Emerson GXT2-10000RT208 user manual Specifications, UPS specifications

Page 50

Specifications

14.0SPECIFICATIONS

Table 7

UPS specifications

 

 

 

 

 

 

Model Number

 

Liebert GXT2-10000RT208

 

 

 

 

 

 

 

8000W/8660VA at 127/220 (120 or 240 degrees only)

 

 

 

8000W/8660VA at 120/208 (120 or 240 degrees)

 

Model Rating

 

8000W/10000VA at 120/240 (180 degrees)

 

 

8000W/10000VA at 115/230 (180 degrees only)

 

 

 

 

 

 

7200W/9000VA at 110/220 (180 degrees only)

 

 

 

6400W/8000VA at 100/200 (180 degrees only)

DIMENSIONS, RACK MOUNT, W x D x H

 

 

Unit, in. (mm)

 

16.93 x 25.98 x 10.5 (430 x 660 x 267); 6U

 

Shipping, in. (mm)

 

22.44 x 33.86 x 15.75 (570 x 860 x 400)

WEIGHT lb (kg)

 

 

Unit

 

109 (49.3)

 

Shipping

 

118 (53.6)

INPUT AC PARAMETERS

 

 

Nominal Operating Frequency

 

50 or 60 Hz (Factory Default = 60)

 

Factory Default VAC

 

120/208 VAC at 120 degrees

L1-L2 Factory Default Input Phase

 

120 degrees

 

Angle

 

 

 

 

 

Allowable Input Phase Angle

 

120, 180, 240 degrees, Auto-sensing on application of AC

 

 

(Restrictions for L-N voltages other than 120 VAC)

 

 

 

Factory Default L1-N, L2-N VAC

 

120 VAC nominal

User Configurable L1-N, L2-N VAC

 

100/110/115/120/127 VAC (May be modified using configuration program)

L1-N, L2-N, Operating Voltage Range Without Battery Operation (Except 100 VAC L-N Operation)

 

100% - 91% loading

 

100 VAC - 140 VAC

 

90% - 71% loading

 

90 VAC - 140 VAC

 

70% - 51% loading

 

80 VAC - 140 VAC

 

50% - 31% loading

 

70 VAC - 140 VAC

 

30% - 0% loading

 

60 VAC - 140 VAC

L1-N, L2-N, Operating Voltage Range Without Battery Operation (100 VAC L-N Operation)

 

100% - 91% loading

 

90 VAC - 140 VAC

 

90% - 71% loading

 

80 VAC - 140 VAC

 

70% - 51% loading

 

70 VAC - 140 VAC

 

50% - 0% loading

 

60 VAC - 140 VAC

L1-N, L2-N Max. Allowable VAC

 

150 VAC

 

Input Frequency w/o Battery

 

40 - 70 Hz

 

Operation

 

 

 

Input Power Connection

 

Hardwire Terminal Block 3W + G (L-L-N-G)

OUTPUT AC PARAMETERS

 

 

Factory Default VAC

 

120/208 VAC @ 120 degrees

 

L1-L2 Factory Default

 

120 degrees

 

Output Phase Angle

 

 

 

 

 

Allowable Output Phase Angle

 

120, 180, 240 degrees Auto-sensing on initial application of input AC

Factory Default L1-N, L2-N VAC

 

120 VAC nominal

User Configurable L1-N, L2-N VAC

 

100/110/115/120/127 VAC, ±2%

 

Output Connections

 

Hardwire Terminal Block 3W + G (L-L-N-G);

 

 

also see 7.2 - Output Receptacle Distribution Options

 

 

 

 

Frequency

 

50 Hz or 60 Hz, Nominal

 

Waveform

 

Sinewave

 

Main Mode Overload

 

130% for 60 seconds; 200% for 5 seconds with transfer to bypass.

44

Image 50
Contents Liebert GXT2-10000RT208 Page Table of Contents Controls and Indicators Modes of OperationSpecifications MaintenanceTroubleshooting CommunicationsFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionStatic Bypass BatteryDC to DC Converter Major Components Internal Battery PackMain Frame and Electronics PD-101 Power Distribution Option with Internal Connector PD-102 Power Distribution Option PD-103WHAT’S Included Tower UPS Installation Install the Main CabinetInstallation and Configuration Attach Bezels to TopReturn flanges Retaining Latches Front Innermembers members Installing the Adjustable Rack-Mount Kit-Sold SeparatelyQuantity M4 nuts Rack Depth M4 nutsUPS External Battery Cabinet External Battery Cabinet InstallationSupport Base With Spacers for External Battery Cabinets Connect Input/Output Power Distribution Module Electrical Connections208 or Output to Load See Note 120 Input & Output Terminal Block ConnectionsElectrical requirements 208 or Input to UPS See NoteScrew holes Output Distributionto attach to UPS Cover Plate Add an Output Power Distribution Module-OptionalHardwire Terminal Block Cover Liebert GXT2 10000RT208Install the Internal Battery Packs Controls and Indicators horizontal overlayHardwire Input Connections Initial Startup and Electrical ChecksHardwire terminal connections Output Receptacle Distribution OptionsWhat You Will Need Liebert GXT2-10000RT208 Configuration Program FeaturesConfiguration Program Configuration Program-Installation Establishing Communication Link withCancel Without Changing UPS Settings Configuration Program-OperationRead/Confirm UPS Configuration Settings Changing UPS SettingsPartial Rejection Programming Rejected When UPS is OffOn-Screen Reminders Output Voltage Selection Notes UPS TabOutput Voltage N Reverse Detection-120V UPS Models OnlyOptions Tab Frequency SelectionOptions Tab Used With Earlier Liebert GXT2 Models Auto Battery Test Time Battery TabLow Battery Time Warning Battery Cabinets NumberAbout Tab OFF/Bypass Button ON/Alarm Silence/Battery Test ButtonControls and Indicators Horizontal overlay for rack mountingBypass Indicator Amber Battery Level Indicators 5 GreenFault Indicator Red UPS on Indicator GreenBattery Recharge Operation Normal Mode OperationBattery Mode Operation Modes of Operation11.1.1 DB-9 Interface Port Communications Interface PortCommunications DB-9 pin assignmentCommunications-Liebert SNMP/OCWEBCARD Snmp Adapter Pin 4 Remote Shutdown on BatteryUPS Intelligent Communications Wrap network cable around ferrite beadRepo Connection Remote Emergency Power OffKey to Repo switch connections 1 VDC Sense Common Internal Battery Replacement Procedures Battery ReplacementMaintenance BatteryUPS Power Module Replacement UPS back panel-control location Indicator status Diagnosis/Audible alarm TroubleshootingFault indicators Alarm conditions Condition AlarmTroubleshooting guide Problem Cause Solution See 12.2 UPS Power Module Replacement Battery run times Battery/External 10000VA Run Time Cabinets Load% MinutesAuto-Learning Battery Run Times Specifications UPS specificationsSee Battery run times Battery specificationsOptional output distribution specifications-PD-101 Model Number PD-101 DIMENSIONS, W x D x HModel Number PD-102 DIMENSIONS, W x D x H Optional output distribution specifications-PD-102Optional output distribution specifications-PD-103 Model Number PD-103 DIMENSIONS, W x D x HModel Number Product Warranty RegistrationExternal battery cabinet specifications Specifications Page Ti n Ne tIti That