Emerson GXT2-10000RT208 user manual Install the Internal Battery Packs

Page 23

Installation and Configuration

6.4Install the Internal Battery Packs

To facilitate shipping and installation, the Liebert GXT2-10000RT208 ships without the internal bat- tery packs installed. Once the UPS is installed in place, the internal battery packs must be installed.

L

ie

b

e

r t

 

 

 

 

!

Controls and Indicators (horizontal overlay)

Mjfcfsu

!

Battery Compartment

Battery

 

Battery

 

Bracket

Battery

Front

Bezel

Connector

 

Battery

Cover

Front of Battery

1.Unpack the two internal battery packs from their shipping container.

2.Lift one battery pack from its packaging, holding it in the center of the pack.

3.Align the battery pack so that the cable is at the top right closest to the power module in the frame.

4.Slip the back of battery pack into the battery compartment and slide it in until the battery reaches the back of the UPS.

5.Install the battery bracket on the front of the battery pack with two screws.

6.Connect the two slotted connectors and tuck the wires in around the battery pack handles.

7.Repeat for the second battery pack.

8.Install the battery cover grille, tightening the three screws.

9.For tower installation, place the vertical overlay over the controls and indicators (see Figure 8).

10.Install the two front bezels.

17

Image 23 Contents
Liebert GXT2-10000RT208 Page Table of Contents Modes of Operation Controls and IndicatorsCommunications MaintenanceTroubleshooting SpecificationsFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description System Description Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterStatic Bypass BatteryDC to DC Converter Major Components Internal Battery PackMain Frame and Electronics PD-102 Power Distribution Option PD-103 PD-101 Power Distribution Option with Internal ConnectorWHAT’S Included Attach Bezels to Top Install the Main CabinetInstallation and Configuration Tower UPS InstallationReturn flanges Retaining Latches Front Innermembers members Installing the Adjustable Rack-Mount Kit-Sold SeparatelyQuantity Rack Depth M4 nuts M4 nuts UPS External Battery Cabinet External Battery Cabinet Installation Support Base With Spacers for External Battery Cabinets Distribution Module Electrical Connections Connect Input/Output Power208 or Input to UPS See Note Input & Output Terminal Block ConnectionsElectrical requirements 208 or Output to Load See Note 120Liebert GXT2 10000RT208 Add an Output Power Distribution Module-OptionalHardwire Terminal Block Cover Screw holes Output Distributionto attach to UPS Cover PlateControls and Indicators horizontal overlay Install the Internal Battery PacksInitial Startup and Electrical Checks Hardwire Input ConnectionsOutput Receptacle Distribution Options Hardwire terminal connectionsWhat You Will Need Liebert GXT2-10000RT208 Configuration Program FeaturesConfiguration Program Establishing Communication Link with Configuration Program-InstallationChanging UPS Settings Configuration Program-OperationRead/Confirm UPS Configuration Settings Cancel Without Changing UPS SettingsPartial Rejection Programming Rejected When UPS is OffOn-Screen Reminders N Reverse Detection-120V UPS Models Only UPS TabOutput Voltage Output Voltage Selection NotesFrequency Selection Options TabOptions Tab Used With Earlier Liebert GXT2 Models Battery Cabinets Number Battery TabLow Battery Time Warning Auto Battery Test TimeAbout Tab Horizontal overlay for rack mounting ON/Alarm Silence/Battery Test ButtonControls and Indicators OFF/Bypass ButtonUPS on Indicator Green Battery Level Indicators 5 GreenFault Indicator Red Bypass Indicator AmberModes of Operation Normal Mode OperationBattery Mode Operation Battery Recharge OperationDB-9 pin assignment Communications Interface PortCommunications 11.1.1 DB-9 Interface PortWrap network cable around ferrite bead Pin 4 Remote Shutdown on BatteryUPS Intelligent Communications Communications-Liebert SNMP/OCWEBCARD Snmp AdapterRepo Connection Remote Emergency Power OffKey to Repo switch connections 1 VDC Sense Common Battery Battery ReplacementMaintenance Internal Battery Replacement ProceduresUPS Power Module Replacement UPS back panel-control location Indicator status Diagnosis/Audible alarm TroubleshootingFault indicators Condition Alarm Alarm conditionsTroubleshooting guide Problem Cause Solution See 12.2 UPS Power Module Replacement Battery/External 10000VA Run Time Cabinets Load% Minutes Battery run timesAuto-Learning Battery Run Times UPS specifications SpecificationsModel Number PD-101 DIMENSIONS, W x D x H Battery specificationsOptional output distribution specifications-PD-101 See Battery run timesModel Number PD-103 DIMENSIONS, W x D x H Optional output distribution specifications-PD-102Optional output distribution specifications-PD-103 Model Number PD-102 DIMENSIONS, W x D x HModel Number Product Warranty RegistrationExternal battery cabinet specifications Specifications Page That Ne tIti Ti n