Emerson ITR manual Chilled Water Self-Contained Systems Chilled Water Coil, Flow Switch Optional

Page 71

Electrical Data

Single Glycol Pump Package (Standard)

This system shall be provided with a centrifugal pump mounted in a weatherproof and vented enclo- sure. The pump shall be rated for GPM (l/s) at _____ ft. of head (kPa), and operate on _____ Volt,

3 phase, _____ Hz.

Dual Glycol Pump Package (Optional)

The dual pump package shall include pumps, enclosure, and field mounted flow switch. The pumps shall be wired to the drycooler control box which includes a lead/lag switch for the pumps. The standby pump shall automatically start upon failure of the lead pump. Each pump shall be rated for

_____ GPM (l/s) at _____ feet of head (kPa).

2.4Chilled Water Self-Contained Systems Chilled Water Coil

The cooling coil shall have a minimum of _____ sq. ft. (sq. m) face area, _____ rows deep. The coil shall

be controlled by a modulating control valve. The chilled water coil shall be designed for closed-loop applications using properly maintained water. It shall be configured as a V-frame and be constructed of copper tubes and aluminum fins and have a maximum face velocity of _____ ft. per minute (m/s) at

_____ CFM (CMH). The water circuit shall be designed to distribute water into the entire coil face

area. The coil shall be supplied with _____ °F (°C) entering water temperature, with a _____ °F (°C)

temperature rise. The coil shall be supplied with _____ GPM (m/s) of chilled water and the pressure

drop shall not exceed _____ PSI (kPa). The coil assembly shall be mounted in a stainless steel conden-

sate drain pan.

Three-way Chilled Water Valve (Standard)

The water circuit shall include a three-way modulating valve. The microprocessor control shall posi- tion the valve in response to room conditions. Cooling capacity will be controlled by bypassing chilled water around the coil.

Two-way Chilled Water Valve (Optional)

The water circuit shall include a two-way modulating valve. The microprocessor control shall position the valve in response to room conditions. The minimum close-off pressure of the valve/actuator assem- bly shall be _____ PSI (kPa).

Design Pressure

The chilled water circuit shall be designed for a pressure of [(150 PSI (1034 kPa)) (400 PSI (2758 kPa))].

Flow Switch (Optional)

The flow switch shall activate the alarm system should the chilled water supply be interrupted. The switch shall be factory mounted and wired.

63

Image 71
Contents Liebert Challenger ITR Table i Product model information Split system configurationsTable iii Self-contained system configurations Table of Contents Optional EQUIPMENT-ALLSYSTEMS AIR-COOLEDSYSTEM-STANDARD and Optional FeaturesGlycool SYSTEMS-STANDARD and Optional Features Refrigeration SystemsComprehensive Monitoring SYSTEMS-OPTIONAL Comprehensive Monitoring SOLUTIONS-OPTIONALSystem Data Dimensional Drawings Electrical Data Figures Page Page Air Filtration Temperature ControlAir Volume Humidity ControlEfficiency in Economic Terms Multiple Configurations to Fit a Variety of SpacesLiebert Challenger ITR Unit configurations Image is Illustrative only Internal System Control DiagnosticsControl Control TypeGraphical Displays-Advanced Graphic Control Only AlarmsCustom Alarm Maximum of Four LoggingInfrared Humidifier Cabinet and FrameElectrical Panel Fan SectionCondensate pump capacity Remote Temperature/ Humidity SensorsDisconnect Switch-Locking Type Condensate PumpChilled Water System-Optional Features Chilled Water System-Standard FeaturesSplit Systems Refrigeration System Components-Standard FeaturesSelf-Contained Systems Air-Cooled, Self-Contained Systems-Optional Features Air-Cooled, Self-Contained Systems-Standard FeaturesPropeller Fan Condensing Unit Air-Cooled Split Systems-Standard FeaturesAir-Cooled Split Systems-Optional Features Centrifugal Fan, Condensing UnitWater/Glycol Split System-Standard Features Water/Glycol Self-Contained Systems-Standard FeaturesGlycol Pump Water/Glycol-Cooled, Split System-Optional FeaturesFactory Installed Non-Fused Disconnect Switch GLYCOOL-Self-Contained Models Only Glycool System-Standard FeaturesEvaporator Coil Econ-O-Coil Three-way Glycool Control Valve Glycol and GLYCOOL-Cooled-Optional EquipmentDrycooler Quiet-Line DrycoolersSteam Generating Humidifier Steam generating humidifier Adjustable Floor StandHigh-Efficiency Motors SCR ReheatHigh-Efficiency Filter High External Static BlowersFirestat Smoke DetectorFirestat Hot Water ReheatNetwork Monitoring Systems Stand-Alone Monitoring and Leak Detection SolutionsEnterprise Monitoring Systems Discrete Output Interface Card Leak Detection ModulesEnvironmental Discrete Outputs Card Liebert SiteScan WebLiebert SiteLink Liebert NformLeak Detection Temperature and Humidity RecorderUniversal Monitor BR 067A BR 060E Liebert Challenger ITR air-cooled data-60 HzInfrared Humidifier Standard Evaporator Coil V-Frame, at Standard Conditions Liebert Challenger ITR air-cooled data-50 HzSystem Type Split Systems Fan Data Blower A12x9ATCondenser Air 35C 95F Ambient Liebert Challenger ITR air-cooled data-50HzConnection Sizes Challenger ITR Unit Indoor Unit BR 071WG BR 060E Net Capacity Data Liebert Challenger ITR water cooled data, 60 HzSystem Type Self-Contained Split Systems Connection Sizes Remote Condensing Unit Water Regulating ValveWater Requirements Coaxial Condenser BTU/H Liebert Challenger ITR water cooled data, 50 HzCapacity, kg/hr lb/hr Glycool Liebert Challenger ITR glycol cooled data, 60 HzSteam Generating Humidifier Optional Indoor UnitGlycool Liebert Challenger ITR glycol cooled data, 50 HzDrycooler 35C 95F Ambient Glycol Pump 3-Phase kW hpSystem Type Glycol Cooled Indoor Unit BR 102C Fan Data Blower A12x9AT Liebert Challenger ITR chilled water data, 60 HzIndoor Unit BR 101C Liebert Challenger ITR chilled water data, 50 Hz50 Hz 60 Hz Unit Weight Models Lb. kg Dimensional DrawingsOptional Floor Stand Model Net Weight 60 Hz 50 Hz Lbs kg MC69W MC68W 36-1/4 SL-11081Liebert Lee-Temp Receiver = 40 1016mm = 7-1/2 190mm Liebert Challenger ITR electrical data1-60 Hz Electrical DataElectric Reheat Only Motor Hp 1.1 kW Self-contained with SCR reheatMotor Hp 1.5 kW Motor Hp 2.2 kWMain Fan Motor Hp 1.1 kW Scroll compressor and main fan for comparison purposes onlyOutdoor condensing units Voltage 208 230 460 575 60 Hz Scroll CompressorIndoor condensing units, water-cooled Outdoor condensing units-Quiet-LineIndoor condensing units, air-cooled Voltage 208/230 460 575 Glycol Fan speed control condensersLiebert Lee-Temp condensers Drycooler and pump package 95F 35C ambientLiebert Challenger ITR electrical data-50 Hz Scroll compressor and main fan for comparison only Indoor condensing units water-cooled Indoor condensing units air-cooledPumps Drycooler only 35C 95F ambient, three-phaseDrycooler only 35C 95F ambient, single phase All Systems SummaryDesign Requirements SubmittalsAdvanced Microprocessor Control Standard Diagnostics AlarmsAudible Alarm Common AlarmCommunications Advanced Microprocessor Control with Graphics OptionalAlarms Hot Water Reheat Optional Infrared Humidifier StandardSteam Generating Humidifier Optional Electric Reheat StandardDirect Expansion Self-Contained Systems Two-way Water Regulating Valve with Bypass Standard Fan Speed Control FSC Head Pressure Control StandardLiebert Lee-Temp Head Pressure Control Optional Centrifugal Fan Condenser OptionalGlycool Self-Contained Systems Outdoor UnitTon Models Direct Expansion Split SystemsCentrifugal Fan Condensing Unit Optional DisconnectWater or Glycol-Cooled Condensing Unit Water or Glycol-Cooled Split SystemsOptional Quiet-Line Models Optional High Ambient ModelsTwo-way Chilled Water Valve Optional Flow Switch OptionalChilled Water Self-Contained Systems Chilled Water Coil Three-way Chilled Water Valve StandardField Quality Control Comprehensive Monitoring SolutionsInstallation of Environmental Control Units Page That Ne tIti Ti n