System Data
Table 15 Liebert Challenger ITR chilled water data, 50 Hz
Capacity Data kW (BTU/H) @ 7.2°C (45°F ) EWT, 5.6°C (10°F) Water Rise; Net Capacity Data
Indoor Unit |
|
| BR 101C | |
BR = Horizontal Flow |
| |||
37.8ºC DB, 21.1ºC WB (100ºF DB, | 70ºF WB) 20% RH, 6.7°C (12°F) | |||
Water Rise |
|
|
|
|
Total | kW (BTU/H) | 34.0 |
| 116,000 |
Sensible | kW (BTU/H) | 31.9 |
| 109,000 |
Flow Rate | l/s (GPM) | 1.3 |
| 19.9 |
Pressure Drop | kPa (ft) | 66.5 |
| 22.3 |
35ºC DB, 20.2ºC WB (95ºF DB, 68.3ºF WB) 24% RH, | ||||
6.1°C (11°F) Water Rise |
|
|
| |
Total | kW (BTU/H) | 31.1 |
| 106,000 |
Sensible | kW (BTU/H) | 29.0 |
| 99,100 |
Flow Rate | l/s (GPM) | 1.3 |
| 19.9 |
Pressure Drop | kPa (ft) | 66.5 |
| 22.3 |
32.2ºC DB, 19.2ºC WB (90ºF DB, 66.5ºF WB) 28% RH | ||||
Total | kW (BTU/H) | 28.2 |
| 96,100 |
Sensible | kW (BTU/H) | 26.0 |
| 88,900 |
Flow Rate | l/s (GPM) | 1.3 |
| 20.0 |
Pressure Drop | kPa (ft) | 66.8 |
| 22.4 |
29.4ºC DB, 18ºC WB (85ºF DB, 64.4ºF WB) 32% RH | ||||
Total | kW (BTU/H) | 24.7 |
| 84,200 |
Sensible | kW (BTU/H) | 23.0 |
| 78,400 |
Flow Rate | l/s (GPM) | 1.1 |
| 17.6 |
Pressure Drop | kPa (ft) | 52.7 |
| 17.7 |
26.7ºC DB, 17.1ºC WB (80ºF DB, 62.7ºF WB) 38% RH | ||||
Total | kW (BTU/H) | 21.5 |
| 73,500 |
Sensible | kW (BTU/H) | 19.6 |
| 66,900 |
|
|
|
|
|
Flow Rate | l/s (GPM) | 1.0 |
| 15.8 |
|
|
|
|
|
Pressure Drop | kPa (ft) | 42.9 |
| 14.4 |
26.7ºC DB, 19.2ºC WB (80ºF DB, 66.5ºF WB) 50% RH | ||||
Total | kW (BTU/H) | 27.5 |
| 94,000 |
Sensible | kW (BTU/H) | 19.8 |
| 67,500 |
Flow Rate | l/s (GPM) | 1.2 |
| 19.7 |
Pressure Drop | kPa (ft) | 65.9 |
| 22.1 |
23.9ºC DB, 16.9ºC WB (75ºF DB, 62.5ºF WB) 50% RH | ||||
Total | kW (BTU/H) | 20.4 |
| 69,700 |
Sensible | kW (BTU/H) | 16.8 |
| 57,500 |
Flow Rate | l/s (GPM) | 0.9 |
| 14.7 |
Pressure Drop | kPa (ft) | 38.1 |
| 12.8 |
23.9ºC DB, 16.2ºC WB (75ºF DB, 61.1ºF WB) 45% RH | ||||
Total | kW (BTU/H) | 19.0 |
| 64,800 |
Sensible | kW (BTU/H) | 17.4 |
| 59,500 |
Flow Rate | l/s (GPM) | 0.8 |
| 13.3 |
Pressure Drop | kPa (ft) | 31.6 |
| 10.6 |
22.2ºC DB, 15.6ºC WB (72ºF DB, 60.1ºF WB) 50% RH | ||||
Total | kW (BTU/H) | 16.7 |
| 57,100 |
Sensible | kW (BTU/H) | 15.1 |
| 51,400 |
Flow Rate | l/s (GPM) | 0.8 |
| 12.0 |
Pressure Drop | kPa (ft) | 26.2 |
| 8.8 |
22.2ºC DB, 14.8ºC WB (72ºF DB, 58.7ºF WB) 45% RH | ||||
Total | kW (BTU/H) | 15.7 |
| 53,500 |
Sensible | kW (BTU/H) | 15.4 |
| 52,400 |
Flow Rate | l/s (GPM) | 0.7 |
| 11.1 |
Pressure Drop | kPa (ft) | 22.6 |
| 7.6 |
Indoor Unit | BR 101C |
Fan Data (Blower A12x9AT)** |
|
|
|
Standard Air, CMH (CFM) | 4420 (2600) |
Standard Fan Motor, kW (hp) | 1.1 |
Opt Fan Motor, kW (hp) | 1.5 (2) |
Ext Static, Pa (in. WG) | 75 (.3) |
Chilled Water Coil | |
|
|
Face Area, m2 (ft2) | .62 (6.67) |
Rows | 4 |
Face Velocity, m/s (FPM) | 1.9 (375) |
Electric Reheat | |
Capacity, element kW (inc. motor heat, BTU/H) | 15 (56,200) |
Hot Water Reheat 82.2°C (180°F) EWT, 23.9°C (75°F) EAT - Optional (Includes std air volume and opt. fan motor hp)
Capacity, inc. motor heat, kW (BTU/H) | 25.3 (86,200) | |
Flow Rate, l/s (GPM) | .32 | (5.0) |
Pressure drop, kPa (ft.) | 50.4 | (16.9) |
Infrared Humidifier - Standard |
|
|
Capacity, kg/hr (lb/hr) | 5 (11) | |
kW | 4.8 | |
Steam Generating Humidifier - Optional |
|
|
Capacity, kg/hr (lb/hr) | 5 (11) | |
kW | 3.9 |
Filter Section - Efficiencies per ASHRAE 52.1 - Disposable Type
20% Eff. available in 51mm (2") - Standard, or Optional 102mm (4") Depths; other Optional 102mm (4") Eff. are: 30%,
Nominal Size - mm | 28.5 x 29.5 |
Nominal Size - inches | 724 x 749 |
Effective Surface Area - m2 (ft2) | 2.2 (24.1) |
Connection |
|
CW Supply | 1 1/8 OD Cu |
CW Return | 1 1/8 OD Cu |
Humidifier Supply | 1/4 OD Cu |
Condensate Drain | 1/2 FPT |
Control Valve |
|
Maximum design water pressure 1034.4 kPa (150 PSI) | |
Valve Actuator | Modulating |
Sensors | Proportional |
Valve Body | |
Valve Size, in. | 1 |
Cv | 13.9 |
| |
Close Off Pressure - kPa (PSI) | 483 (70) |
*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for ASHRAE
**Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.
37