Emerson ITR Alarms, Audible Alarm, Common Alarm, Remote Monitoring, Analog Inputs, Diagnostics

Page 62

Electrical Data

Alarms

The microprocessor shall activate an audible and visual alarm in event of any of the following condi- tions:

High Temperature

Low Temperature

High Humidity

Low Humidity

Short Cycle

Compressor Overload (Optional)

Main Fan Overload (Optional)

Humidifier Problem

High Head Pressure

Change Filter

Loss of Air Flow

Low Suction Pressure

Loss of Power

Custom Alarm (#1 to #4)

Custom alarms are four customer accessible alarm inputs to be indicated on the front panel. Custom alarms can be identified with prepared (programmed) alarm labels for the following frequently used inputs:

Water Under Floor

Smoke Detected

Standby GC Pump On

Loss of Water Flow

Standby Unit On

User customized text can be entered for two of the four custom alarms. Each alarm (unit and custom) can be separately enabled or disabled, selected to activate the common alarm, and programmed for a time delay of 0 to 255 seconds.

Audible Alarm

The audible alarm shall annunciate any alarm that is enabled by the operator.

Common Alarm

A programmable common alarm shall be provided to interface user selected alarms with a remote alarm device.

Remote Monitoring

All alarms shall be communicated to the Liebert monitoring system with the following information: date and time of occurrence, unit number, and present temperature and humidity.

Analog Inputs

The system shall include four customer accessible analog inputs for sensors provided by others. The analog inputs shall accept a 4 to 20 mA signal. The user shall be able to change the input to 0 to 5 VDC or 0 to 10 VDC if desired. The gains for each analog input shall be programmable from the front panel. The analog inputs shall be able to be monitored from the front panel.

Diagnostics

The control system and electronic circuitry shall be provided with self-diagnostics to aid in trouble- shooting. The microcontroller board shall be diagnosed and reported as pass/not pass. Control inputs shall be indicated as on or off at the front monitor panel. Control outputs shall be able to be turned on or off from the front monitor panel without using jumpers or a service terminal. Each control output shall be indicated by an LED on a circuit board.

Data Collection

54

Image 62
Contents Liebert Challenger ITR Table i Product model information Split system configurationsTable iii Self-contained system configurations Table of Contents Refrigeration Systems AIR-COOLEDSYSTEM-STANDARD and Optional FeaturesGlycool SYSTEMS-STANDARD and Optional Features Optional EQUIPMENT-ALLSYSTEMSComprehensive Monitoring SYSTEMS-OPTIONAL Comprehensive Monitoring SOLUTIONS-OPTIONALSystem Data Dimensional Drawings Electrical Data Figures Page Page Humidity Control Temperature ControlAir Volume Air FiltrationEfficiency in Economic Terms Multiple Configurations to Fit a Variety of SpacesLiebert Challenger ITR Unit configurations Image is Illustrative only Control Type DiagnosticsControl Internal System ControlLogging AlarmsCustom Alarm Maximum of Four Graphical Displays-Advanced Graphic Control OnlyFan Section Cabinet and FrameElectrical Panel Infrared HumidifierCondensate Pump Remote Temperature/ Humidity SensorsDisconnect Switch-Locking Type Condensate pump capacityChilled Water System-Standard Features Chilled Water System-Optional FeaturesSplit Systems Refrigeration System Components-Standard FeaturesSelf-Contained Systems Air-Cooled, Self-Contained Systems-Standard Features Air-Cooled, Self-Contained Systems-Optional FeaturesCentrifugal Fan, Condensing Unit Air-Cooled Split Systems-Standard FeaturesAir-Cooled Split Systems-Optional Features Propeller Fan Condensing UnitWater/Glycol Self-Contained Systems-Standard Features Water/Glycol Split System-Standard FeaturesGlycol Pump Water/Glycol-Cooled, Split System-Optional FeaturesFactory Installed Non-Fused Disconnect Switch Glycool System-Standard Features GLYCOOL-Self-Contained Models OnlyQuiet-Line Drycoolers Glycol and GLYCOOL-Cooled-Optional EquipmentDrycooler Evaporator Coil Econ-O-Coil Three-way Glycool Control ValveSteam generating humidifier Adjustable Floor Stand Steam Generating HumidifierHigh External Static Blowers SCR ReheatHigh-Efficiency Filter High-Efficiency MotorsHot Water Reheat Smoke DetectorFirestat FirestatNetwork Monitoring Systems Stand-Alone Monitoring and Leak Detection SolutionsEnterprise Monitoring Systems Leak Detection Modules Discrete Output Interface CardLiebert Nform Liebert SiteScan WebLiebert SiteLink Environmental Discrete Outputs CardLeak Detection Temperature and Humidity RecorderUniversal Monitor Liebert Challenger ITR air-cooled data-60 Hz BR 067A BR 060EInfrared Humidifier Standard Fan Data Blower A12x9AT Liebert Challenger ITR air-cooled data-50 HzSystem Type Split Systems Evaporator Coil V-Frame, at Standard ConditionsCondenser Air 35C 95F Ambient Liebert Challenger ITR air-cooled data-50HzConnection Sizes Challenger ITR Unit Indoor Unit BR 071WG BR 060E Net Capacity Data Liebert Challenger ITR water cooled data, 60 HzSystem Type Self-Contained Split Systems Connection Sizes Remote Condensing Unit Water Regulating ValveWater Requirements Coaxial Condenser Liebert Challenger ITR water cooled data, 50 Hz BTU/HCapacity, kg/hr lb/hr Liebert Challenger ITR glycol cooled data, 60 Hz GlycoolIndoor Unit Steam Generating Humidifier OptionalLiebert Challenger ITR glycol cooled data, 50 Hz GlycoolDrycooler 35C 95F Ambient Glycol Pump 3-Phase kW hpSystem Type Glycol Cooled Liebert Challenger ITR chilled water data, 60 Hz Indoor Unit BR 102C Fan Data Blower A12x9ATLiebert Challenger ITR chilled water data, 50 Hz Indoor Unit BR 101CDimensional Drawings 50 Hz 60 Hz Unit Weight Models Lb. kgOptional Floor Stand Model Net Weight 60 Hz 50 Hz Lbs kg MC69W MC68W SL-11081 36-1/4Liebert Lee-Temp Receiver = 40 1016mm = 7-1/2 190mm Electrical Data Liebert Challenger ITR electrical data1-60 HzMotor Hp 2.2 kW Self-contained with SCR reheatMotor Hp 1.5 kW Electric Reheat Only Motor Hp 1.1 kWVoltage 208 230 460 575 60 Hz Scroll Compressor Scroll compressor and main fan for comparison purposes onlyOutdoor condensing units Main Fan Motor Hp 1.1 kWIndoor condensing units, water-cooled Outdoor condensing units-Quiet-LineIndoor condensing units, air-cooled Drycooler and pump package 95F 35C ambient Fan speed control condensersLiebert Lee-Temp condensers Voltage 208/230 460 575 GlycolLiebert Challenger ITR electrical data-50 Hz Scroll compressor and main fan for comparison only Indoor condensing units air-cooled Indoor condensing units water-cooled Pumps Drycooler only 35C 95F ambient, three-phase Drycooler only 35C 95F ambient, single phase Submittals SummaryDesign Requirements All SystemsAdvanced Microprocessor Control Standard Common Alarm AlarmsAudible Alarm DiagnosticsAdvanced Microprocessor Control with Graphics Optional CommunicationsAlarms Electric Reheat Standard Infrared Humidifier StandardSteam Generating Humidifier Optional Hot Water Reheat OptionalDirect Expansion Self-Contained Systems Centrifugal Fan Condenser Optional Fan Speed Control FSC Head Pressure Control StandardLiebert Lee-Temp Head Pressure Control Optional Two-way Water Regulating Valve with Bypass StandardOutdoor Unit Glycool Self-Contained SystemsOptional Disconnect Direct Expansion Split SystemsCentrifugal Fan Condensing Unit Ton ModelsOptional High Ambient Models Water or Glycol-Cooled Split SystemsOptional Quiet-Line Models Water or Glycol-Cooled Condensing UnitThree-way Chilled Water Valve Standard Flow Switch OptionalChilled Water Self-Contained Systems Chilled Water Coil Two-way Chilled Water Valve OptionalField Quality Control Comprehensive Monitoring SolutionsInstallation of Environmental Control Units Page Ti n Ne tIti That