Emerson GXT2-10000RT208 user manual Battery run times

Page 48

Troubleshooting

Using the configuration program, the user may specify the number of GXT2-288VBATT external bat- tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.

Table 6 shows estimated run times at different loads.

Table 6 Battery run times

Battery/External

 

10000VA Run Time

Cabinets

Load%

in Minutes

 

10%

107

 

20%

52

 

30%

31

 

40%

22

Internal Battery

50%

16

60%

13

 

 

70%

10

 

80%

9

 

90%

7

 

100%

6

 

10%

251

 

20%

118

 

30%

74

Internal Battery

40%

52

50%

39

+ 1 External Battery

60%

32

Cabinet

 

70%

26

 

80%

22

 

90%

19

 

100%

17

 

10%

333

 

20%

216

 

30%

118

Internal Battery

40%

85

50%

66

+ 2 External Battery

60%

53

Cabinets

 

70%

44

 

80%

38

 

90%

32

 

100%

28

 

10%

494

 

20%

265

 

30%

191

Internal Battery

40%

119

50%

92

+ 3 External Battery

60%

75

Cabinets

 

70%

62

 

80%

54

 

90%

47

 

100%

41

 

10%

590

 

20%

295

 

30%

236

Internal Battery

40%

178

50%

119

+ 4 External Battery

60%

98

Cabinets

 

70%

82

 

80%

71

 

90%

61

 

100%

54

Battery/External

 

10000VA Run Time

Cabinets

Load%

in Minutes

 

10%

548

 

20%

284

 

30%

217

Internal Battery

40%

151

50%

107

+ 1 LRT Battery

60%

86

Pack

 

70%

66

 

80%

55

 

90%

47

 

100%

40

 

10%

1030

 

20%

538

 

30%

332

Internal Battery

40%

269

50%

231

+ 2 LRT Battery

60%

195

Pack

 

70%

158

 

80%

125

 

90%

109

 

100%

96

 

10%

1473

 

20%

821

 

30%

520

Internal Battery

40%

382

50%

289

+ 3 LRT Battery

60%

264

Pack

 

70%

238

 

80%

215

 

90%

189

 

100%

165

 

10%

1973

 

20%

1053

 

30%

672

 

40%

515

Internal Battery

50%

406

+ 4 LRT

60%

304

 

70%

280

 

80%

263

 

90%

243

 

100%

224

42

Image 48 Contents
Liebert GXT2-10000RT208 Page Table of Contents Controls and Indicators Modes of OperationMaintenance TroubleshootingSpecifications CommunicationsFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionBattery DC to DC ConverterStatic Bypass Internal Battery Pack Main Frame and ElectronicsMajor Components PD-101 Power Distribution Option with Internal Connector PD-102 Power Distribution Option PD-103WHAT’S Included Install the Main Cabinet Installation and ConfigurationTower UPS Installation Attach Bezels to TopInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityReturn flanges Retaining Latches Front Innermembers members M4 nuts Rack Depth M4 nutsExternal Battery Cabinet Installation Support Base With Spacers for External Battery CabinetsUPS External Battery Cabinet Connect Input/Output Power Distribution Module Electrical ConnectionsInput & Output Terminal Block Connections Electrical requirements208 or Output to Load See Note 120 208 or Input to UPS See NoteAdd an Output Power Distribution Module-Optional Hardwire Terminal Block CoverScrew holes Output Distributionto attach to UPS Cover Plate Liebert GXT2 10000RT208Install the Internal Battery Packs Controls and Indicators horizontal overlayHardwire Input Connections Initial Startup and Electrical ChecksHardwire terminal connections Output Receptacle Distribution OptionsLiebert GXT2-10000RT208 Configuration Program Features Configuration ProgramWhat You Will Need Configuration Program-Installation Establishing Communication Link withConfiguration Program-Operation Read/Confirm UPS Configuration SettingsCancel Without Changing UPS Settings Changing UPS SettingsProgramming Rejected When UPS is Off On-Screen RemindersPartial Rejection UPS Tab Output VoltageOutput Voltage Selection Notes N Reverse Detection-120V UPS Models OnlyOptions Tab Frequency SelectionOptions Tab Used With Earlier Liebert GXT2 Models Battery Tab Low Battery Time WarningAuto Battery Test Time Battery Cabinets NumberAbout Tab ON/Alarm Silence/Battery Test Button Controls and IndicatorsOFF/Bypass Button Horizontal overlay for rack mountingBattery Level Indicators 5 Green Fault Indicator RedBypass Indicator Amber UPS on Indicator GreenNormal Mode Operation Battery Mode OperationBattery Recharge Operation Modes of OperationCommunications Interface Port Communications11.1.1 DB-9 Interface Port DB-9 pin assignmentPin 4 Remote Shutdown on Battery UPS Intelligent CommunicationsCommunications-Liebert SNMP/OCWEBCARD Snmp Adapter Wrap network cable around ferrite beadRemote Emergency Power Off Key to Repo switch connections 1 VDC Sense CommonRepo Connection Battery Replacement MaintenanceInternal Battery Replacement Procedures BatteryUPS Power Module Replacement UPS back panel-control location Troubleshooting Fault indicators Indicator status Diagnosis/Audible alarm Alarm conditions Condition AlarmTroubleshooting guide Problem Cause Solution See 12.2 UPS Power Module Replacement Battery run times Battery/External 10000VA Run Time Cabinets Load% MinutesAuto-Learning Battery Run Times Specifications UPS specificationsBattery specifications Optional output distribution specifications-PD-101See Battery run times Model Number PD-101 DIMENSIONS, W x D x HOptional output distribution specifications-PD-102 Optional output distribution specifications-PD-103Model Number PD-102 DIMENSIONS, W x D x H Model Number PD-103 DIMENSIONS, W x D x HProduct Warranty Registration External battery cabinet specificationsModel Number Specifications Page Ne t ItiTi n That