Emerson ITR manual Direct Expansion Self-Contained Systems

Page 66

Electrical Data

2.1.12Plenum

The unit shall be supplied with a (2 way) (3 way) (4 way) (low-profile, cold-aisle) air discharge ple- num. The plenum shall be 18 in. (457mm) high or less, insulated and powder painted the same color as the room unit.

2.1.13Disconnect Switch, Locking Type

The manual disconnect switch shall be mounted in the high voltage section of the electrical panel. The switch shall prevent access to the high voltage electrical components until switched to the “OFF” posi- tion.

2.1.14Remote Sensors (Required for Select Applications)

The unit shall be supplied with remote temperature and humidity sensors. The sensors shall be con- nected to the unit by a 30 ft. (9m), 60 ft. (18m), 90 ft. (27m), 120 ft. (36m), 150 ft. (45m) shielded cable.

2.1.15Remote Sensor Installation Location

The remote temperature and humidity sensor should be installed in the cold aisle in front of the equipment to be cooled. It should be mounted at the farthest point from the cooling unit that supply air needs to reach but still within the unit’s area of influence. The sensor should be installed at the highest point that equipment will draw in cooled air.

2.1.16Firestat (Optional)

The firestat shall immediately shut down the system when high temperatures are detected. The fir- estat shall be mounted in the electrical panel with the sensing element in the return air.

2.1.17Smoke Detector (Optional)

The smoke detector senses the return air, shuts down the unit upon detection, and sends visual and audible alarm. Dry contacts are available for a remote customer alarm. This smoke detector is not intended to function as or replace any room smoke detection system that may be required by local or national codes.

2.1.18Condensate Pump

The condensate pump shall have the capacity of ____ GPH (l/h) at ____ ft. (m) head @ ____ V - ____ Hz. It shall be complete with (single) (dual) integral float switch, pump, motor assembly, and reservoir.

2.2Direct Expansion Self-Contained Systems

Direct Expansion Coil

The evaporator coil shall have _____ sq.ft. (sq. m) face area, _____ rows deep. It shall be configured as

V-frame and be constructed of copper tubes and aluminum fins and have a maximum face velocity of

_____ ft. per minute (m/s) at _____ CFM (CMH). The coil shall be provided with a stainless steel drain

pan.

Refrigeration System

The refrigeration system shall consist of a high efficiency scroll compressor, hot gas bypass, pressure safety switches, externally equalized expansion valve, filter drier, refrigerant sight glass and mois- ture indicator.

2.2.1Air-Cooled Self-Contained Systems

Pump Down Control

A liquid line solenoid valve shall be provided for pump down control.

Crankcase Heater

A crankcase heater shall be provided for additional system protection from refrigerant migration dur- ing off cycles.

Propeller Fan Condenser (Standard)

The Liebert manufactured air-cooled condenser shall be the low profile, slow speed, direct-drive, pro- peller-fan type. The condenser shall be constructed of aluminum and contain a copper tube, alumi- num fin coil with an integral electric control panel. The system shall be designed for _____ °F (°C) ambient. The air-cooled condenser shall have a _____ Volt, _____ phase, ____ Hz power supply.

58

Image 66
Contents Liebert Challenger ITR Split system configurations Table iii Self-contained system configurationsTable i Product model information Table of Contents Refrigeration Systems AIR-COOLEDSYSTEM-STANDARD and Optional FeaturesGlycool SYSTEMS-STANDARD and Optional Features Optional EQUIPMENT-ALLSYSTEMSComprehensive Monitoring SOLUTIONS-OPTIONAL System Data Dimensional Drawings Electrical DataComprehensive Monitoring SYSTEMS-OPTIONAL Figures Page Page Humidity Control Temperature ControlAir Volume Air FiltrationMultiple Configurations to Fit a Variety of Spaces Liebert Challenger ITREfficiency in Economic Terms Unit configurations Image is Illustrative only Control Type DiagnosticsControl Internal System ControlLogging AlarmsCustom Alarm Maximum of Four Graphical Displays-Advanced Graphic Control OnlyFan Section Cabinet and FrameElectrical Panel Infrared HumidifierCondensate Pump Remote Temperature/ Humidity SensorsDisconnect Switch-Locking Type Condensate pump capacityChilled Water System-Standard Features Chilled Water System-Optional FeaturesRefrigeration System Components-Standard Features Self-Contained SystemsSplit Systems Air-Cooled, Self-Contained Systems-Standard Features Air-Cooled, Self-Contained Systems-Optional FeaturesCentrifugal Fan, Condensing Unit Air-Cooled Split Systems-Standard FeaturesAir-Cooled Split Systems-Optional Features Propeller Fan Condensing UnitWater/Glycol Self-Contained Systems-Standard Features Water/Glycol Split System-Standard FeaturesWater/Glycol-Cooled, Split System-Optional Features Factory Installed Non-Fused Disconnect SwitchGlycol Pump Glycool System-Standard Features GLYCOOL-Self-Contained Models OnlyQuiet-Line Drycoolers Glycol and GLYCOOL-Cooled-Optional EquipmentDrycooler Evaporator Coil Econ-O-Coil Three-way Glycool Control ValveSteam generating humidifier Adjustable Floor Stand Steam Generating HumidifierHigh External Static Blowers SCR ReheatHigh-Efficiency Filter High-Efficiency MotorsHot Water Reheat Smoke DetectorFirestat FirestatStand-Alone Monitoring and Leak Detection Solutions Enterprise Monitoring SystemsNetwork Monitoring Systems Leak Detection Modules Discrete Output Interface CardLiebert Nform Liebert SiteScan WebLiebert SiteLink Environmental Discrete Outputs CardTemperature and Humidity Recorder Universal MonitorLeak Detection Liebert Challenger ITR air-cooled data-60 Hz BR 067A BR 060EInfrared Humidifier Standard Fan Data Blower A12x9AT Liebert Challenger ITR air-cooled data-50 HzSystem Type Split Systems Evaporator Coil V-Frame, at Standard ConditionsLiebert Challenger ITR air-cooled data-50Hz Connection Sizes Challenger ITR UnitCondenser Air 35C 95F Ambient Liebert Challenger ITR water cooled data, 60 Hz System Type Self-Contained Split SystemsIndoor Unit BR 071WG BR 060E Net Capacity Data Water Regulating Valve Water Requirements Coaxial CondenserConnection Sizes Remote Condensing Unit Liebert Challenger ITR water cooled data, 50 Hz BTU/HCapacity, kg/hr lb/hr Liebert Challenger ITR glycol cooled data, 60 Hz GlycoolIndoor Unit Steam Generating Humidifier OptionalLiebert Challenger ITR glycol cooled data, 50 Hz GlycoolGlycol Pump 3-Phase kW hp System Type Glycol CooledDrycooler 35C 95F Ambient Liebert Challenger ITR chilled water data, 60 Hz Indoor Unit BR 102C Fan Data Blower A12x9ATLiebert Challenger ITR chilled water data, 50 Hz Indoor Unit BR 101CDimensional Drawings 50 Hz 60 Hz Unit Weight Models Lb. kgOptional Floor Stand Model Net Weight 60 Hz 50 Hz Lbs kg MC69W MC68W SL-11081 36-1/4Liebert Lee-Temp Receiver = 40 1016mm = 7-1/2 190mm Electrical Data Liebert Challenger ITR electrical data1-60 HzMotor Hp 2.2 kW Self-contained with SCR reheatMotor Hp 1.5 kW Electric Reheat Only Motor Hp 1.1 kWVoltage 208 230 460 575 60 Hz Scroll Compressor Scroll compressor and main fan for comparison purposes onlyOutdoor condensing units Main Fan Motor Hp 1.1 kWOutdoor condensing units-Quiet-Line Indoor condensing units, air-cooledIndoor condensing units, water-cooled Drycooler and pump package 95F 35C ambient Fan speed control condensersLiebert Lee-Temp condensers Voltage 208/230 460 575 GlycolLiebert Challenger ITR electrical data-50 Hz Scroll compressor and main fan for comparison only Indoor condensing units air-cooled Indoor condensing units water-cooledDrycooler only 35C 95F ambient, three-phase Drycooler only 35C 95F ambient, single phasePumps Submittals SummaryDesign Requirements All SystemsAdvanced Microprocessor Control Standard Common Alarm AlarmsAudible Alarm DiagnosticsAdvanced Microprocessor Control with Graphics Optional CommunicationsAlarms Electric Reheat Standard Infrared Humidifier StandardSteam Generating Humidifier Optional Hot Water Reheat OptionalDirect Expansion Self-Contained Systems Centrifugal Fan Condenser Optional Fan Speed Control FSC Head Pressure Control StandardLiebert Lee-Temp Head Pressure Control Optional Two-way Water Regulating Valve with Bypass StandardOutdoor Unit Glycool Self-Contained SystemsOptional Disconnect Direct Expansion Split SystemsCentrifugal Fan Condensing Unit Ton ModelsOptional High Ambient Models Water or Glycol-Cooled Split SystemsOptional Quiet-Line Models Water or Glycol-Cooled Condensing UnitThree-way Chilled Water Valve Standard Flow Switch OptionalChilled Water Self-Contained Systems Chilled Water Coil Two-way Chilled Water Valve OptionalComprehensive Monitoring Solutions Installation of Environmental Control UnitsField Quality Control Page Ti n Ne tIti That