Chapter 2 System Installation
2.2.3 Install the Ground Cable
Figure 2-10 Installing the System Shelf Ground
124791
Step 5 Determine if the system is equipped with the optional 1 RU Distribution Shelf; if so, continue with the “2.2.3.3 Install the 1 RU Distribution Shelf Ground” section on page
2.2.3.3 Install the 1 RU Distribution Shelf Ground
Step 1 Locate the #10 studs at the rear of the 1 RU Distribution Shelf.
Step 2 Using a
Step 3 The connection at the shelf end is made using a
Step 4 To accommodate future upgrades, leave a service loop (1.5ft [60cm]) at the side of the shelf.
Cisco AC/DC Power System User Guide, R1.0