Communication

NOTE

Remote Power Off will be performed by NO contact.

The current limited source (+12VDC, 50mA) will be available from UPS.

The connection to the Liebert® GXT3for remote connection will be via terminal block connector.

Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.

This signal must last for 1.5 seconds or longer.

A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown timer. This timer cannot be stopped once triggered. If the utility power returns during this countdown, the Liebert GXT3 will still shut down and must remain shut down for 10 seconds. Whether the UPS turns back On when the power is restored depends on the auto-restart setting.

9.2.3On Battery

On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this dry contact will be closed.

9.2.4Low Battery

Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery and has reached the Low Battery Warning time selected in the configuration program, this dry contact will be closed.

NOTE

The rated values for the dry contacts are:

Rated Voltage: 30V (AC or DC)

Rated Current: 300mA

9.3Liebert IntelliSlot® Communication Cards

The Liebert IntelliSlot port on the UPS accepts three optional cards:

Liebert IntelliSlot SNMP Card

Liebert IntelliSlot Relay Card

Liebert IntelliSlot 485 Card.

The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the network.

The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and delivers support for built-in shutdown for AS/400 systems.

The Liebert IntelliSlot 485 Card is used to connect the UPS and computer system.

Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the UPS or any additional ancillary product for the Liebert GXT3. These instructions are available at multilink.liebert.com

25

Image 31
Contents Liebert GXT3 230V,5000VA-UL Listed Page Table of Contents Communication MaintenanceTroubleshooting SpecificationsFigures Page Important Safety Instructions Information for the Protection of the Environment Glossary of Symbols Introduction System Description Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterDC-to-DC Converter BatteryDynamic Bypass Major Components Main Frame and ElectronicsLiebert GXT3 5000VA Terminal Block Communication Removable Power Distribution Box Internal Battery PacksOuter Surface View Power Distribution Box Quick-Connect WHAT’S Included Connectors Spacers Support Bases Install the Main CabinetInstallation and Configuration Tower UPS InstallationQuantity Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately Operation and Display Panel Rotated Clockwise 90 DegreesRetaining latch UPS or battery813mm DepthUPS or battery cabinet Apply grease External Battery Cabinet InstallationTo remove Connect Input/Output PowerTo install Branch circuit breaker ratings HardwireTerminal Block ConnectionsElectrical specifications Distribution Box Electrical ConnectionsConfiguration Program Configuration Program FeaturesWhat You Will Need Controls and Indicators ON/Alarm Silence/Manual Battery Test ButtonStandby/Manual Bypass Button Battery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberUPS status indicators UPS Status IndicatorsUPS Status Indicator Icon Color Description Initial Startup and Electrical Checks Startup Checklist for the Liebert GXT3Operation Put the Liebert GXT3 in Manual Bypass Manual Battery TestDisconnecting Input Power from the Liebert GXT3 Maintenance BypassRemove Screws IT Power System Connectors IT Power System ConfigurationDry Contact Any Mode ShutdownBattery Mode Shutdown Communication Interface PortLow Battery On BatteryLiebert IntelliSlot Communication Cards Repo switch connection diagram Remote Emergency Power OffLiebert MultiLink Maintenance Replacing the Internal Battery PackBattery Replacement Procedures Precautions Battery ChargingChecking UPS Functions Checking UPS StatusIndicator Diagnosis/Audible alarm UPS SymptomsTroubleshooting IndicatorsAudible alarm description Audible AlarmCondition Alarm Problem Cause Solution Troubleshooting tableIlluminated UPS specifications SpecificationsPower distribution specifications Operating temperature parametersExternal battery cabinet specifications Auto-Learning Battery Run Times Page Care Ne tIs t Twor k