Emerson ITR manual Water or Glycol-Cooled Split Systems, Optional Quiet-Line Models

Page 70

Electrical Data

Propeller Fan Condensing Unit

The condenser coil shall be constructed of copper tubes and aluminum fins with a direct drive propel- ler type fan and shall include a scroll compressor, high pressure switch, Liebert Lee-Temp receiver, head pressure control valve, and liquid line solenoid valve. All components shall be factory assembled, charged with refrigerant and sealed. No brazing, dehydration, or charging shall be required. Con- densing unit shall be designed for 95°F (35°C) ambient and be capable of operation to -30°F (-34.4°C).

A hot gas bypass circuit shall be provided to reduce compressor cycling and improve operation under low load conditions.

(Optional) Quiet-Line Models

The condensing unit shall be designed to operate at a sound level less then 58 dBa.

(Optional) High Ambient Models

The outdoor condensing unit shall be designed for design ambient operation of 105°F (40.6°C).

5-Ton Models

Condensing unit must be hard piped with the evaporator. Sweat adapters are shipped loose with all evaporators for use on the 5 ton condensing units.

2.3.1Water or Glycol-Cooled Split Systems

Water or Glycol-Cooled Condensing Unit

The water/glycol condensing unit shall be equipped with a coaxial condenser having a total system pressure drop of _____ ft. of water (kPa) and a flow rate of _____ GPM (l/s) with _____ °F (°C) entering water/glycol temperature.

Components shall include scroll compressor and high-pressure switch. The condensing unit shall be factory charged with R-22 refrigerant.

The condenser circuit shall be pre-piped with a [(2-way) (three-way)] regulating valve which is head- pressure actuated.

The condenser water/glycol circuit shall be designed for a static operating pressure of [(150 PSI (1034 kPa)) (350 PSI (2413 kPa))].

A hot gas bypass circuit shall be provided to reduce compressor cycling and improve operation under low load conditions.

A 70/30 Cu-Ni Econ-O-Coil must be specified whenever a GLYCOOL or Dual Cooling Source system is applied to a cooling tower loop or other open water system.

(Optional) Disconnect

Factory installed non-fused disconnect switch allows unit to be turned off for maintenance.

5-Ton Models

Condensing unit must be hard piped with the evaporator. Sweat adapters are shipped loose with all evaporators for use on the 5 ton condensing units.

Propeller Fan Drycooler (Standard)

The Liebert manufactured drycooler shall be the low profile, slow speed, direct drive propeller fan type. The drycooler shall be constructed of aluminum and contain a copper tube aluminum fin coil with an integral electric control panel. The drycooler shall be designed for _____ °F (°C) ambient.

Centrifugal Fan Drycooler (Optional)

The system shall be supplied with a centrifugal fan drycooler (LCD). The drycooler shall be con- structed of galvanized steel with a copper tube, aluminum fin coil. The heavy duty fan shall be the centrifugal type, double width, double inlet. The 1750 RPM (1450 RPM @ 50 Hz) fan motor shall be mounted on an adjustable base, and equipped with an adjustable motor pulley. A three-way control valve and thermostat shall maintain the desired fluid temperature. Electrical controls shall be in a rain tight enclosure. The system shall be designed for _____ °F (°C) ambient. The drycooler shall have a _____ Volt, 3 phase, _____ Hz power supply.

62

Image 70
Contents Liebert Challenger ITR Table iii Self-contained system configurations Split system configurationsTable i Product model information Table of Contents Refrigeration Systems AIR-COOLEDSYSTEM-STANDARD and Optional FeaturesGlycool SYSTEMS-STANDARD and Optional Features Optional EQUIPMENT-ALLSYSTEMSSystem Data Dimensional Drawings Electrical Data Comprehensive Monitoring SOLUTIONS-OPTIONALComprehensive Monitoring SYSTEMS-OPTIONAL Figures Page Page Humidity Control Temperature ControlAir Volume Air FiltrationLiebert Challenger ITR Multiple Configurations to Fit a Variety of SpacesEfficiency in Economic Terms Unit configurations Image is Illustrative only Control Type DiagnosticsControl Internal System ControlLogging AlarmsCustom Alarm Maximum of Four Graphical Displays-Advanced Graphic Control OnlyFan Section Cabinet and FrameElectrical Panel Infrared HumidifierCondensate Pump Remote Temperature/ Humidity SensorsDisconnect Switch-Locking Type Condensate pump capacityChilled Water System-Standard Features Chilled Water System-Optional FeaturesSelf-Contained Systems Refrigeration System Components-Standard FeaturesSplit Systems Air-Cooled, Self-Contained Systems-Standard Features Air-Cooled, Self-Contained Systems-Optional FeaturesCentrifugal Fan, Condensing Unit Air-Cooled Split Systems-Standard FeaturesAir-Cooled Split Systems-Optional Features Propeller Fan Condensing UnitWater/Glycol Self-Contained Systems-Standard Features Water/Glycol Split System-Standard FeaturesFactory Installed Non-Fused Disconnect Switch Water/Glycol-Cooled, Split System-Optional FeaturesGlycol Pump Glycool System-Standard Features GLYCOOL-Self-Contained Models OnlyQuiet-Line Drycoolers Glycol and GLYCOOL-Cooled-Optional EquipmentDrycooler Evaporator Coil Econ-O-Coil Three-way Glycool Control ValveSteam generating humidifier Adjustable Floor Stand Steam Generating HumidifierHigh External Static Blowers SCR ReheatHigh-Efficiency Filter High-Efficiency MotorsHot Water Reheat Smoke DetectorFirestat FirestatEnterprise Monitoring Systems Stand-Alone Monitoring and Leak Detection SolutionsNetwork Monitoring Systems Leak Detection Modules Discrete Output Interface CardLiebert Nform Liebert SiteScan WebLiebert SiteLink Environmental Discrete Outputs CardUniversal Monitor Temperature and Humidity RecorderLeak Detection Liebert Challenger ITR air-cooled data-60 Hz BR 067A BR 060EInfrared Humidifier Standard Fan Data Blower A12x9AT Liebert Challenger ITR air-cooled data-50 HzSystem Type Split Systems Evaporator Coil V-Frame, at Standard ConditionsConnection Sizes Challenger ITR Unit Liebert Challenger ITR air-cooled data-50HzCondenser Air 35C 95F Ambient System Type Self-Contained Split Systems Liebert Challenger ITR water cooled data, 60 HzIndoor Unit BR 071WG BR 060E Net Capacity Data Water Requirements Coaxial Condenser Water Regulating ValveConnection Sizes Remote Condensing Unit Liebert Challenger ITR water cooled data, 50 Hz BTU/HCapacity, kg/hr lb/hr Liebert Challenger ITR glycol cooled data, 60 Hz GlycoolIndoor Unit Steam Generating Humidifier OptionalLiebert Challenger ITR glycol cooled data, 50 Hz GlycoolSystem Type Glycol Cooled Glycol Pump 3-Phase kW hpDrycooler 35C 95F Ambient Liebert Challenger ITR chilled water data, 60 Hz Indoor Unit BR 102C Fan Data Blower A12x9ATLiebert Challenger ITR chilled water data, 50 Hz Indoor Unit BR 101CDimensional Drawings 50 Hz 60 Hz Unit Weight Models Lb. kgOptional Floor Stand Model Net Weight 60 Hz 50 Hz Lbs kg MC69W MC68W SL-11081 36-1/4Liebert Lee-Temp Receiver = 40 1016mm = 7-1/2 190mm Electrical Data Liebert Challenger ITR electrical data1-60 HzMotor Hp 2.2 kW Self-contained with SCR reheatMotor Hp 1.5 kW Electric Reheat Only Motor Hp 1.1 kWVoltage 208 230 460 575 60 Hz Scroll Compressor Scroll compressor and main fan for comparison purposes onlyOutdoor condensing units Main Fan Motor Hp 1.1 kWIndoor condensing units, air-cooled Outdoor condensing units-Quiet-LineIndoor condensing units, water-cooled Drycooler and pump package 95F 35C ambient Fan speed control condensersLiebert Lee-Temp condensers Voltage 208/230 460 575 GlycolLiebert Challenger ITR electrical data-50 Hz Scroll compressor and main fan for comparison only Indoor condensing units air-cooled Indoor condensing units water-cooledDrycooler only 35C 95F ambient, single phase Drycooler only 35C 95F ambient, three-phasePumps Submittals SummaryDesign Requirements All SystemsAdvanced Microprocessor Control Standard Common Alarm AlarmsAudible Alarm DiagnosticsAdvanced Microprocessor Control with Graphics Optional CommunicationsAlarms Electric Reheat Standard Infrared Humidifier StandardSteam Generating Humidifier Optional Hot Water Reheat OptionalDirect Expansion Self-Contained Systems Centrifugal Fan Condenser Optional Fan Speed Control FSC Head Pressure Control StandardLiebert Lee-Temp Head Pressure Control Optional Two-way Water Regulating Valve with Bypass StandardOutdoor Unit Glycool Self-Contained SystemsOptional Disconnect Direct Expansion Split SystemsCentrifugal Fan Condensing Unit Ton ModelsOptional High Ambient Models Water or Glycol-Cooled Split SystemsOptional Quiet-Line Models Water or Glycol-Cooled Condensing UnitThree-way Chilled Water Valve Standard Flow Switch OptionalChilled Water Self-Contained Systems Chilled Water Coil Two-way Chilled Water Valve OptionalInstallation of Environmental Control Units Comprehensive Monitoring SolutionsField Quality Control Page Ti n Ne tIti That