Emerson GXT2-10000RT208 user manual UPS Power Module Replacement

Page 42

Maintenance

12.2UPS Power Module Replacement

! CAUTION

The UPS must be switched to manual bypass before personnel begin to replace the power module.

NOTE

During the procedure, the connected load will not be protected from power disturbances, such as spikes, sags and failure.

To remove the UPS power module without shutting off power to the connected load:

1.Place the UPS on internal bypass. This may be done by any of the three following methods:

a.Press the Off button on the front panel one time.

b.Slide the bracket away from the manual bypass switch on the rear of the UPS—this requires loosening the captive screw and sliding the bracket away from the manual bypass switch.

c.Remove the front grille covering the power module.

2.Move the manual bypass breaker on the rear of the UPS to the bypass position—this requires loosening the captive screw and sliding the bracket away from the manual bypass switch (see Figure 10).

3.Open the input circuit breaker on the rear of the UPS (see Figure 10).

4.Open the output circuit breaker on the rear of the UPS (see Figure 10).

5.Remove the top two front plastic bezels by pulling them forward.

6.Remove the power module cover grille and the battery cover grille with the screws securing them to the frame.

7.Disconnect the slotted battery connectors from the internal battery packs.

8.If additional external batteries are used, disconnect the two external battery connectors.

9.Slide the power module out the front, supporting its weight as it is withdrawn.

10.Insert the replacement UPS power module.

11.Reconnect the slotted internal battery connectors.

12.Reconnect the external battery cables, if used.

13.Reattach both front cover grilles.

14.Reattach the front plastic bezels.

15.Close the input circuit breaker on the rear of the UPS (see Figure 10).

16.Close the output circuit breaker on the rear of the UPS (see Figure 10).

17.Move the bypass breaker on the rear of the UPS back to the INVERTER position (see Figure 10).

18.Slide the bracket back next to the manual bypass breaker and tighten its thumbscrew.

19.Press the On button on the front panel one time to return the UPS to Normal Mode operation.

36

Image 42
Contents Liebert GXT2-10000RT208 Page Table of Contents Controls and Indicators Modes of OperationSpecifications MaintenanceTroubleshooting CommunicationsFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionBattery DC to DC ConverterStatic Bypass Internal Battery Pack Main Frame and ElectronicsMajor Components PD-101 Power Distribution Option with Internal Connector PD-102 Power Distribution Option PD-103WHAT’S Included Tower UPS Installation Install the Main CabinetInstallation and Configuration Attach Bezels to TopInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityReturn flanges Retaining Latches Front Innermembers members M4 nuts Rack Depth M4 nutsExternal Battery Cabinet Installation Support Base With Spacers for External Battery CabinetsUPS External Battery Cabinet Connect Input/Output Power Distribution Module Electrical Connections208 or Output to Load See Note 120 Input & Output Terminal Block ConnectionsElectrical requirements 208 or Input to UPS See NoteScrew holes Output Distributionto attach to UPS Cover Plate Add an Output Power Distribution Module-OptionalHardwire Terminal Block Cover Liebert GXT2 10000RT208Install the Internal Battery Packs Controls and Indicators horizontal overlayHardwire Input Connections Initial Startup and Electrical ChecksHardwire terminal connections Output Receptacle Distribution OptionsLiebert GXT2-10000RT208 Configuration Program Features Configuration ProgramWhat You Will Need Configuration Program-Installation Establishing Communication Link withCancel Without Changing UPS Settings Configuration Program-OperationRead/Confirm UPS Configuration Settings Changing UPS SettingsProgramming Rejected When UPS is Off On-Screen RemindersPartial Rejection Output Voltage Selection Notes UPS TabOutput Voltage N Reverse Detection-120V UPS Models OnlyOptions Tab Frequency SelectionOptions Tab Used With Earlier Liebert GXT2 Models Auto Battery Test Time Battery TabLow Battery Time Warning Battery Cabinets NumberAbout Tab OFF/Bypass Button ON/Alarm Silence/Battery Test ButtonControls and Indicators Horizontal overlay for rack mountingBypass Indicator Amber Battery Level Indicators 5 GreenFault Indicator Red UPS on Indicator GreenBattery Recharge Operation Normal Mode OperationBattery Mode Operation Modes of Operation11.1.1 DB-9 Interface Port Communications Interface PortCommunications DB-9 pin assignmentCommunications-Liebert SNMP/OCWEBCARD Snmp Adapter Pin 4 Remote Shutdown on BatteryUPS Intelligent Communications Wrap network cable around ferrite beadRemote Emergency Power Off Key to Repo switch connections 1 VDC Sense CommonRepo Connection Internal Battery Replacement Procedures Battery ReplacementMaintenance BatteryUPS Power Module Replacement UPS back panel-control location Troubleshooting Fault indicatorsIndicator status Diagnosis/Audible alarm Alarm conditions Condition AlarmTroubleshooting guide Problem Cause Solution See 12.2 UPS Power Module Replacement Battery run times Battery/External 10000VA Run Time Cabinets Load% MinutesAuto-Learning Battery Run Times Specifications UPS specificationsSee Battery run times Battery specificationsOptional output distribution specifications-PD-101 Model Number PD-101 DIMENSIONS, W x D x HModel Number PD-102 DIMENSIONS, W x D x H Optional output distribution specifications-PD-102Optional output distribution specifications-PD-103 Model Number PD-103 DIMENSIONS, W x D x HProduct Warranty Registration External battery cabinet specificationsModel Number Specifications Page Ti n Ne tIti That