Emerson manual Liebert Challenger ITR chilled water data, 50 Hz, Indoor Unit BR 101C

Page 45

System Data

Table 15 Liebert Challenger ITR chilled water data, 50 Hz

Capacity Data kW (BTU/H) @ 7.2°C (45°F ) EWT, 5.6°C (10°F) Water Rise; Net Capacity Data

Indoor Unit

 

 

BR 101C

BR = Horizontal Flow

 

37.8ºC DB, 21.1ºC WB (100ºF DB,

70ºF WB) 20% RH, 6.7°C (12°F)

Water Rise

 

 

 

 

Total

kW (BTU/H)

34.0

 

116,000

Sensible

kW (BTU/H)

31.9

 

109,000

Flow Rate

l/s (GPM)

1.3

 

19.9

Pressure Drop

kPa (ft)

66.5

 

22.3

35ºC DB, 20.2ºC WB (95ºF DB, 68.3ºF WB) 24% RH,

6.1°C (11°F) Water Rise

 

 

 

Total

kW (BTU/H)

31.1

 

106,000

Sensible

kW (BTU/H)

29.0

 

99,100

Flow Rate

l/s (GPM)

1.3

 

19.9

Pressure Drop

kPa (ft)

66.5

 

22.3

32.2ºC DB, 19.2ºC WB (90ºF DB, 66.5ºF WB) 28% RH

Total

kW (BTU/H)

28.2

 

96,100

Sensible

kW (BTU/H)

26.0

 

88,900

Flow Rate

l/s (GPM)

1.3

 

20.0

Pressure Drop

kPa (ft)

66.8

 

22.4

29.4ºC DB, 18ºC WB (85ºF DB, 64.4ºF WB) 32% RH

Total

kW (BTU/H)

24.7

 

84,200

Sensible

kW (BTU/H)

23.0

 

78,400

Flow Rate

l/s (GPM)

1.1

 

17.6

Pressure Drop

kPa (ft)

52.7

 

17.7

26.7ºC DB, 17.1ºC WB (80ºF DB, 62.7ºF WB) 38% RH

Total

kW (BTU/H)

21.5

 

73,500

Sensible

kW (BTU/H)

19.6

 

66,900

 

 

 

 

 

Flow Rate

l/s (GPM)

1.0

 

15.8

 

 

 

 

 

Pressure Drop

kPa (ft)

42.9

 

14.4

26.7ºC DB, 19.2ºC WB (80ºF DB, 66.5ºF WB) 50% RH

Total

kW (BTU/H)

27.5

 

94,000

Sensible

kW (BTU/H)

19.8

 

67,500

Flow Rate

l/s (GPM)

1.2

 

19.7

Pressure Drop

kPa (ft)

65.9

 

22.1

23.9ºC DB, 16.9ºC WB (75ºF DB, 62.5ºF WB) 50% RH

Total

kW (BTU/H)

20.4

 

69,700

Sensible

kW (BTU/H)

16.8

 

57,500

Flow Rate

l/s (GPM)

0.9

 

14.7

Pressure Drop

kPa (ft)

38.1

 

12.8

23.9ºC DB, 16.2ºC WB (75ºF DB, 61.1ºF WB) 45% RH

Total

kW (BTU/H)

19.0

 

64,800

Sensible

kW (BTU/H)

17.4

 

59,500

Flow Rate

l/s (GPM)

0.8

 

13.3

Pressure Drop

kPa (ft)

31.6

 

10.6

22.2ºC DB, 15.6ºC WB (72ºF DB, 60.1ºF WB) 50% RH

Total

kW (BTU/H)

16.7

 

57,100

Sensible

kW (BTU/H)

15.1

 

51,400

Flow Rate

l/s (GPM)

0.8

 

12.0

Pressure Drop

kPa (ft)

26.2

 

8.8

22.2ºC DB, 14.8ºC WB (72ºF DB, 58.7ºF WB) 45% RH

Total

kW (BTU/H)

15.7

 

53,500

Sensible

kW (BTU/H)

15.4

 

52,400

Flow Rate

l/s (GPM)

0.7

 

11.1

Pressure Drop

kPa (ft)

22.6

 

7.6

Indoor Unit

BR 101C

Fan Data (Blower A12x9AT)**

 

 

 

Standard Air, CMH (CFM)

4420 (2600)

Standard Fan Motor, kW (hp)

1.1 (1-1/2)

Opt Fan Motor, kW (hp)

1.5 (2)

Ext Static, Pa (in. WG)

75 (.3)

Chilled Water Coil (V-Frame, at standard conditions)

 

 

Face Area, m2 (ft2)

.62 (6.67)

Rows

4

Face Velocity, m/s (FPM)

1.9 (375)

Electric Reheat 2-Stage (Stainless Steel, Fin Tubular) - Std

Capacity, element kW (inc. motor heat, BTU/H)

15 (56,200)

Hot Water Reheat 82.2°C (180°F) EWT, 23.9°C (75°F) EAT - Optional (Includes std air volume and opt. fan motor hp)

Capacity, inc. motor heat, kW (BTU/H)

25.3 (86,200)

Flow Rate, l/s (GPM)

.32

(5.0)

Pressure drop, kPa (ft.)

50.4

(16.9)

Infrared Humidifier - Standard

 

 

Capacity, kg/hr (lb/hr)

5 (11)

kW

4.8

Steam Generating Humidifier - Optional

 

 

Capacity, kg/hr (lb/hr)

5 (11)

kW

3.9

Filter Section - Efficiencies per ASHRAE 52.1 - Disposable Type

20% Eff. available in 51mm (2") - Standard, or Optional 102mm (4") Depths; other Optional 102mm (4") Eff. are: 30%, 40-45%, 60-65%

Nominal Size - mm

28.5 x 29.5

Nominal Size - inches

724 x 749

Effective Surface Area - m2 (ft2)

2.2 (24.1)

Connection Sizes-Challenger ITR Unit

 

CW Supply

1 1/8 OD Cu

CW Return

1 1/8 OD Cu

Humidifier Supply

1/4 OD Cu

Condensate Drain

1/2 FPT

Control Valve

 

Maximum design water pressure 1034.4 kPa (150 PSI)

Valve Actuator

Modulating

Sensors

Proportional

Valve Body

Three-Way

Valve Size, in.

1

Cv

13.9

Two-Way Valve (Optional)

 

Close Off Pressure - kPa (PSI)

483 (70)

*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the standard rating for ASHRAE 127-2001.All capacities are nominal values; actual performance will be ±5%.

**Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for recommendations.

37

Image 45
Contents Liebert Challenger ITR Split system configurations Table iii Self-contained system configurationsTable i Product model information Table of Contents Glycool SYSTEMS-STANDARD and Optional Features AIR-COOLEDSYSTEM-STANDARD and Optional FeaturesRefrigeration Systems Optional EQUIPMENT-ALLSYSTEMSComprehensive Monitoring SOLUTIONS-OPTIONAL System Data Dimensional Drawings Electrical DataComprehensive Monitoring SYSTEMS-OPTIONAL Figures Page Page Air Volume Temperature ControlHumidity Control Air FiltrationMultiple Configurations to Fit a Variety of Spaces Liebert Challenger ITREfficiency in Economic Terms Unit configurations Image is Illustrative only Control DiagnosticsControl Type Internal System ControlCustom Alarm Maximum of Four AlarmsLogging Graphical Displays-Advanced Graphic Control OnlyElectrical Panel Cabinet and FrameFan Section Infrared HumidifierDisconnect Switch-Locking Type Remote Temperature/ Humidity SensorsCondensate Pump Condensate pump capacityChilled Water System-Optional Features Chilled Water System-Standard FeaturesRefrigeration System Components-Standard Features Self-Contained SystemsSplit Systems Air-Cooled, Self-Contained Systems-Optional Features Air-Cooled, Self-Contained Systems-Standard FeaturesAir-Cooled Split Systems-Optional Features Air-Cooled Split Systems-Standard FeaturesCentrifugal Fan, Condensing Unit Propeller Fan Condensing UnitWater/Glycol Split System-Standard Features Water/Glycol Self-Contained Systems-Standard FeaturesWater/Glycol-Cooled, Split System-Optional Features Factory Installed Non-Fused Disconnect SwitchGlycol Pump GLYCOOL-Self-Contained Models Only Glycool System-Standard FeaturesDrycooler Glycol and GLYCOOL-Cooled-Optional EquipmentQuiet-Line Drycoolers Evaporator Coil Econ-O-Coil Three-way Glycool Control ValveSteam Generating Humidifier Steam generating humidifier Adjustable Floor StandHigh-Efficiency Filter SCR ReheatHigh External Static Blowers High-Efficiency MotorsFirestat Smoke DetectorHot Water Reheat FirestatStand-Alone Monitoring and Leak Detection Solutions Enterprise Monitoring SystemsNetwork Monitoring Systems Discrete Output Interface Card Leak Detection ModulesLiebert SiteLink Liebert SiteScan WebLiebert Nform Environmental Discrete Outputs CardTemperature and Humidity Recorder Universal MonitorLeak Detection BR 067A BR 060E Liebert Challenger ITR air-cooled data-60 HzInfrared Humidifier Standard System Type Split Systems Liebert Challenger ITR air-cooled data-50 HzFan Data Blower A12x9AT Evaporator Coil V-Frame, at Standard ConditionsLiebert Challenger ITR air-cooled data-50Hz Connection Sizes Challenger ITR UnitCondenser Air 35C 95F Ambient Liebert Challenger ITR water cooled data, 60 Hz System Type Self-Contained Split SystemsIndoor Unit BR 071WG BR 060E Net Capacity Data Water Regulating Valve Water Requirements Coaxial CondenserConnection Sizes Remote Condensing Unit BTU/H Liebert Challenger ITR water cooled data, 50 HzCapacity, kg/hr lb/hr Glycool Liebert Challenger ITR glycol cooled data, 60 HzSteam Generating Humidifier Optional Indoor UnitGlycool Liebert Challenger ITR glycol cooled data, 50 HzGlycol Pump 3-Phase kW hp System Type Glycol CooledDrycooler 35C 95F Ambient Indoor Unit BR 102C Fan Data Blower A12x9AT Liebert Challenger ITR chilled water data, 60 HzIndoor Unit BR 101C Liebert Challenger ITR chilled water data, 50 Hz50 Hz 60 Hz Unit Weight Models Lb. kg Dimensional DrawingsOptional Floor Stand Model Net Weight 60 Hz 50 Hz Lbs kg MC69W MC68W 36-1/4 SL-11081Liebert Lee-Temp Receiver = 40 1016mm = 7-1/2 190mm Liebert Challenger ITR electrical data1-60 Hz Electrical DataMotor Hp 1.5 kW Self-contained with SCR reheatMotor Hp 2.2 kW Electric Reheat Only Motor Hp 1.1 kWOutdoor condensing units Scroll compressor and main fan for comparison purposes onlyVoltage 208 230 460 575 60 Hz Scroll Compressor Main Fan Motor Hp 1.1 kWOutdoor condensing units-Quiet-Line Indoor condensing units, air-cooledIndoor condensing units, water-cooled Liebert Lee-Temp condensers Fan speed control condensersDrycooler and pump package 95F 35C ambient Voltage 208/230 460 575 GlycolLiebert Challenger ITR electrical data-50 Hz Scroll compressor and main fan for comparison only Indoor condensing units water-cooled Indoor condensing units air-cooledDrycooler only 35C 95F ambient, three-phase Drycooler only 35C 95F ambient, single phasePumps Design Requirements SummarySubmittals All SystemsAdvanced Microprocessor Control Standard Audible Alarm AlarmsCommon Alarm DiagnosticsCommunications Advanced Microprocessor Control with Graphics OptionalAlarms Steam Generating Humidifier Optional Infrared Humidifier StandardElectric Reheat Standard Hot Water Reheat OptionalDirect Expansion Self-Contained Systems Liebert Lee-Temp Head Pressure Control Optional Fan Speed Control FSC Head Pressure Control StandardCentrifugal Fan Condenser Optional Two-way Water Regulating Valve with Bypass StandardGlycool Self-Contained Systems Outdoor UnitCentrifugal Fan Condensing Unit Direct Expansion Split SystemsOptional Disconnect Ton ModelsOptional Quiet-Line Models Water or Glycol-Cooled Split SystemsOptional High Ambient Models Water or Glycol-Cooled Condensing UnitChilled Water Self-Contained Systems Chilled Water Coil Flow Switch OptionalThree-way Chilled Water Valve Standard Two-way Chilled Water Valve OptionalComprehensive Monitoring Solutions Installation of Environmental Control UnitsField Quality Control Page Iti Ne tTi n That