Emerson GXT3 230V External Battery Cabinet Installation, UPS or battery cabinet Apply grease

Page 19
Apply grease (inside)
Insert the UPS into the front members, lift the front and push it into the rack..

Installation and Configuration

6.If available, apply a bead of grease 25mm (1") long at four (4) places inside the bottom, curved tracks of the front members as shown below right. The grease will allow the equipment to slide into the bracket assemblies more easily.

! CAUTION

Lifting equipment into the rack may be a two-person job, depending on the weight of the equipment. Liebert® recommends taking the internal batteries out of the UPS during rack installation. This will make the UPS cabinet lighter and easier to handle. For the weight of the UPS, see Table 7; for the battery cabinet’s weight, see Table 10.

UPS or battery cabinet

Apply grease

7.Insert the equipment, with inner members attached in Step 5, into the bracket assemblies by inserting the top and

bottom edges of the inner members into the top and bottom curved tracks of the front members and sliding the equipment into the rack (see figure at right). Ends of inner

members are tapered to allow the rear of the equipment to be angled upward before insertion, if space allows.

Then the rear, bottom edges of the inner members can be placed into the front edge of the bottom tracks and the front of the equipment can be tipped up so they are level to insert the top edges of the inner members before sliding the equipment into the rack (see figure below right). The equip- ment should move smoothly into the bracket assemblies. If it does not, recheck the alignment of the front and rear members from Steps 2 3.

8.Secure the front of the equipment to the rack mounting rails to prevent the equipment from sliding out of position. If securing holes are provided on the front of the equipment that align with the center holes on the return flange of the front members, you can use the four (4) extra M5 screws provided in the kit to secure the equipment. Otherwise, the equipment should be secured to the front of the rack with four (4) customer-supplied fasteners.

5.2External Battery Cabinet Installation

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed on one side of the UPS or stacked beneath the UPS. External battery cabinets can be used in either a rack-mount or tower configuration.

! CAUTION

The external battery cabinet(s) are heavy (see 12.0 - Specifications). Take proper precautions when lifting them.

Figure 8 External battery cabinets connected to Liebert GXT3

10,000VA Liebert GXT3

Battery Cabinets

Cables connecting battery cabinets to 10,000VA Liebert® GXT3; 5000VA external battery packs have same features

13

Image 19
Contents Liebert GXT3 230V,5000VA-UL Listed Page Table of Contents Communication MaintenanceTroubleshooting SpecificationsFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction System Description Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterDC-to-DC Converter BatteryDynamic Bypass Major Components Main Frame and ElectronicsLiebert GXT3 5000VA Terminal Block Communication Removable Power Distribution Box Internal Battery PacksOuter Surface View Power Distribution Box Quick-Connect WHAT’S Included Connectors Spacers Support Bases Install the Main CabinetInstallation and Configuration Tower UPS InstallationQuantity Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately Operation and Display Panel Rotated Clockwise 90 DegreesRetaining latch UPS or battery813mm DepthUPS or battery cabinet Apply grease External Battery Cabinet InstallationTo remove Connect Input/Output PowerTo install Branch circuit breaker ratings HardwireTerminal Block ConnectionsElectrical specifications Distribution Box Electrical ConnectionsConfiguration Program Configuration Program FeaturesWhat You Will Need Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonStandby/Manual Bypass Button Battery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberUPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Initial Startup and Electrical Checks Startup Checklist for the Liebert GXT3Operation Put the Liebert GXT3 in Manual Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Maintenance BypassRemove Screws IT Power System Connectors IT Power System ConfigurationDry Contact Any Mode ShutdownBattery Mode Shutdown Communication Interface PortLow Battery On BatteryLiebert IntelliSlot Communication Cards Repo switch connection diagram Remote Emergency Power OffLiebert MultiLink Maintenance Replacing the Internal Battery PackBattery Replacement Procedures Precautions Battery ChargingChecking UPS Functions Checking UPS StatusIndicator Diagnosis/Audible alarm UPS SymptomsTroubleshooting IndicatorsAudible alarm description Audible AlarmCondition Alarm Problem Cause Solution Troubleshooting tableIlluminated UPS specifications SpecificationsPower distribution specifications Operating temperature parametersExternal battery cabinet specifications Auto-Learning Battery Run Times Page Care Ne tIs t Twor k