Emerson GXT2-10000RT208 Normal Mode Operation, Battery Mode Operation, Battery Recharge Operation

Page 37
Normal Mode Operation Batteries at 100% charge
L1 Load at 10%, L2 Load at 90%
Battery Mode Operation Batteries at 30% charge
L1 Load at 60%, L2 Load at 60%

Modes of Operation

10.0MODES OF OPERATION

10.1Normal Mode Operation

During normal operation, utility power provides energy to the UPS. The filters, power factor correction circuit and the inverter process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state. The four green Load Level indica- tors display an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) indicator will illuminate and the UPS will sound an audible alarm. The display template indicates the percent- age of load (see example at right) on the UPS output.

10.2Battery Mode Operation

Battery mode occurs in event of an extreme input voltage condition or complete utility failure. The battery system supplies power through the DC to DC converter to the inverter to generate power for the connected load. During battery mode an alarm sounds every 10 seconds. This will change to two beeps every 5 seconds when the battery runs low (approximately 2 minutes remaining, but this is user configurable). The AC Input indicator will extinguish and the Battery indicator will illuminate to warn that a utility problem has occurred. Each Battery Level indicator repre- sents a 20% capacity level. As capacity decreases, fewer indicators remain illuminated. Refer to 13.0 - Trouble- shooting. For approximate battery run times, refer to Table 6 - Battery run times. These times are approximate

based on resistive load and an ambient temperature of 77°F (25°C). To increase this time, turn off non-essential pieces of equipment (such as idle computers and monitors) or add the optional external battery cabinet.

! CAUTION

Turning OFF the UPS while in battery mode will result in loss of output power.

10.3Battery Recharge Operation

Once utility power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging.

31

Image 37
Contents Liebert GXT2-10000RT208 Page Table of Contents Modes of Operation Controls and IndicatorsTroubleshooting MaintenanceSpecifications CommunicationsFigures Important Safety Instructions Page Glossary of Symbols Introduction and System Description Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionDC to DC Converter BatteryStatic Bypass Main Frame and Electronics Internal Battery PackMajor Components PD-102 Power Distribution Option PD-103 PD-101 Power Distribution Option with Internal ConnectorWHAT’S Included Installation and Configuration Install the Main CabinetTower UPS Installation Attach Bezels to TopQuantity Installing the Adjustable Rack-Mount Kit-Sold SeparatelyReturn flanges Retaining Latches Front Innermembers members Rack Depth M4 nuts M4 nutsSupport Base With Spacers for External Battery Cabinets External Battery Cabinet InstallationUPS External Battery Cabinet Distribution Module Electrical Connections Connect Input/Output PowerElectrical requirements Input & Output Terminal Block Connections208 or Output to Load See Note 120 208 or Input to UPS See NoteHardwire Terminal Block Cover Add an Output Power Distribution Module-OptionalScrew holes Output Distributionto attach to UPS Cover Plate Liebert GXT2 10000RT208Controls and Indicators horizontal overlay Install the Internal Battery PacksInitial Startup and Electrical Checks Hardwire Input ConnectionsOutput Receptacle Distribution Options Hardwire terminal connectionsConfiguration Program Liebert GXT2-10000RT208 Configuration Program FeaturesWhat You Will Need Establishing Communication Link with Configuration Program-InstallationRead/Confirm UPS Configuration Settings Configuration Program-OperationCancel Without Changing UPS Settings Changing UPS SettingsOn-Screen Reminders Programming Rejected When UPS is OffPartial Rejection Output Voltage UPS TabOutput Voltage Selection Notes N Reverse Detection-120V UPS Models OnlyFrequency Selection Options TabOptions Tab Used With Earlier Liebert GXT2 Models Low Battery Time Warning Battery TabAuto Battery Test Time Battery Cabinets NumberAbout Tab Controls and Indicators ON/Alarm Silence/Battery Test ButtonOFF/Bypass Button Horizontal overlay for rack mountingFault Indicator Red Battery Level Indicators 5 GreenBypass Indicator Amber UPS on Indicator GreenBattery Mode Operation Normal Mode OperationBattery Recharge Operation Modes of OperationCommunications Communications Interface Port11.1.1 DB-9 Interface Port DB-9 pin assignmentUPS Intelligent Communications Pin 4 Remote Shutdown on BatteryCommunications-Liebert SNMP/OCWEBCARD Snmp Adapter Wrap network cable around ferrite beadKey to Repo switch connections 1 VDC Sense Common Remote Emergency Power OffRepo Connection Maintenance Battery ReplacementInternal Battery Replacement Procedures BatteryUPS Power Module Replacement UPS back panel-control location Fault indicators TroubleshootingIndicator status Diagnosis/Audible alarm Condition Alarm Alarm conditionsTroubleshooting guide Problem Cause Solution See 12.2 UPS Power Module Replacement Battery/External 10000VA Run Time Cabinets Load% Minutes Battery run timesAuto-Learning Battery Run Times UPS specifications SpecificationsOptional output distribution specifications-PD-101 Battery specificationsSee Battery run times Model Number PD-101 DIMENSIONS, W x D x HOptional output distribution specifications-PD-103 Optional output distribution specifications-PD-102Model Number PD-102 DIMENSIONS, W x D x H Model Number PD-103 DIMENSIONS, W x D x HExternal battery cabinet specifications Product Warranty RegistrationModel Number Specifications Page Iti Ne tTi n That