 4 seconds)

 

 

 

 

 

 

 

 

 

E

On bypass due to inverter failure (1-second beep every 4 seconds)

 

 

 

 

 

 

 

A&B

UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and

 

battery charger failure) and continuous alarm

 

 

 

 

 

 

 

 

A&C

UPS failed battery test (2-second beep every 60 seconds)

 

 

 

 

 

 

 

A&D

Maintance bypass switch on (continuous)

 

 

 

 

 

 

 

 

 

A&E

Bypass feedback (1-second beep every 4 seconds)

 

 

 

 

 

 

 

B&C

REPO (one quarter-second beep every one-quarter of a second)

 

 

 

 

 

 

 

 

 

B&E

Short circuit on the output

 

 

 

 

 

 

 

 

 

 

 

C&E

UPS shutdown by command from communication (USB port or Liebert IntelliSlot®

 

port) (no audible)

 

 

 

 

 

 

 

 

 

 

 

 

 

Utility LED flash

L-N reverse

 

 

 

 

 

 

 

 

 

 

 

Battery Indicator Flashing

Internal battery source not available (continuous horn); check battery connection,

power down, reboot UPS

 

 

 

 

 

 

 

 

 

 

 

Bypass Indicator Flashing

Utility power voltage or frequency is out of tolerance; bypass is unavailable

 

 

 

 

 

 

 

 

 

30

Image 36
Contents Liebert GXT3 230V,5000VA-UL Listed Page Table of Contents Maintenance TroubleshootingSpecifications CommunicationFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionBattery DC-to-DC ConverterDynamic Bypass Main Frame and Electronics Major ComponentsLiebert GXT3 5000VA Terminal Block Communication Internal Battery Packs Removable Power Distribution BoxOuter Surface View Power Distribution Box Quick-Connect WHAT’S Included Install the Main Cabinet Installation and ConfigurationTower UPS Installation Connectors Spacers Support BasesRack-Mount UPS Installation Installing the Adjustable Rack-Mount Kit-Sold SeparatelyOperation and Display Panel Rotated Clockwise 90 Degrees QuantityUPS or battery 813mmDepth Retaining latchExternal Battery Cabinet Installation UPS or battery cabinet Apply greaseConnect Input/Output Power To removeTo install HardwireTerminal Block Connections Electrical specificationsDistribution Box Electrical Connections Branch circuit breaker ratingsConfiguration Program Features Configuration ProgramWhat You Will Need ON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsStandby/Manual Bypass Button Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenUPS Status Indicators UPS status indicatorsUPS Status Indicator Icon Color Description Startup Checklist for the Liebert GXT3 Initial Startup and Electrical ChecksOperation Manual Battery Test Disconnecting Input Power from the Liebert GXT3Maintenance Bypass Put the Liebert GXT3 in Manual BypassIT Power System Configuration Remove Screws IT Power System ConnectorsAny Mode Shutdown Battery Mode ShutdownCommunication Interface Port Dry ContactOn Battery Low BatteryLiebert IntelliSlot Communication Cards Remote Emergency Power Off Repo switch connection diagramLiebert MultiLink Replacing the Internal Battery Pack MaintenanceBattery Replacement Procedures Battery Charging PrecautionsChecking UPS Status Checking UPS FunctionsUPS Symptoms TroubleshootingIndicators Indicator Diagnosis/Audible alarmAudible Alarm Audible alarm descriptionCondition Alarm Troubleshooting table Problem Cause SolutionIlluminated Specifications UPS specificationsOperating temperature parameters Power distribution specificationsExternal battery cabinet specifications Auto-Learning Battery Run Times Page Ne t Is tTwor k Care