Emerson ITR manual Outdoor Unit, Glycool Self-Contained Systems

Page 68

Electrical Data

Outdoor Unit

Propeller Fan Drycooler (Standard)

The Liebert manufactured drycooler shall be the low profile, slow speed, direct drive propeller fan type. The drycooler shall be constructed of aluminum and contain a copper tube aluminum fin coil with an integral electric control panel. The drycooler shall be designed for _____ °F (°C) ambient.

Centrifugal Fan Drycooler (Optional)

The system shall be supplied with a centrifugal fan drycooler (LCD). The drycooler shall be con- structed of galvanized steel with a copper tube, aluminum fin coil. The heavy duty fan shall be the centrifugal type, double width, double inlet. The 1750 RPM (1450 RPM @ 50 Hz) fan motor shall be mounted on an adjustable base, and equipped with an adjustable motor pulley. A three-way control valve and thermostat shall maintain the desired fluid temperature. Electrical controls shall be in a rain-tight enclosure. The system shall be designed for _____ °F (°C) ambient. The drycooler shall have

a _____ Volt, 3 phase, _____ Hz power supply.

Single Glycol Pump Package (Standard)

This system shall be provided with a centrifugal pump mounted in a weatherproof and vented enclo- sure. The pump shall be rated for _____ GPM (l/s) at _____ ft. of head (kPa), and operate on _____ Volt,

3 phase, _____ Hz.

Dual Glycol Pump Package (Optional)

The dual pump package shall include pumps, enclosure, and field mounted flow switch. The pumps shall be wired to the drycooler control box which includes a lead/lag switch for the pumps. The standby pump shall automatically start upon failure of the lead pump. Each pump shall be rated

_____ for GPM (l/s) at _____ feet of head (kPa).

2.2.3GLYCOOL Self-Contained Systems

Econ-O-Coil

The Econ-O-Coil shall be constructed of copper tubes and aluminum fins and be located upstream of the evaporator coil. The Econ-O-Coil shall be designed for closed-loop applications using properly treated glycol solutions. Applications using a cooling tower loop or other open water system must specify a 70/30 Cu-Ni Econ-O-Coil for improved corrosion resistance. The coil shall be rated at _____

BTU/HR (kW) sensible cooling capacity with a 45°F (7.2°C) entering glycol solution temperature. The GLYCOOL coil shall require _____ GPM (l/s) and the total unit pressure drop shall not exceed _____

feet of water (kPa) when in the free cooling mode.

Three-way GLYCOOL Valve

The Econ-O-Coil coil shall be equipped with a fully proportional three-way control valve. This motor- ized control valve shall control the amount of flow to the Econ-O-Coil and maintain constant tempera- ture and relative humidity.

Glycol Condenser

The glycol system shall be equipped with a coaxial condenser having a total pressure drop of _____

feet of water (kPa) and a flow rate of _____ GPM (l/s), with _____ °F (°C) entering 40% ethylene glycol temperature.

Three-way Water Regulating Valve

The condenser circuit shall be pre-piped with a head pressure actuated three-way water regulating valve.

Design Pressure

The Econ-O-Coil/condenser circuit shall be designed for a pressure of [(150 PSI (1034 kPa)) (300 PSI (2069 kPa))].

Comparator Circuit

The system shall be equipped with a microprocessorcontrolled comparator sensor that permits free- cooling operation whenever entering glycol temperature is below return-air temperature.

60

Image 68
Contents Liebert Challenger ITR Table i Product model information Split system configurationsTable iii Self-contained system configurations Table of Contents AIR-COOLEDSYSTEM-STANDARD and Optional Features Glycool SYSTEMS-STANDARD and Optional FeaturesRefrigeration Systems Optional EQUIPMENT-ALLSYSTEMSComprehensive Monitoring SYSTEMS-OPTIONAL Comprehensive Monitoring SOLUTIONS-OPTIONALSystem Data Dimensional Drawings Electrical Data Figures Page Page Temperature Control Air VolumeHumidity Control Air FiltrationEfficiency in Economic Terms Multiple Configurations to Fit a Variety of SpacesLiebert Challenger ITR Unit configurations Image is Illustrative only Diagnostics ControlControl Type Internal System ControlAlarms Custom Alarm Maximum of FourLogging Graphical Displays-Advanced Graphic Control OnlyCabinet and Frame Electrical PanelFan Section Infrared HumidifierRemote Temperature/ Humidity Sensors Disconnect Switch-Locking TypeCondensate Pump Condensate pump capacityChilled Water System-Standard Features Chilled Water System-Optional FeaturesSplit Systems Refrigeration System Components-Standard FeaturesSelf-Contained Systems Air-Cooled, Self-Contained Systems-Standard Features Air-Cooled, Self-Contained Systems-Optional FeaturesAir-Cooled Split Systems-Standard Features Air-Cooled Split Systems-Optional FeaturesCentrifugal Fan, Condensing Unit Propeller Fan Condensing UnitWater/Glycol Self-Contained Systems-Standard Features Water/Glycol Split System-Standard FeaturesGlycol Pump Water/Glycol-Cooled, Split System-Optional FeaturesFactory Installed Non-Fused Disconnect Switch Glycool System-Standard Features GLYCOOL-Self-Contained Models OnlyGlycol and GLYCOOL-Cooled-Optional Equipment DrycoolerQuiet-Line Drycoolers Evaporator Coil Econ-O-Coil Three-way Glycool Control ValveSteam generating humidifier Adjustable Floor Stand Steam Generating HumidifierSCR Reheat High-Efficiency FilterHigh External Static Blowers High-Efficiency MotorsSmoke Detector FirestatHot Water Reheat FirestatNetwork Monitoring Systems Stand-Alone Monitoring and Leak Detection SolutionsEnterprise Monitoring Systems Leak Detection Modules Discrete Output Interface CardLiebert SiteScan Web Liebert SiteLinkLiebert Nform Environmental Discrete Outputs CardLeak Detection Temperature and Humidity RecorderUniversal Monitor Liebert Challenger ITR air-cooled data-60 Hz BR 067A BR 060EInfrared Humidifier Standard Liebert Challenger ITR air-cooled data-50 Hz System Type Split SystemsFan Data Blower A12x9AT Evaporator Coil V-Frame, at Standard ConditionsCondenser Air 35C 95F Ambient Liebert Challenger ITR air-cooled data-50HzConnection Sizes Challenger ITR Unit Indoor Unit BR 071WG BR 060E Net Capacity Data Liebert Challenger ITR water cooled data, 60 HzSystem Type Self-Contained Split Systems Connection Sizes Remote Condensing Unit Water Regulating ValveWater Requirements Coaxial Condenser Liebert Challenger ITR water cooled data, 50 Hz BTU/HCapacity, kg/hr lb/hr Liebert Challenger ITR glycol cooled data, 60 Hz GlycoolIndoor Unit Steam Generating Humidifier OptionalLiebert Challenger ITR glycol cooled data, 50 Hz GlycoolDrycooler 35C 95F Ambient Glycol Pump 3-Phase kW hpSystem Type Glycol Cooled Liebert Challenger ITR chilled water data, 60 Hz Indoor Unit BR 102C Fan Data Blower A12x9ATLiebert Challenger ITR chilled water data, 50 Hz Indoor Unit BR 101CDimensional Drawings 50 Hz 60 Hz Unit Weight Models Lb. kgOptional Floor Stand Model Net Weight 60 Hz 50 Hz Lbs kg MC69W MC68W SL-11081 36-1/4Liebert Lee-Temp Receiver = 40 1016mm = 7-1/2 190mm Electrical Data Liebert Challenger ITR electrical data1-60 HzSelf-contained with SCR reheat Motor Hp 1.5 kWMotor Hp 2.2 kW Electric Reheat Only Motor Hp 1.1 kWScroll compressor and main fan for comparison purposes only Outdoor condensing unitsVoltage 208 230 460 575 60 Hz Scroll Compressor Main Fan Motor Hp 1.1 kWIndoor condensing units, water-cooled Outdoor condensing units-Quiet-LineIndoor condensing units, air-cooled Fan speed control condensers Liebert Lee-Temp condensersDrycooler and pump package 95F 35C ambient Voltage 208/230 460 575 GlycolLiebert Challenger ITR electrical data-50 Hz Scroll compressor and main fan for comparison only Indoor condensing units air-cooled Indoor condensing units water-cooledPumps Drycooler only 35C 95F ambient, three-phaseDrycooler only 35C 95F ambient, single phase Summary Design RequirementsSubmittals All SystemsAdvanced Microprocessor Control Standard Alarms Audible AlarmCommon Alarm DiagnosticsAdvanced Microprocessor Control with Graphics Optional CommunicationsAlarms Infrared Humidifier Standard Steam Generating Humidifier OptionalElectric Reheat Standard Hot Water Reheat OptionalDirect Expansion Self-Contained Systems Fan Speed Control FSC Head Pressure Control Standard Liebert Lee-Temp Head Pressure Control OptionalCentrifugal Fan Condenser Optional Two-way Water Regulating Valve with Bypass StandardOutdoor Unit Glycool Self-Contained SystemsDirect Expansion Split Systems Centrifugal Fan Condensing UnitOptional Disconnect Ton ModelsWater or Glycol-Cooled Split Systems Optional Quiet-Line ModelsOptional High Ambient Models Water or Glycol-Cooled Condensing UnitFlow Switch Optional Chilled Water Self-Contained Systems Chilled Water CoilThree-way Chilled Water Valve Standard Two-way Chilled Water Valve OptionalField Quality Control Comprehensive Monitoring SolutionsInstallation of Environmental Control Units Page Ne t ItiTi n That