6.3.2Input & Output Terminal Block Connections

Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share the same conduit.

Table 1 Electrical requirements

 

 

 

 

Recommended Wire

Maximum Wire

Terminal

Input Current

Recommended (Max.) External

(including ground wire)

Accepted by

Tightening

Rating

Overcurrent Protection

(75°C copper wire)

Terminal Block

Torque

48A

 

60A

 

 

6 AWG

4 AWG

22 in-lb

 

 

 

(2.48N-m)

 

 

 

 

 

 

 

 

 

L2

N

L1

L2

 

N

L1

 

 

 

OUTPUT

 

INPUT

60A Max. Branch

 

 

 

 

Overcurrent Protection

 

 

 

 

 

 

 

 

6 AWG - USE COPPER WIRE ONLY - 22 in-lb (2.48N-m)- Strip 8mm

 

 

L2

N

L1

L2

N

L1

0

 

 

 

120

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208 or 240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output to Load - See Note 1

 

120

 

 

 

 

 

 

120

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208 or 240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input to UPS - See Note 2

NOTE

1. The installer must provide circuit breaker protection according to local codes. The utility disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain service space around the UPS or use flexible conduit.

2.The installer must provide output distribution panels, circuit breaker protection or emergency disconnects according to local codes. Output circuits must not share a common conduit with any other wiring.

For best performance, distribute all L-N loads evenly between L1 and L2.

15

Image 21
Contents Liebert GXT2-10000RT208 Page Table of Contents Modes of Operation Controls and IndicatorsTroubleshooting MaintenanceSpecifications CommunicationsFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionBattery DC to DC ConverterStatic Bypass Internal Battery Pack Main Frame and ElectronicsMajor Components PD-102 Power Distribution Option PD-103 PD-101 Power Distribution Option with Internal ConnectorWHAT’S Included Installation and Configuration Install the Main CabinetTower UPS Installation Attach Bezels to TopInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityReturn flanges Retaining Latches Front Innermembers members Rack Depth M4 nuts M4 nutsExternal Battery Cabinet Installation Support Base With Spacers for External Battery CabinetsUPS External Battery Cabinet Distribution Module Electrical Connections Connect Input/Output PowerElectrical requirements Input & Output Terminal Block Connections208 or Output to Load See Note 120 208 or Input to UPS See NoteHardwire Terminal Block Cover Add an Output Power Distribution Module-OptionalScrew holes Output Distributionto attach to UPS Cover Plate Liebert GXT2 10000RT208Controls and Indicators horizontal overlay Install the Internal Battery PacksInitial Startup and Electrical Checks Hardwire Input ConnectionsOutput Receptacle Distribution Options Hardwire terminal connectionsLiebert GXT2-10000RT208 Configuration Program Features Configuration ProgramWhat You Will Need Establishing Communication Link with Configuration Program-InstallationRead/Confirm UPS Configuration Settings Configuration Program-OperationCancel Without Changing UPS Settings Changing UPS SettingsProgramming Rejected When UPS is Off On-Screen RemindersPartial Rejection Output Voltage UPS TabOutput Voltage Selection Notes N Reverse Detection-120V UPS Models OnlyFrequency Selection Options TabOptions Tab Used With Earlier Liebert GXT2 Models Low Battery Time Warning Battery TabAuto Battery Test Time Battery Cabinets NumberAbout Tab Controls and Indicators ON/Alarm Silence/Battery Test ButtonOFF/Bypass Button Horizontal overlay for rack mountingFault Indicator Red Battery Level Indicators 5 GreenBypass Indicator Amber UPS on Indicator GreenBattery Mode Operation Normal Mode OperationBattery Recharge Operation Modes of OperationCommunications Communications Interface Port11.1.1 DB-9 Interface Port DB-9 pin assignmentUPS Intelligent Communications Pin 4 Remote Shutdown on BatteryCommunications-Liebert SNMP/OCWEBCARD Snmp Adapter Wrap network cable around ferrite beadRemote Emergency Power Off Key to Repo switch connections 1 VDC Sense CommonRepo Connection Maintenance Battery ReplacementInternal Battery Replacement Procedures BatteryUPS Power Module Replacement UPS back panel-control location Troubleshooting Fault indicatorsIndicator status Diagnosis/Audible alarm Condition Alarm Alarm conditionsTroubleshooting guide Problem Cause Solution See 12.2 UPS Power Module Replacement Battery/External 10000VA Run Time Cabinets Load% Minutes Battery run timesAuto-Learning Battery Run Times UPS specifications SpecificationsOptional output distribution specifications-PD-101 Battery specificationsSee Battery run times Model Number PD-101 DIMENSIONS, W x D x HOptional output distribution specifications-PD-103 Optional output distribution specifications-PD-102Model Number PD-102 DIMENSIONS, W x D x H Model Number PD-103 DIMENSIONS, W x D x HProduct Warranty Registration External battery cabinet specificationsModel Number Specifications Page Iti Ne tTi n That