Emerson GXT2-10000RT208 user manual Install the Main Cabinet, Installation and Configuration

Page 16

Installation and Configuration

6.0INSTALLATION AND CONFIGURATION

This section includes instructions on how to install, configure and perform initial electrical checks of your UPS installation.

DO NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 7.0 - Initial Startup and Electrical Checks.

Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Liebert representative.

! CAUTION

The UPS is heavy (see 14.0 - Specifications). Take proper precautions when lifting or moving it.

Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, cor- rosives and other conductive contaminants. Maintain a minimum clearance of 4" (100mm) in the front and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).

NOTE

UPS operation in sustained temperatures above 77°F (25°C) reduces battery life.

6.1Install the Main Cabinet

The Liebert GXT2-10000RT208 may be installed either as a tower unit or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instructions in either 6.1.1 - Tower UPS Installation or 6.1.2 - Installing the Adjustable Rack- Mount Kit—Sold Separately.

6.1.1Tower UPS Installation

When using the Liebert GXT2-10000RT208 in a tower configuration, use the included support base (shown below, left) to stabilize the UPS.

If any external battery cabinets are added, they will include spacers to accommodate the additional cabinets (shown below, right).

Figure 5 Support base and spacers

End Bases

Spacers

Attach Bezels to Top

When used as a tower, the Liebert GXT2-10000RT208 requires bezels attached to the top. To connect the bezels:

1.Position the UPS so that the battery compartments are on the right side.

2.Attach the top bezels by placing them on the mounting holes and sliding them toward the rear of the UPS.

10

Image 16
Contents Liebert GXT2-10000RT208 Page Table of Contents Controls and Indicators Modes of OperationMaintenance TroubleshootingSpecifications CommunicationsFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionDC to DC Converter BatteryStatic Bypass Main Frame and Electronics Internal Battery PackMajor Components PD-101 Power Distribution Option with Internal Connector PD-102 Power Distribution Option PD-103WHAT’S Included Install the Main Cabinet Installation and ConfigurationTower UPS Installation Attach Bezels to TopQuantity Installing the Adjustable Rack-Mount Kit-Sold SeparatelyReturn flanges Retaining Latches Front Innermembers members M4 nuts Rack Depth M4 nutsSupport Base With Spacers for External Battery Cabinets External Battery Cabinet InstallationUPS External Battery Cabinet Connect Input/Output Power Distribution Module Electrical ConnectionsInput & Output Terminal Block Connections Electrical requirements208 or Output to Load See Note 120 208 or Input to UPS See NoteAdd an Output Power Distribution Module-Optional Hardwire Terminal Block CoverScrew holes Output Distributionto attach to UPS Cover Plate Liebert GXT2 10000RT208Install the Internal Battery Packs Controls and Indicators horizontal overlayHardwire Input Connections Initial Startup and Electrical ChecksHardwire terminal connections Output Receptacle Distribution OptionsConfiguration Program Liebert GXT2-10000RT208 Configuration Program FeaturesWhat You Will Need Configuration Program-Installation Establishing Communication Link withConfiguration Program-Operation Read/Confirm UPS Configuration SettingsCancel Without Changing UPS Settings Changing UPS SettingsOn-Screen Reminders Programming Rejected When UPS is OffPartial Rejection UPS Tab Output VoltageOutput Voltage Selection Notes N Reverse Detection-120V UPS Models OnlyOptions Tab Frequency SelectionOptions Tab Used With Earlier Liebert GXT2 Models Battery Tab Low Battery Time WarningAuto Battery Test Time Battery Cabinets NumberAbout Tab ON/Alarm Silence/Battery Test Button Controls and IndicatorsOFF/Bypass Button Horizontal overlay for rack mountingBattery Level Indicators 5 Green Fault Indicator RedBypass Indicator Amber UPS on Indicator GreenNormal Mode Operation Battery Mode OperationBattery Recharge Operation Modes of OperationCommunications Interface Port Communications11.1.1 DB-9 Interface Port DB-9 pin assignmentPin 4 Remote Shutdown on Battery UPS Intelligent CommunicationsCommunications-Liebert SNMP/OCWEBCARD Snmp Adapter Wrap network cable around ferrite beadKey to Repo switch connections 1 VDC Sense Common Remote Emergency Power OffRepo Connection Battery Replacement MaintenanceInternal Battery Replacement Procedures BatteryUPS Power Module Replacement UPS back panel-control location Fault indicators TroubleshootingIndicator status Diagnosis/Audible alarm Alarm conditions Condition AlarmTroubleshooting guide Problem Cause Solution See 12.2 UPS Power Module Replacement Battery run times Battery/External 10000VA Run Time Cabinets Load% MinutesAuto-Learning Battery Run Times Specifications UPS specificationsBattery specifications Optional output distribution specifications-PD-101See Battery run times Model Number PD-101 DIMENSIONS, W x D x HOptional output distribution specifications-PD-102 Optional output distribution specifications-PD-103Model Number PD-102 DIMENSIONS, W x D x H Model Number PD-103 DIMENSIONS, W x D x HExternal battery cabinet specifications Product Warranty RegistrationModel Number Specifications Page Ne t ItiTi n That