Emerson manual Electrical Data, Liebert Challenger ITR electrical data1-60 Hz

Page 51

Electrical Data

15.0ELECTRICAL DATA

Table 16

Liebert Challenger ITR electrical data1—60 Hz

 

 

 

 

 

 

 

 

 

 

 

Self-Contained

 

 

 

 

Split System Evaporator or Chilled Water

 

 

 

 

 

 

 

 

 

 

Model Type

 

 

BR067A, BR071WG, BM061G

 

 

 

BR060E, BR102C

 

 

 

 

 

 

 

All Voltages Are 3 Phase Unless Noted Otherwise

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

208

 

230

460

 

575

 

208

 

230

 

460

 

575

With Electric Reheat and Humidifier (Infrared or Steam Generating) (Note: See Table 17 for units w/SCR reheats.2)

 

 

 

Motor

 

 

 

1.5 hp (1.1 kW)

 

 

 

 

 

1.5 hp (1.1 kW)

 

 

FLA

68.0

 

65.0

32.3

 

24.6

 

60.6

 

55.4

 

28.1

 

24.6

 

WSA

83.6

 

80.0

39.7

 

30.8

 

75.8

 

69.3

 

35.1

 

30.8

 

OPD

90

 

90

40

 

30

 

80

 

70

 

40

 

35

Motor

 

 

 

2.0 hp

(1.5 kW)

 

 

 

 

 

2.0 hp

(1.5 kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLA

69.8

 

66.6

33.1

 

25.2

 

62.4

 

57.0

 

28.9

 

25.2

 

WSA

85.4

 

81.6

40.5

 

31.5

 

78.0

 

71.3

 

36.1

 

31.5

 

OPD

90

 

90

45

 

30

 

80

 

80

 

40

 

35

Motor

 

 

 

3.0 hp

(2.2 kW)

 

 

 

 

 

3.0 hp

(2.2 kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLA

72.9

 

69.4

34.5

 

26.4

 

65.5

 

59.8

 

30.3

 

26.4

 

WSA

88.5

 

84.4

41.9

 

33.0

 

81.9

 

74.8

 

37.9

 

33.0

 

OPD

90

 

90

45

 

35

 

90

 

80

 

40

 

35

Humidifier Only (Infrared

or Steam

Generating)

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

 

1.5 hp (1.1 kW)

 

 

 

 

 

1.5 hp (1.1 kW)

 

 

FLA

39.7

 

37.0

18.4

 

16.9

 

19.0

 

16.3

 

8.4

 

9.5

 

WSA

44.9

 

42.2

20.9

 

18.8

 

23.8

 

20.4

 

10.5

 

11.9

 

OPD

60

 

60

30

 

25

 

25

 

20

 

15

 

15

Motor

 

 

 

2.0 hp

(1.5 kW)

 

 

 

 

 

2.0 hp

(1.5 kW)

 

 

 

FLA

41.5

 

38.6

19.2

 

17.5

 

20.8

 

17.9

 

9.2

 

10.1

 

WSA

46.7

 

43.8

21.7

 

19.4

 

26.0

 

22.4

 

11.5

 

12.6

 

OPD

60

 

60

30

 

25

 

30

 

25

 

15

 

15

Motor

 

 

 

3.0 hp

(2.2 kW)

 

 

 

 

 

3.0 hp

(2.2 kW)

 

 

 

FLA

44.6

41.4

20.6

18.7

 

23.9

20.7

 

10.6

 

11.3

 

WSA

49.8

46.6

23.1

20.6

 

29.9

25.9

 

13.3

 

14.1

 

OPD

70

60

30

25

 

35

30

 

15

 

15

Electric Reheat Only (Note: See Table 17 for Self-contained units w/SCR reheats.2)

Motor

 

1.5 hp (1.1 kW)

 

 

1.5 hp (1.1 kW)

 

FLA

68.0

65.0

32.3

24.6

47.3

44.3

22.3

17.2

WSA

83.6

80.0

39.7

30.2

59.1

55.4

27.9

21.5

OPD

90

90

40

30

60

60

30

25

Motor

 

2.0 hp

(1.5 kW)

 

 

2.0 hp

(1.5 kW)

 

FLA

69.8

66.6

33.1

25.2

49.1

45.9

23.1

17.8

WSA

85.4

81.6

40.5

30.8

61.4

57.4

28.9

22.3

OPD

90

90

45

30

70

60

30

25

Motor

 

3.0 hp

(2.2 kW)

 

 

3.0 hp

(2.2 kW)

 

FLA

72.9

69.4

34.5

26.4

52.2

48.7

24.5

19.0

WSA

88.5

84.4

41.9

32.0

65.3

60.9

30.6

23.8

OPD

90

90

45

35

60

70

35

20

Without Electric Reheat

and Humidifier

 

 

 

 

 

 

 

Motor

 

1.5 hp (1.1 kW)

 

 

1.5 hp (1.1 kW)

 

FLA

26.4

25.9

12.6

9.5

5.7

5.2

2.6

2.1

WSA

31.6

31.1

15.1

11.4

7.1

6.5

3.3

2.6

OPD

50

50

25

15

15

15

15

15

Motor

 

2.0 hp

(1.5 kW)

 

 

2.0 hp

(1.5 kW)

 

 

 

 

 

 

 

 

 

 

FLA

28.2

27.5

13.4

10.1

7.5

6.8

3.4

2.7

WSA

33.4

32.7

15.9

12.0

9.4

8.5

4.3

3.4

OPD

50

50

25

15

15

15

15

15

Motor

 

3.0 hp

(2.2 kW)

 

 

3.0 hp

(2.2 kW)

 

FLA

31.3

30.3

14.8

11.3

10.6

9.6

4.8

3.9

WSA

36.5

35.5

17.3

13.2

13.3

12.0

6.0

4.9

OPD

50

50

25

20

20

20

15

15

1.Contact factory for 380-3-60 data.

2.For Split System Evaporators with SCR reheat, use the values above. The values above were calculated per UL Standard 1995.

FLA = Full Load Amps (Input Amps); WSA = Wire Size Amps (Minimum Supply Circuit Ampacity); OPD = Maximum Overcurrent Protective Device Size RLA = Rated Load Amps; LRA = Locked Rotor Amps

* R = In the Row; M = In the Row with Econ-O-Coil

43

Image 51
Contents Liebert Challenger ITR Split system configurations Table iii Self-contained system configurationsTable i Product model information Table of Contents Optional EQUIPMENT-ALLSYSTEMS AIR-COOLEDSYSTEM-STANDARD and Optional FeaturesGlycool SYSTEMS-STANDARD and Optional Features Refrigeration SystemsComprehensive Monitoring SOLUTIONS-OPTIONAL System Data Dimensional Drawings Electrical DataComprehensive Monitoring SYSTEMS-OPTIONAL Figures Page Page Air Filtration Temperature ControlAir Volume Humidity ControlMultiple Configurations to Fit a Variety of Spaces Liebert Challenger ITREfficiency in Economic Terms Unit configurations Image is Illustrative only Internal System Control DiagnosticsControl Control TypeGraphical Displays-Advanced Graphic Control Only AlarmsCustom Alarm Maximum of Four LoggingInfrared Humidifier Cabinet and FrameElectrical Panel Fan SectionCondensate pump capacity Remote Temperature/ Humidity SensorsDisconnect Switch-Locking Type Condensate PumpChilled Water System-Optional Features Chilled Water System-Standard FeaturesRefrigeration System Components-Standard Features Self-Contained SystemsSplit Systems Air-Cooled, Self-Contained Systems-Optional Features Air-Cooled, Self-Contained Systems-Standard FeaturesPropeller Fan Condensing Unit Air-Cooled Split Systems-Standard FeaturesAir-Cooled Split Systems-Optional Features Centrifugal Fan, Condensing UnitWater/Glycol Split System-Standard Features Water/Glycol Self-Contained Systems-Standard FeaturesWater/Glycol-Cooled, Split System-Optional Features Factory Installed Non-Fused Disconnect SwitchGlycol Pump GLYCOOL-Self-Contained Models Only Glycool System-Standard FeaturesEvaporator Coil Econ-O-Coil Three-way Glycool Control Valve Glycol and GLYCOOL-Cooled-Optional EquipmentDrycooler Quiet-Line DrycoolersSteam Generating Humidifier Steam generating humidifier Adjustable Floor StandHigh-Efficiency Motors SCR ReheatHigh-Efficiency Filter High External Static BlowersFirestat Smoke DetectorFirestat Hot Water ReheatStand-Alone Monitoring and Leak Detection Solutions Enterprise Monitoring SystemsNetwork Monitoring Systems Discrete Output Interface Card Leak Detection ModulesEnvironmental Discrete Outputs Card Liebert SiteScan WebLiebert SiteLink Liebert NformTemperature and Humidity Recorder Universal MonitorLeak Detection BR 067A BR 060E Liebert Challenger ITR air-cooled data-60 HzInfrared Humidifier Standard Evaporator Coil V-Frame, at Standard Conditions Liebert Challenger ITR air-cooled data-50 HzSystem Type Split Systems Fan Data Blower A12x9ATLiebert Challenger ITR air-cooled data-50Hz Connection Sizes Challenger ITR UnitCondenser Air 35C 95F Ambient Liebert Challenger ITR water cooled data, 60 Hz System Type Self-Contained Split SystemsIndoor Unit BR 071WG BR 060E Net Capacity Data Water Regulating Valve Water Requirements Coaxial CondenserConnection Sizes Remote Condensing Unit BTU/H Liebert Challenger ITR water cooled data, 50 HzCapacity, kg/hr lb/hr Glycool Liebert Challenger ITR glycol cooled data, 60 HzSteam Generating Humidifier Optional Indoor UnitGlycool Liebert Challenger ITR glycol cooled data, 50 HzGlycol Pump 3-Phase kW hp System Type Glycol CooledDrycooler 35C 95F Ambient Indoor Unit BR 102C Fan Data Blower A12x9AT Liebert Challenger ITR chilled water data, 60 HzIndoor Unit BR 101C Liebert Challenger ITR chilled water data, 50 Hz50 Hz 60 Hz Unit Weight Models Lb. kg Dimensional DrawingsOptional Floor Stand Model Net Weight 60 Hz 50 Hz Lbs kg MC69W MC68W 36-1/4 SL-11081Liebert Lee-Temp Receiver = 40 1016mm = 7-1/2 190mm Liebert Challenger ITR electrical data1-60 Hz Electrical DataElectric Reheat Only Motor Hp 1.1 kW Self-contained with SCR reheatMotor Hp 1.5 kW Motor Hp 2.2 kWMain Fan Motor Hp 1.1 kW Scroll compressor and main fan for comparison purposes onlyOutdoor condensing units Voltage 208 230 460 575 60 Hz Scroll CompressorOutdoor condensing units-Quiet-Line Indoor condensing units, air-cooledIndoor condensing units, water-cooled Voltage 208/230 460 575 Glycol Fan speed control condensersLiebert Lee-Temp condensers Drycooler and pump package 95F 35C ambientLiebert Challenger ITR electrical data-50 Hz Scroll compressor and main fan for comparison only Indoor condensing units water-cooled Indoor condensing units air-cooledDrycooler only 35C 95F ambient, three-phase Drycooler only 35C 95F ambient, single phasePumps All Systems SummaryDesign Requirements SubmittalsAdvanced Microprocessor Control Standard Diagnostics AlarmsAudible Alarm Common AlarmCommunications Advanced Microprocessor Control with Graphics OptionalAlarms Hot Water Reheat Optional Infrared Humidifier StandardSteam Generating Humidifier Optional Electric Reheat StandardDirect Expansion Self-Contained Systems Two-way Water Regulating Valve with Bypass Standard Fan Speed Control FSC Head Pressure Control StandardLiebert Lee-Temp Head Pressure Control Optional Centrifugal Fan Condenser OptionalGlycool Self-Contained Systems Outdoor UnitTon Models Direct Expansion Split SystemsCentrifugal Fan Condensing Unit Optional DisconnectWater or Glycol-Cooled Condensing Unit Water or Glycol-Cooled Split SystemsOptional Quiet-Line Models Optional High Ambient ModelsTwo-way Chilled Water Valve Optional Flow Switch OptionalChilled Water Self-Contained Systems Chilled Water Coil Three-way Chilled Water Valve StandardComprehensive Monitoring Solutions Installation of Environmental Control UnitsField Quality Control Page That Ne tIti Ti n