Emerson ITR manual Advanced Microprocessor Control Standard

Page 61

Electrical Data

2.1.4Advanced Microprocessor Control (Standard)

The Advanced control processor shall be microprocessor based with a front monitor LCD display panel and control keys for user inputs. The controls shall be menu driven with on-screen prompts for easy user operation. The system shall allow user review and programming of temperature and humid- ity setpoints, alarm parameters, and setup selections including choice of control type. A password shall be required to make system changes. For all user selections, the range of acceptable input (tem- perature, humidity, or time delay) shall be displayed on the monitor screen. The system shall provide monitoring of room conditions, operational status in % of each function, component run times, date and time, and four analog inputs from sensors provided by others.

Control

The control system shall allow programming of the following room conditions:

Temperature Setpoint 65 to 85°F (18-29°C)

Temperature Sensitivity +1 to +9.9°F (0.6 to 5.6°C) in 0.1° increments

Humidity Setpoint 20 to 80% RH

Humidity Sensitivity +1 to +30% RH

All setpoints shall be adjustable from the individual unit front monitor panel. The microprocessor can be set within these ranges, however, the unit may not be able to control to extreme combinations of temperature and humidity.

Temperature and Humidity Sensors shall be capable of being calibrated using the front monitor panel controls to coordinate with other temperature and humidity sensors in the room.

Predictive Humidity Control

The microprocessor shall calculate the moisture content in the room and prevent unnecessary humid- ification and dehumidification cycles by responding to changes in dew point temperature.

Compressor Short-Cycle Control

The control system shall include a program to prevent compressor short-cycling.

System Auto-Restart

For start-up after power failure, the system shall provide automatic restart with a programmable (up to 9.9 minutes in 6-second increments) time delay. Programming can be performed either at the unit or from the central site monitoring system.

Sequential Load Activation

During start-up, or after power failure, the microprocessor shall sequence operational load activation to minimize inrush current. Systems allowing multiple loads to start simultaneously are unaccept- able.

Chilled Water/Hot Water/Econ-O-Coil Flush Cycles

Chilled water, hot water, and Econ-O-Cool coils (if unit is so equipped) shall be automatically flushed to prevent the buildup of contaminants. Systems without this feature shall include the necessary devices to bypass fluid into the coil on a programmed basis.

Front Monitor Display Panel

The microprocessor shall provide a front monitor LCD backlit display panel with 4 rows of 20 charac- ters with adjustable contrast. This display (along with five front mounted control keys) shall be the only operator interface required to obtain all available system information such as room conditions, operational status, alarms, control and alarm setpoints, and all user selections including alarm delays, sensor calibration, DIP switch selections, and diagnostics. All indicators shall be in language form. No symbols or codes shall be acceptable.

53

Image 61
Contents Liebert Challenger ITR Table iii Self-contained system configurations Split system configurationsTable i Product model information Table of Contents Glycool SYSTEMS-STANDARD and Optional Features AIR-COOLEDSYSTEM-STANDARD and Optional FeaturesRefrigeration Systems Optional EQUIPMENT-ALLSYSTEMSSystem Data Dimensional Drawings Electrical Data Comprehensive Monitoring SOLUTIONS-OPTIONALComprehensive Monitoring SYSTEMS-OPTIONAL Figures Page Page Air Volume Temperature ControlHumidity Control Air FiltrationLiebert Challenger ITR Multiple Configurations to Fit a Variety of SpacesEfficiency in Economic Terms Unit configurations Image is Illustrative only Control DiagnosticsControl Type Internal System ControlCustom Alarm Maximum of Four AlarmsLogging Graphical Displays-Advanced Graphic Control OnlyElectrical Panel Cabinet and FrameFan Section Infrared HumidifierDisconnect Switch-Locking Type Remote Temperature/ Humidity SensorsCondensate Pump Condensate pump capacityChilled Water System-Optional Features Chilled Water System-Standard FeaturesSelf-Contained Systems Refrigeration System Components-Standard FeaturesSplit Systems Air-Cooled, Self-Contained Systems-Optional Features Air-Cooled, Self-Contained Systems-Standard FeaturesAir-Cooled Split Systems-Optional Features Air-Cooled Split Systems-Standard FeaturesCentrifugal Fan, Condensing Unit Propeller Fan Condensing UnitWater/Glycol Split System-Standard Features Water/Glycol Self-Contained Systems-Standard FeaturesFactory Installed Non-Fused Disconnect Switch Water/Glycol-Cooled, Split System-Optional FeaturesGlycol Pump GLYCOOL-Self-Contained Models Only Glycool System-Standard FeaturesDrycooler Glycol and GLYCOOL-Cooled-Optional EquipmentQuiet-Line Drycoolers Evaporator Coil Econ-O-Coil Three-way Glycool Control ValveSteam Generating Humidifier Steam generating humidifier Adjustable Floor StandHigh-Efficiency Filter SCR ReheatHigh External Static Blowers High-Efficiency MotorsFirestat Smoke DetectorHot Water Reheat FirestatEnterprise Monitoring Systems Stand-Alone Monitoring and Leak Detection SolutionsNetwork Monitoring Systems Discrete Output Interface Card Leak Detection ModulesLiebert SiteLink Liebert SiteScan WebLiebert Nform Environmental Discrete Outputs CardUniversal Monitor Temperature and Humidity RecorderLeak Detection BR 067A BR 060E Liebert Challenger ITR air-cooled data-60 HzInfrared Humidifier Standard System Type Split Systems Liebert Challenger ITR air-cooled data-50 HzFan Data Blower A12x9AT Evaporator Coil V-Frame, at Standard ConditionsConnection Sizes Challenger ITR Unit Liebert Challenger ITR air-cooled data-50HzCondenser Air 35C 95F Ambient System Type Self-Contained Split Systems Liebert Challenger ITR water cooled data, 60 HzIndoor Unit BR 071WG BR 060E Net Capacity Data Water Requirements Coaxial Condenser Water Regulating ValveConnection Sizes Remote Condensing Unit BTU/H Liebert Challenger ITR water cooled data, 50 HzCapacity, kg/hr lb/hr Glycool Liebert Challenger ITR glycol cooled data, 60 HzSteam Generating Humidifier Optional Indoor UnitGlycool Liebert Challenger ITR glycol cooled data, 50 HzSystem Type Glycol Cooled Glycol Pump 3-Phase kW hpDrycooler 35C 95F Ambient Indoor Unit BR 102C Fan Data Blower A12x9AT Liebert Challenger ITR chilled water data, 60 HzIndoor Unit BR 101C Liebert Challenger ITR chilled water data, 50 Hz50 Hz 60 Hz Unit Weight Models Lb. kg Dimensional DrawingsOptional Floor Stand Model Net Weight 60 Hz 50 Hz Lbs kg MC69W MC68W 36-1/4 SL-11081Liebert Lee-Temp Receiver = 40 1016mm = 7-1/2 190mm Liebert Challenger ITR electrical data1-60 Hz Electrical DataMotor Hp 1.5 kW Self-contained with SCR reheatMotor Hp 2.2 kW Electric Reheat Only Motor Hp 1.1 kWOutdoor condensing units Scroll compressor and main fan for comparison purposes onlyVoltage 208 230 460 575 60 Hz Scroll Compressor Main Fan Motor Hp 1.1 kWIndoor condensing units, air-cooled Outdoor condensing units-Quiet-LineIndoor condensing units, water-cooled Liebert Lee-Temp condensers Fan speed control condensersDrycooler and pump package 95F 35C ambient Voltage 208/230 460 575 GlycolLiebert Challenger ITR electrical data-50 Hz Scroll compressor and main fan for comparison only Indoor condensing units water-cooled Indoor condensing units air-cooledDrycooler only 35C 95F ambient, single phase Drycooler only 35C 95F ambient, three-phasePumps Design Requirements SummarySubmittals All SystemsAdvanced Microprocessor Control Standard Audible Alarm AlarmsCommon Alarm DiagnosticsCommunications Advanced Microprocessor Control with Graphics OptionalAlarms Steam Generating Humidifier Optional Infrared Humidifier StandardElectric Reheat Standard Hot Water Reheat OptionalDirect Expansion Self-Contained Systems Liebert Lee-Temp Head Pressure Control Optional Fan Speed Control FSC Head Pressure Control StandardCentrifugal Fan Condenser Optional Two-way Water Regulating Valve with Bypass StandardGlycool Self-Contained Systems Outdoor UnitCentrifugal Fan Condensing Unit Direct Expansion Split SystemsOptional Disconnect Ton ModelsOptional Quiet-Line Models Water or Glycol-Cooled Split SystemsOptional High Ambient Models Water or Glycol-Cooled Condensing UnitChilled Water Self-Contained Systems Chilled Water Coil Flow Switch OptionalThree-way Chilled Water Valve Standard Two-way Chilled Water Valve OptionalInstallation of Environmental Control Units Comprehensive Monitoring SolutionsField Quality Control Page Iti Ne tTi n That