Emerson ITR manual Advanced Microprocessor Control with Graphics Optional, Communications

Page 63

Electrical Data

The control system shall maintain accumulative operating hours of compressor, reheat, humidifier, fan motor, and Econ-O-Coil. The ten most recent alarms shall also be retained.

Communications

The microprocessor shall be compatible with all Liebert remote monitoring and control devices.

2.1.5Advanced Microprocessor Control with Graphics (Optional)

The optional Advanced control processor shall be microprocessor based with a front monitor dot matrix display panel and control keys for user inputs. The controls shall be menu driven with on- screen prompts for easy user operation. The system shall allow user review and programming of tem- perature and humidity setpoints, alarm parameters, and setup selections including choice of control type. A password shall be required to make system changes. For all user selections, the range of acceptable input (temperature, humidity, or time delay) shall be displayed on the monitor screen. The system shall provide monitoring of room conditions, operational status in % of each function, compo- nent run times, date and time, and four analog inputs from sensors provided by others.

Control

The control system shall allow programming of the following room conditions:

Temperature Setpoint 65 to 85°F (18-29°C)

Temperature Sensitivity +1 to +9.9°F (0.6 to 5.6°C) in 0.1° increments

Humidity Setpoint 20 to 80% RH

Humidity Sensitivity +1 to +30% RH

All setpoints shall be adjustable from the individual unit front monitor panel.

Temperature and Humidity Sensors shall be capable of being calibrated using the front monitor panel controls to coordinate with other temperature and humidity sensors in the room.

Predictive Humidity Control

The microprocessor shall calculate the moisture content in the room and prevent unnecessary humid- ification and dehumidification cycles by responding to changes in dew point temperature.

Compressor Short-Cycle Control

The control system shall include a program to prevent compressor short-cycling.

System Auto-Restart

For start-up after power failure, the system shall provide automatic restart with a programmable (up to 9.9 minutes in 6-second increments) time delay. Programming can be performed either at the unit or from the central site monitoring system.

Sequential Load Activation

During start-up, or after power failure, the microprocessor shall sequence operational load activation to minimize inrush current. Systems allowing multiple loads to start simultaneously are unaccept- able.

Chilled Water/Hot Water/Econ-O-Coil Flush Cycles

Chilled water, hot water, and Econ-O-Cool coils shall be automatically flushed to prevent the buildup of contaminants. Systems without this feature shall include the necessary devices to bypass fluid into the coil on a programmed basis.

Front Monitor Display Panel

The microprocessor shall provide a front monitor 240 x 120 dot matrix display panel with adjustable backlighting. This display (along with five front mounted control keys) shall be the only operator interface required to obtain all available system information such as room conditions, operational sta- tus, graphical data, alarms, control and alarm setpoints, and all user selections including alarm delays, sensor calibration, DIP switch selections, and diagnostics. All indicators shall be in language form. No symbols or codes shall be acceptable.

55

Image 63
Contents Liebert Challenger ITR Split system configurations Table iii Self-contained system configurationsTable i Product model information Table of Contents Optional EQUIPMENT-ALLSYSTEMS AIR-COOLEDSYSTEM-STANDARD and Optional FeaturesGlycool SYSTEMS-STANDARD and Optional Features Refrigeration SystemsComprehensive Monitoring SOLUTIONS-OPTIONAL System Data Dimensional Drawings Electrical DataComprehensive Monitoring SYSTEMS-OPTIONAL Figures Page Page Air Filtration Temperature ControlAir Volume Humidity ControlMultiple Configurations to Fit a Variety of Spaces Liebert Challenger ITREfficiency in Economic Terms Unit configurations Image is Illustrative only Internal System Control DiagnosticsControl Control TypeGraphical Displays-Advanced Graphic Control Only AlarmsCustom Alarm Maximum of Four LoggingInfrared Humidifier Cabinet and FrameElectrical Panel Fan SectionCondensate pump capacity Remote Temperature/ Humidity SensorsDisconnect Switch-Locking Type Condensate PumpChilled Water System-Optional Features Chilled Water System-Standard FeaturesRefrigeration System Components-Standard Features Self-Contained SystemsSplit Systems Air-Cooled, Self-Contained Systems-Optional Features Air-Cooled, Self-Contained Systems-Standard FeaturesPropeller Fan Condensing Unit Air-Cooled Split Systems-Standard FeaturesAir-Cooled Split Systems-Optional Features Centrifugal Fan, Condensing UnitWater/Glycol Split System-Standard Features Water/Glycol Self-Contained Systems-Standard FeaturesWater/Glycol-Cooled, Split System-Optional Features Factory Installed Non-Fused Disconnect SwitchGlycol Pump GLYCOOL-Self-Contained Models Only Glycool System-Standard FeaturesEvaporator Coil Econ-O-Coil Three-way Glycool Control Valve Glycol and GLYCOOL-Cooled-Optional EquipmentDrycooler Quiet-Line DrycoolersSteam Generating Humidifier Steam generating humidifier Adjustable Floor StandHigh-Efficiency Motors SCR ReheatHigh-Efficiency Filter High External Static BlowersFirestat Smoke DetectorFirestat Hot Water ReheatStand-Alone Monitoring and Leak Detection Solutions Enterprise Monitoring SystemsNetwork Monitoring Systems Discrete Output Interface Card Leak Detection ModulesEnvironmental Discrete Outputs Card Liebert SiteScan WebLiebert SiteLink Liebert NformTemperature and Humidity Recorder Universal MonitorLeak Detection BR 067A BR 060E Liebert Challenger ITR air-cooled data-60 HzInfrared Humidifier Standard Evaporator Coil V-Frame, at Standard Conditions Liebert Challenger ITR air-cooled data-50 HzSystem Type Split Systems Fan Data Blower A12x9ATLiebert Challenger ITR air-cooled data-50Hz Connection Sizes Challenger ITR UnitCondenser Air 35C 95F Ambient Liebert Challenger ITR water cooled data, 60 Hz System Type Self-Contained Split SystemsIndoor Unit BR 071WG BR 060E Net Capacity Data Water Regulating Valve Water Requirements Coaxial CondenserConnection Sizes Remote Condensing Unit BTU/H Liebert Challenger ITR water cooled data, 50 HzCapacity, kg/hr lb/hr Glycool Liebert Challenger ITR glycol cooled data, 60 HzSteam Generating Humidifier Optional Indoor UnitGlycool Liebert Challenger ITR glycol cooled data, 50 HzGlycol Pump 3-Phase kW hp System Type Glycol CooledDrycooler 35C 95F Ambient Indoor Unit BR 102C Fan Data Blower A12x9AT Liebert Challenger ITR chilled water data, 60 HzIndoor Unit BR 101C Liebert Challenger ITR chilled water data, 50 Hz50 Hz 60 Hz Unit Weight Models Lb. kg Dimensional DrawingsOptional Floor Stand Model Net Weight 60 Hz 50 Hz Lbs kg MC69W MC68W 36-1/4 SL-11081Liebert Lee-Temp Receiver = 40 1016mm = 7-1/2 190mm Liebert Challenger ITR electrical data1-60 Hz Electrical DataElectric Reheat Only Motor Hp 1.1 kW Self-contained with SCR reheatMotor Hp 1.5 kW Motor Hp 2.2 kWMain Fan Motor Hp 1.1 kW Scroll compressor and main fan for comparison purposes onlyOutdoor condensing units Voltage 208 230 460 575 60 Hz Scroll CompressorOutdoor condensing units-Quiet-Line Indoor condensing units, air-cooledIndoor condensing units, water-cooled Voltage 208/230 460 575 Glycol Fan speed control condensersLiebert Lee-Temp condensers Drycooler and pump package 95F 35C ambientLiebert Challenger ITR electrical data-50 Hz Scroll compressor and main fan for comparison only Indoor condensing units water-cooled Indoor condensing units air-cooledDrycooler only 35C 95F ambient, three-phase Drycooler only 35C 95F ambient, single phasePumps All Systems Summary Design Requirements SubmittalsAdvanced Microprocessor Control Standard Diagnostics AlarmsAudible Alarm Common AlarmCommunications Advanced Microprocessor Control with Graphics OptionalAlarms Hot Water Reheat Optional Infrared Humidifier StandardSteam Generating Humidifier Optional Electric Reheat StandardDirect Expansion Self-Contained Systems Two-way Water Regulating Valve with Bypass Standard Fan Speed Control FSC Head Pressure Control StandardLiebert Lee-Temp Head Pressure Control Optional Centrifugal Fan Condenser OptionalGlycool Self-Contained Systems Outdoor UnitTon Models Direct Expansion Split SystemsCentrifugal Fan Condensing Unit Optional DisconnectWater or Glycol-Cooled Condensing Unit Water or Glycol-Cooled Split SystemsOptional Quiet-Line Models Optional High Ambient ModelsTwo-way Chilled Water Valve Optional Flow Switch OptionalChilled Water Self-Contained Systems Chilled Water Coil Three-way Chilled Water Valve StandardComprehensive Monitoring Solutions Installation of Environmental Control UnitsField Quality Control Page That Ne tIti Ti n