Emerson GXT2-10000RT208 External Battery Cabinet Installation, UPS External Battery Cabinet

Page 19

Installation and Configuration

6.2External Battery Cabinet Installation

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed on one side of the UPS or stacked beneath the UPS.

The external battery cabinet frame and battery kits are shipped separately. This 4U cabinet arrives without internal batteries to lighten the cabinet for easier installation. Once the cabinet has been placed in its final floor or rack position, the internal batteries may be installed.

! CAUTION

The external battery cabinet(s) are heavy (see 14.0 - Specifications). External battery cabinets can be used in rack-mount or tower configuration. Take proper precautions when lifting them.

! CAUTION

Verify that the battery cabinet circuit breaker is in the OFF position. Do no energize the battery cabinet at this time. When installation is complete, you will be instructed to turn on the circuit breaker.

When the external battery cabinet is received, it should be inspected for freight damage. Report dam- age to the carrier and your local dealer or Liebert representative.

To install an external battery cabinet:

1.For slide rail installations, first remove the top/side fin by sliding it forward and lifting it up. Optional rack-mount handles are shipped with the external battery cabinet and may be installed now. (Securing hardware and slide rails are sold separately. Please contact your local dealer or Liebert representative for these additional options and any assistance needed.)

2.Fasten the slides into position with the screws according to the instructions included with the slide rails.

3.Use the enclosed support bases for the tower option to prevent the assembly from tipping over. One additional set of support base extensions ships with each external battery cabinet.

4.Install the two battery packs and secure with the two brackets supplied.

5.Connect the two slotted battery cables.

6.Attach the battery cover plate and the two front bezels.

7.Connect the supplied external battery cabinet cables to either set of connectors on the rear of the external battery cabinet, then to the rear of the UPS.

8.The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to Table 6 - Battery run times in this manual.

9.Do NOT turn on the battery cabinet circuit breaker at this time. Please complete the remainder of the installation first.

NOTE

UPS automatically detects the number of standard batteries that are connected. The configuration program may be used to set up the UPS for operation with non- standard external batteries. Instructions for using the configuration program follow in 8.0 - Configuration

Program.

Support Base With Spacers for External Battery Cabinets

+

BATTERY CONNECTION

+

CIRCUIT BREAKER

 

+

 

+

BATTERY CONNECTOR

UPS and

External Battery Cabinet

13

Image 19
Contents Liebert GXT2-10000RT208 Page Table of Contents Modes of Operation Controls and IndicatorsCommunications MaintenanceTroubleshooting SpecificationsFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description System Description Rectifier/Power Factor Correction PFC CircuitBattery Charger InverterDC to DC Converter BatteryStatic Bypass Main Frame and Electronics Internal Battery PackMajor Components PD-102 Power Distribution Option PD-103 PD-101 Power Distribution Option with Internal ConnectorWHAT’S Included Attach Bezels to Top Install the Main CabinetInstallation and Configuration Tower UPS InstallationQuantity Installing the Adjustable Rack-Mount Kit-Sold SeparatelyReturn flanges Retaining Latches Front Innermembers members Rack Depth M4 nuts M4 nutsSupport Base With Spacers for External Battery Cabinets External Battery Cabinet InstallationUPS External Battery Cabinet Distribution Module Electrical Connections Connect Input/Output Power208 or Input to UPS See Note Input & Output Terminal Block ConnectionsElectrical requirements 208 or Output to Load See Note 120Liebert GXT2 10000RT208 Add an Output Power Distribution Module-OptionalHardwire Terminal Block Cover Screw holes Output Distributionto attach to UPS Cover PlateControls and Indicators horizontal overlay Install the Internal Battery PacksInitial Startup and Electrical Checks Hardwire Input ConnectionsOutput Receptacle Distribution Options Hardwire terminal connectionsConfiguration Program Liebert GXT2-10000RT208 Configuration Program FeaturesWhat You Will Need Establishing Communication Link with Configuration Program-InstallationChanging UPS Settings Configuration Program-OperationRead/Confirm UPS Configuration Settings Cancel Without Changing UPS SettingsOn-Screen Reminders Programming Rejected When UPS is OffPartial Rejection N Reverse Detection-120V UPS Models Only UPS TabOutput Voltage Output Voltage Selection NotesFrequency Selection Options TabOptions Tab Used With Earlier Liebert GXT2 Models Battery Cabinets Number Battery TabLow Battery Time Warning Auto Battery Test TimeAbout Tab Horizontal overlay for rack mounting ON/Alarm Silence/Battery Test ButtonControls and Indicators OFF/Bypass ButtonUPS on Indicator Green Battery Level Indicators 5 GreenFault Indicator Red Bypass Indicator AmberModes of Operation Normal Mode OperationBattery Mode Operation Battery Recharge OperationDB-9 pin assignment Communications Interface PortCommunications 11.1.1 DB-9 Interface PortWrap network cable around ferrite bead Pin 4 Remote Shutdown on BatteryUPS Intelligent Communications Communications-Liebert SNMP/OCWEBCARD Snmp AdapterKey to Repo switch connections 1 VDC Sense Common Remote Emergency Power OffRepo Connection Battery Battery ReplacementMaintenance Internal Battery Replacement ProceduresUPS Power Module Replacement UPS back panel-control location Fault indicators TroubleshootingIndicator status Diagnosis/Audible alarm Condition Alarm Alarm conditionsTroubleshooting guide Problem Cause Solution See 12.2 UPS Power Module Replacement Battery/External 10000VA Run Time Cabinets Load% Minutes Battery run timesAuto-Learning Battery Run Times UPS specifications SpecificationsModel Number PD-101 DIMENSIONS, W x D x H Battery specificationsOptional output distribution specifications-PD-101 See Battery run timesModel Number PD-103 DIMENSIONS, W x D x H Optional output distribution specifications-PD-102Optional output distribution specifications-PD-103 Model Number PD-102 DIMENSIONS, W x D x HExternal battery cabinet specifications Product Warranty RegistrationModel Number Specifications Page That Ne tIti Ti n