Chapter 1 | Introduction |
1.1.6 General Specifications
Table
|
|
| Output at | Output at |
Configuration | Rectifiers | Distribution | 220V AC | 110V AC |
|
|
|
|
|
Small Systems | 2 | 32A | 13.3A | |
|
| Block |
|
|
|
|
|
|
|
Medium Systems | 3 | 64A | 26.6A | |
|
| Block |
|
|
|
| 4- position 1RU DC |
|
|
|
| Distribution Shelf |
|
|
|
|
|
|
|
Large Systems | 4 | 96A | 40A | |
|
| Block |
|
|
|
| 4- position 1RU DC |
|
|
|
| Distribution Shelf |
|
|
|
|
|
|
|
1.1.6 General Specifications
Table
Table
From | To | Wire Gauge | Ampacity |
|
|
|
|
System Shelf | 1U DC Distribution | 4 x 6AWG (16mm²) | 96A (max) |
| Shelf |
| |
|
|
| |
|
|
|
|
Circuit Breakers | Load | 10 - 8AWG | 30A (max) |
|
| (6mm² - 10mm²) |
|
|
|
|
|
GMT Fuse Block | Load | 16 - 14AWG | 15A (max) |
|
| (1.5mm² - 2.5mm²) |
|
|
|
|
|
AC Service Panel | System Shelf | 3 conductor 14AWG | 9.1A x (4) inputs |
|
| (2.5mm²) per AC input | <37A Total |
|
|
| |
|
|
|
|
Table
Table
Electrical | Value |
|
|
Input Voltage | (A) |
| (B) |
|
|
Input Frequency | |
|
|
Transient Response | +/- 4%, recovery time 2ms |
|
|
Load Sharing | +/- 5% of nominal current |
|
|
Table
Cisco AC/DC Power System User Guide, R1.0
May 2006 |