Installation and Configuration
6.3Connect Input/Output Power
The UPS has hardwire terminal blocks for input and output electrical connections. Optional output distribution modules permit connecting additional loads to the UPS. These optional
! WARNING
The UPS must be completely powered down before beginning to make these electrical connections.
6.3.1Distribution Module Electrical Connections
Electrical connections are made through a removable conduit box that attaches to the rear of the UPS.
The installer must provide a 60A branch circuit breaker. The input circuit breaker and the output cir- cuit breaker on the rear
The manual bypass switch passes utility power directly to the bypass switch from the input terminal block. The input circuit breaker does not disconnect power from the manual bypass switch.
Figure 6 60A branch circuit breaker connection diagram
Utility
60A External
Branch
Circuit Breaker
UPS
60A 60A Input Output Circuit Circuit Breaker Breaker
60A Maintenance
Bypass Breaker
Input Output Indicator Indicator
Input
Output
Terminal
Block
Optional
Output
Distribution
Plate
! CAUTION
A disconnect switch shall be provided by others for ac input circuit. To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent protection for 60 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.
! CAUTION
A disconnect switch shall be provided by others for ac output circuit. To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent protection for 60 amperes rating in accordance with the National Electric Code, ANSI/NFPA 70.